background image

IMPORTANT: 

If the unit is installed in the ceiling, 

be sure that the ceiling grid is supported

 

separately from the unit. The ceiling grid must not 
be supported by any part of the unit, grille, or any

 

associated wiring or piping work.

6

Step 3 — Install Ductwork

UPFLOW INSTALLATION If return air is to be ducted, 
install duct flush to the floor. Only use the return-air opening

 

provided. All return air must pass through the coil.
HORIZONTAL INSTALLATIONSBe sure installation

 

complies with all applicable building codes, which may require

 

installation of a secondary condensate pan.
NOTE: To ensure proper drainage for horizontal installations, 
unit must be installed so it is within 

1

/

8

-in. pitch of the length

 

and width of the unit. 

1.

Arrange support for unit by setting it in or above

 

secondary condensate pan.

2.

When suspending unit from ceiling, dimples in casing

 

indicate proper location of screws for mounting metal 
support straps.

DUCT CONNECTIONS Connect supply-air duct over 
outside of  

3

/

4

-in. flange provided on supply-air opening. 

Secure duct to flange with proper fasteners for type of duct 
used, and seal duct-to-unit joint.

Duct connection flanges are provided at the discharge air 

unit connection.

Use flexible connectors between ductwork and unit to

 

prevent transmission of vibration. Ductwork passing through

 

unconditioned space must be insulated and covered with vapor 
barrier.
DUCTWORK

    

ACOUSTICAL

    

TREATMENT Metal 

duct systems that do not have a 90-degree elbow and 10 ft of 
main duct to first branch takeoff may require internal acoustical 
insulation lining.

As an alternative, fibrous ductwork may be used if 

constructed and installed in accordance with the latest edition

 

of SMACNA (Sheet Metal and Air-Conditioning Contractors’ 
National Association) construction standard on fibrous glass 
ducts. Both acoustical lining and fibrous ductwork shall 
comply with National Fire Protection Association Standards 
90A or B as tested by UL (Underwriters Laboratories) 
Standard 181 for Class 1 air ducts.

Step 4 — Connect Piping

CONDENSATE PIPING 

  The  unit  is  supplied with a 

3

/

4

-in. female pipe thread drain connection to connect drain

 

piping. When installing the unit, follow these 
recommendations:
• Condensate piping should slope downward in the 

direction of condensate flow, with a minimum gradient 
of 1 in. per 100 inches.

• Condensate piping should be installed in such a way that 

it does not block the front service panel.

• A drain trap may be required by local codes and is 

recommended for odor control.

• The differential height between inlet and outlet should be 

at least 3 inches. The differential height between the 

bottom of the trap and outlet should also be 3 inches. 
See Fig. 4.

Fig. 4 — Condensate Drain Trap

• Auxiliary drain should be connected and run to a location

 

where it is easily visible when it becomes active, 
suggesting a problem with the main drain system.

• When multiple units are connected to a common

 

condensate drain, ensure that the drain is large enough to

 

cope with the volume of condensate from all units. It is 
also recommended to have an air vent in the condensate 
piping to prevent air locks.

• Insulate the drain line to prevent sweating and provide 

proper support to prevent undue stress.

• Condensate piping must not be installed where it may be 

exposed to freezing temperatures.

REFRIGERANT PIPING

CAUTION

When connecting from an indoor unit to an outdoor unit, 
the isolation valve at the outdoor unit should be in the 
closed position throughout the refrigerant piping process. 
Failure to follow this procedure may result in equipment 
damage.

When connecting from an indoor unit to an outdoor unit, 

follow these procedures:
• Check for maximum height drop and length of 

refrigerant piping between the indoor and outdoor unit. If 
the difference is more than 33 ft, consider mounting the 
outdoor unit above indoor unit.

• Refrigerant piping connection between indoor and

 

outdoor units should be performed once the units are 
secured at their respective installation locations.

• The refrigeration piping starts at the indoor unit and ends 

at the outdoor unit. 

• The number of bends in the refrigeration piping must be 

fewer than 15.

• The refrigerant piping should be dry and free of dust and

 

other contaminants.

