6 - SETUP
6.1 - 42AM air heater
To ensure correct air diffusion and to comply with the EN 294 standard relating to safety
zones, you are recommended to position AIR HEATER units at a height of:
■
Between 2.5 and 4.5 metres when wall-mounted
■
Between 4.5 and 10 metres when ceiling-mounted.
The rear of the unit must be at a sufficient distance from the wall to facilitate removal of
the fan motor assembly when necessary.
6.2 -
42AMA Destratifier
It is recommended that destratifiers are positioned at a height of 5 to 15 metres.
The rear of the unit must be at least 145 mm away from any walls to facilitate removal of the fan
motor assembly when necessary.
6.3 - Wall-mounting the 42AM air heater
Installation using wall-mounting support kit
Installation mainly for HEATING purposes
Installation using low wall-mounting support kit
Installation mainly for COOLING or REVERSIBLE purposes
Size
42AM-EC30
42AM-AC35
42AM-EC35
42AM-AC40
42AM-EC40
42AM-AC45
42AM-EC45
42AM-AC50
42AM-EC50
42AM-AC63
42AM-EC63
42AM-AC64
B
Filter box wall bracket
C
Wall bracket (Code 7181226)
D
Drain sleeve in cooling mode, outer diameter 32
X
mm
310
260
Y
mm
390
340
Distance to allow between the wall bracket legs for mounting the AIR HEATER
Dimensions
mm
512
558
610
710
808
943
943
Min: 0.15 m
Min: 0.15 m
Min: 2.5 m
Max: 4.5 m
Min: 4.5 m
Max: 10 m
Min: 0.145 m
Min: 5 m
Max: 15 m