background image

4

shipping damage is filed, the unit, shipping carton, and all
packing must be retained for physical inspection by the trans-
portation company. All units should be stored in the factory
shipping carton with internal packaging in place until installa-
tion.
PROTECTING UNITS FROM DAMAGE — Do  not  apply
force or pressure to the coil, piping, or drain stub-outs during
handling. All units should be handled by the chassis or as close
as possible to the unit mounting point locations. 

The unit must always be properly supported. Temporary

supports used during installation or service must be adequate to
hold the unit securely. To maintain warranty, protect units
against hostile environments (such as rain, snow or extreme
temperature), theft, vandalism, and debris on jobsite. Equip-
ment covered in this manual is not suitable for outdoor installa-
tions. Do not allow foreign material to fall into drain pan. Pre-
vent dust and debris from being deposited on motor, fan wheels
and coils. Failure to do so may have serious adverse effects on
unit operation and in the case of motor and blower assembly,
may result in immediate or premature failure. Failure of any
unit caused by deposits of foreign material on the motor or
blower wheels will not be covered by the manufacturer’s war-
ranty. Some units and/or job conditions may require some form
of temporary covering during construction.
PREPARING JOBSITE FOR UNIT INSTALLATION —
To save time and to reduce the possibility of costly errors, set
up a complete sample installation in a typical room at jobsite.
Check all critical dimensions such as pipe, wire, and duct con-
nections requirements. Refer to job drawings and product
dimension drawings as required. Instruct all trades in their
parts of the installation. Units must be installed in compliance
with all applicable local code requirements.
IDENTIFYING AND PREPARING UNITS —   Be  sure
power requirements match available power source. Refer to
unit nameplate and wiring diagram. In addition:

• Check all tags on unit to determine if shipping screws are

to be removed. Remove screws as directed.

• Rotate the fan wheel by hand to ensure that the fan is

unrestricted and can rotate freely. Check for shipping
damage and fan obstructions. Adjust blower motor as
required. 

Step 2 — Position the Unit

Select the unit position with the following points in mind:

• The unit should be installed on wall studs that are strong

enough to support the total weight of the unit, refrigerant
piping, and condensate.

• The unit should be mounted 8 ft or more from the floor

and if possible, centrally located on the wall from both
ends.

• Proper clearance should be provided on the side and top

as shown in Fig. 3.

• The unit should not be positioned directly above any

obstruction.

• The unit must be installed square and level.

• The condensate drain should have sufficient downward

slope in the condensate flow direction.

Step 3 — Mount the Unit

1.

Detach the mounting plate from the unit.

2.

Place the mounting plate on the wall where the unit will
be installed and mark the mounting holes. See Fig. 4.

Be sure the mounting hole marks are positioned over the
wall studs.

3.

Mark the condensate and refrigerant piping route. If nec-
essary, cut hole in wall to route the piping.

4.

Secure the mounting plate with screws that can support
the weight of the unit. For nominal weight of the unit, see
Table 1. 

DANGER

Units must not be installed where they may be exposed to
potentially explosive or flammable atmosphere. If this
instruction is not followed exactly, a fire or explosion may
result, causing property damage, injury, or loss of life.

CAUTION

When determining the unit mounting location, make sure
that there are no water, plumbing, or electrical lines run-
ning through the wall. Failure to follow this instruction
may result in property damage.

6 in. MIN.

5 in.
MIN.

5 in.
MIN.

A40-1705

Fig. 3 — Required Clearances

Fig. 4 — Mounting Plate

NOTE: All dimensions in inches.

18-1/4 

2-1/4 

28 

MOUNTING
PLATE

UNIT SIZES 007-012

31-3/8 

28-3/4 

2-5/8 

UNIT SIZES 015-018

MOUNTING
PLATE

Содержание 40WAW007

Страница 1: ... 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage Recognize safety information This is the safety alert...

