5
—
minimum RPM of auto fan mode, details see Table 2. Jumper switch up is ON and down is
OFF. The position of DIP1 shows below: Fig 4 for single motor; Fig 5 for dual motor.
(Fig 4) Single Motor
(Fig 5) Dual Motor
Site
Function
Description
DIP1-1
Unit type
OFF-2 pipes
ON-4 pipes
DIP1-2 Heater
OFF-Without heater
ON-With heater
DIP1-3
Motor power
OFF-45W
ON-75W
DIP1-4
Control sensor selection OFF-Temp.sensor on PCB
ON-Temp.sensor on controller
DIP1-5
Re-power start type
OFF-Keep OFF
ON-Keep the status as before
(Table 1)
DIP1-6 DIP1-7 DIP1-8
RPM
OFF OFF OFF
300
OFF OFF ON
400
OFF ON OFF
450
OFF ON ON
500
ON OFF OFF
550
ON OFF ON
600
ON ON OFF
650
ON ON ON
700
(Table 2)