2
GENERAL
The 40WAV vertical AHU (air-handling unit) is equipped
with a DC motor which provides excellent efficiency. The unit
features dual drain spouts so it can be mounted vertically or
horizontally, and is ideal for closet applications. Through ther-
mostatic control of operations, conditions can be varied to suit
diverse requirements and activities.
The equipment is initially protected under the manufactur-
er’s standard warranty; however, the warranty is provided un-
der the condition that the steps outlined in this manual for ini-
tial inspection, proper installation, regular periodic mainte-
nance, and everyday operation of the unit be followed in detail.
This manual should be fully reviewed in advance before initial
installation, start-up and any maintenance. Contact your local
sales representative or the factory with any questions BEFORE
proceeding.
Table 1 lists physical data for each unit size. See Fig. 1 for
model number nomenclature. Figure 2 shows unit dimensions.
Table 1 — 40WAV Physical Data
LEGEND
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these proce-
dures may result in damage to equipment. For information
about replacement oil type and viscosity, see the Single-
Phase VRF Outdoor Unit installation instructions.
UNIT 40WAV
018
024
030
036
048
POWER SUPPLY (V-Ph-Hz)
208/230-1-60
COOLING CAPACITY (Btuh)
18,000
24,000
30,000
36,000
48,000
HEATING CAPACITY (Btuh)
21,000
27,000
34,000
40,000
54,000
INDOOR FAN MOTOR
Type
DC Motor
Input (W)
220
290
390
350
590
Insulation Class
E
INDOOR COIL
Number of Rows
4 x 2
Fin Spacing (fins/in.)
16
Fin Type
Hydrophylic Aluminum
Tube Diameter, OD (in.)
9
/
32
Tube Type
Inner Groove Tube
Number of Circuits
8
12
INDOOR AIRFLOW (cfm)
Low
460
600
750
900
1120
Medium
550
730
870
1050
1360
High
650
800
1000
1200
1650
EXTERNAL STATIC PRESSURE, HIGH (in. wg)
0.6
0.8
INDOOR NOISE LEVEL (dBA)
Low
43
43
47
52
55
Medium
45
47
49
54
57
High
48
49
52
57
58
SUPPLY DUCT DIMENSIONS, W x D (in.)
18
x 10
5
/
16
19
1
/
2
x 10
5
/
16
DIMENSIONS
Unit Dimensions, W x H x D (in.)
19
5
/
8
x 46
1
/
2
x
20
5
/
8
22
x 54
1
/
2
x
24
Packing Dimensions, W x H x D (in.)
22
3
/
8
x 50
1
/
4
x
25
3
/
8
24
5
/
8
x 58
1
/
4
x
27
3
/
4
Net/Gross Weight (lb)
123/147
163/190
REFRIGERANT TYPE
R-410A
THROTTLE
EXV
DESIGN PRESSURE (psig)
650
REFRIGERANT PIPING (in.)
Liquid Side, OD
1
/
4
3
/
8
Gas Side, OD
1
/
2
5
/
8
CONNECTING WIRING (AWG)
Power Wiring
3 x 14
Signal Wiring
3 x 20
DRAINAGE WATER PIPE DIAMETER, OD (in.)
3
/
4
AWG
— American Wire Gage
EXV
— Electronic Expansion Valve