Страница 2: ...eted Failure to follow these proce dures may result in damage to equipment For information about replacement oil type and viscosity see the Single Phase VRF Outdoor Unit installation instructions UNIT 40WAW 007 009 012 015 018 POWER SUPPLY V Ph Hz 208 230 1 60 COOLING CAPACITY Btuh 7 500 9 500 12 000 15 000 19 000 HEATING CAPACITY Btuh 8 500 10 900 13 600 17 000 21 000 INDOOR FAN MOTOR Type AC Mot...

Страница 3: ...ostats controller etc are accounted for whether packaged separately or shipped at a later date Any hidden damage should be re corded a claim should be filed with the transportation compa ny and the factory should be notified In the event a claim for Fig 1 Model Number Nomenclature LEGEND VRF Variable Refrigerant Flow 40 WA W 007 3 40 Indoor Unit Product Type WA Single Phase VRF Voltage V Ph Hz 3 2...

Страница 4: ...lable power source Refer to unit nameplate and wiring diagram In addition Check all tags on unit to determine if shipping screws are to be removed Remove screws as directed Rotate the fan wheel by hand to ensure that the fan is unrestricted and can rotate freely Check for shipping damage and fan obstructions Adjust blower motor as required Step 2 Position the Unit Select the unit position with the...

Страница 5: ...e than 33 ft consider mounting the outdoor unit above indoor unit Refrigerant piping connection between indoor and out door units should be performed once the units are secured at their respective installation locations The refrigeration piping starts at the indoor unit and ends at the outdoor unit The number of bends in the refrigeration piping must be fewer than 15 The refrigerant piping should ...

Страница 6: ...ntrol wiring do not cross as this might cause disturbance on the controls side See Fig 8 for wiring diagram WARNING All units must be wired strictly in accordance with the wir ing diagram furnished with the unit Any wiring different from the wiring diagram could result in personal injury and property damage CAUTION Any original factory wiring that requires replacement must be replaced with wiring ...

Страница 7: ...r C Fan Capacitor CS Water Level Switch DM Pump Motor EEV Electronic Expansion Valve FM Indoor Fan GM Swing Motor HEAT Auxiliary Heater T1 Inlet Air Temperature T2 Coil Temperature T2B Evap Outlet Temperature in Cooling Mode TR Transformer XP1 7 Plug XS1 7 Jack XT1 2 Terminal Block Optional Component or Field Wiring ...

Страница 8: ...le and 4 pin connector from electrical box of indoor unit see Fig 10 For setup in structions refer to the controller installation manual WIRED REMOTE CONTROLLER NON PROGRAM MABLE To connect wired remote controller thermostat to the indoor unit use 5 core shielded cable and 5 pin connec tor from unit display panel see Fig 11 For setup instructions refer to the controller installation manual CENTRAL...

Страница 9: ...ser fan is in operation c Indicator light is showing normal operation and no er ror is indicated NOTE If unit is turned off or restarted there is a 3 minute time delay for the compressor to start from the time power is restored MAINTENANCE EVERY 3 MONTHS Check air filter condition Clean or replace if necessary EVERY 6 MONTHS Follow 3 month maintenance sched ule In addition Clean condensate tray wi...

Страница 10: ... short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance the signal wire from high voltage power wires Signal wire close to electromagnetic source Distance signal wires from electromagnetic source Signal wire length exceeds 360 ft Reduce the signal wire length P...

Страница 11: ...ig B SW2 Settings ON OFF 1 2 3 4 a40 1923 POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON ON Coil Temperature 78 8 F No Heat ON OFF 1 2 3 4 a40 1924 POSITION 3 4 MODE FAN STATUS SP REACHED SP Set Point OFF OFF Cooling Mode Fan On SP Reached Heating Mode Fan On SP Reached Default ...

Страница 12: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400030 01 Printed in U S A Form 40WAW 2SI Pg 12 4 16 Replaces 40WAW 1SI Carrier Corporation 2016 ...

Отзывы: