GENERAL
The 40VMW high wall mount unit provides an efficient way to
heat or cool a space and an attractive appearance. The
equipment is initially protected under manufacturer’s standard
warranty; however, warranty is provided under the condition
that the steps outlined in this manual for initial inspection,
proper installation, regular periodic maintenance, and everyday
operation of the unit be followed in detail. This manual should
be fully reviewed in advance before initial installation, start-up,
and any maintenance. Contact your local sales representative
or the factory with any questions BEFORE proceeding.
Table 1 lists physical data for each unit size. See Fig. 1 for
model number nomenclature. Figures 2 and 3 show unit
dimensions. Table 2 shows components that may or may not be
used for a particular installation.
Table 1 — 40VMW Physical Data
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these
procedures may result in damage to equipment. For
information about replacement oil type and viscosity, see
the Installation, Start-Up, and Service Instructions for the
38VMAH and 38VMAR outdoor units.
UNIT 40VMW
005
007
009
012
015
018
024
030
POWER SUPPLY (V-Ph-Hz)
208/230-1-60
TOTAL COOLING CAPACITY (Btuh)
5,000
7,500
9,500
12,000
15,000
18,000
24,000
30,000
SENSIBLE COOLING CAPACITY (Btuh)
4,060
5,640
6,520
7,930
10,140
12,040
15,330
18,950
HEATING CAPACITY (Btuh)
6,000
8,500
10,900
13,500
17,000
21,000
27,000
34,000
INDOOR FAN MOTOR
Type
DC Motor
Input (W)
11
25
25
30
35
45
75
85
INDOOR COIL
Number of Rows
2
Fin Spacing (fins/in.)
17
20
Fin Type
Hydrophilic Aluminum
Tube Diameter, OD (in.)
0.276
Tube Type
Inner Groove
Number of Circuits
3
4
5
INDOOR AIRFLOW (cfm)
Low
245
245
250
380
440
460
480
Medium
245
270
280
420
470
530
600
High
245
320
360
480
560
650
770
INDOOR NOISE LEVEL (dBA)
Low
31.7
31.2
31.8
32.8
38.4
38.9
36.8
38.1
Medium
31.7
32.2
32.6
34.6
39.6
40.2
42.0
43.6
High
31.7
34.0
34.5
36.4
41.7
41.8
43.2
48.3
UNIT
Unit Dimensions W x H x D (in.)
36 x 11-3/8 x 9
42-1/4 x 12-3/8 x 9
47 x 13-1/2 x 10-1/8
Packing Dimensions W x H x D (in.)
40-1/8 x 15-3/8 x 12-3/8
46-1/2 x 17-1/8 x 12-7/8
50-3/4 x 15-1/8 x 18-1/8
Net/Gross Weight (lb)
28/35
32/40.5
38/50.5
REFRIGERANT TYPE
R-410A
EXPANSION DEVICE
EEV
DESIGN PRESSURE, H/L (psig)
580/320
REFRIGERANT PIPING (in.)
Liquid Side, OD
1
/
4
3
/
8
Suction Side, OD
1
/
2
5
/
8
CONNECTING WIRING
Power Wiring
Sized per NEC and Local Codes Based on Nameplate Electrical Data
Signal Wiring
2-Core Stranded Shielded Cable 18 AWG
DRAINAGE WATER PIPE DIAMETER, OD (in.)
3
/
4
NPT
LEGEND
AWG — American Wire Gage
EEV
— Electronic Expansion Valve
NEC
— National Electrical Code