• The bending angle of the refrigerant pipe should not 

exceed 90 F and the bending radius should be as large as 
possible to prevent any breakage in piping.

• Use proper cutting and flaring tools to avoid leakage.

• Use a torque wrench for flare nuts. Refer to Table 3 fo

flare nut torque recommendations.

Table 3 —Flare Nut Torque Recommendations

Outside Diameter (in.)

Recommended Torque (ft-lb)

1/4

15

3/8

26

1/2

41

5/8

48

Содержание 40VMV012

Страница 1: ...Canadian Electrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal...

Страница 2: ...at the steps outlined in this manual for initial inspection proper installation regular periodic maintenance and everyday operation of the unit be followed in detail This manual should be fully review...

Страница 3: ...20 1260 Medium 320 510 680 850 1020 1360 1530 High 400 600 800 1000 1200 1600 1800 EXTERNAL STATIC PRESSURE in wg 0 8 INDOOR UNIT NOISE LEVEL dBA Low 34 5 34 4 37 9 44 4 39 3 43 8 47 9 Medium 34 5 37...

Страница 4: ...mensions shown in inches 40VMV UNIT SIZE A B C D 012 030 46 1 2 19 5 8 18 21 5 8 036 054 54 1 2 22 19 1 2 24 RIGHT SIDE A FRONT B C D DRAIN PIPE LEFT SIDE AIR RETURN REFRIGERANT SIDE PIPE LIQUID REFRI...

Страница 5: ...al dimensions such as pipe wire and duct connections requirements Refer to job drawings and product dimension drawings as required Instruct all trades in their parts of the installation Units must be...

Страница 6: ...ould slope downward in the direction of condensate flow with a minimum gradient of 1 in per 100 inches Condensate piping should be installed in such a way that it does not block the front service pane...

Страница 7: ...rect wiring or voltage is not covered by warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls that are used with the unit See Table 4 for...

Страница 8: ...ce N C 5 N 1 1 5 C Voltage range 0 24V AC DC Current range 0 1A FAN CTON HTON AUXH RED BLACK XS4 XP4 XS5 XP5 XS6 XP6 XT1 BLACK RED Y G CN27 CN3 CN18 CN31 CN54 CN4 CN15 CN19 CN8 CN21 CN12 CN26 CN14 CN2...

Страница 9: ...e to buy communication wires from Carrier connect the indoor unit side of the communication wires using the connector provided with the accessories as shown in Fig 11 13 CAUTION Failure to follow thes...

Страница 10: ...Fig 11 Connecting the Communication Cable to Indoor Unit to Outdoor Unit Using the Supplied Connector Connector in accessory kit Connector on indoor unit Communication cable in field 10...

Страница 11: ...oor To Sub MDC To outdoor Indoor unit 1 L1 L2 L3 L3 L3 L3 L4 L5 L6 L7 L8 L9 L10 1 1 L Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 HA HB HA HB HA HB HA HB HA HB HA HB Touch sc...

Страница 12: ...t Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 P Q HA HB HA HB HA HB HA HB HA HB HA HB Network Resistor Maximum wiring length L1 L3 3937 ft 16 AWG 2 Core Strande...

Страница 13: ...he power is restored MAINTENANCE CAUTION When servicing or repairing this unit use only factory approved service replacement parts Refer to the rating plate on the unit for complete unit model number...

Страница 14: ...o an indoor unit Press ROOM TEMP and SWING simultaneously for 3 seconds If there is no address for this indoor unit the display shows FE 00 see Fig 16 otherwise the display shows the current address o...

Страница 15: ...M Electronically Erasable Programmable Read only Memory EEV Electronic Expansion Valve MDC Multiport Distribution Controller ERROR CODE MODE STATUS NO ERROR Setting Temperature Starting Shutdown Stand...

Страница 16: ...ignal wire close to electromagnetic source Distance signal wires from electromagnetic source PC board fault Replace PC board E2 E4 E5 Check Temperature Sensor Loose connection at port on PC board Tigh...

Страница 17: ...1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 OFF Normal Mode Default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION OFF Standard...

Страница 18: ...speed M speed 500 AIRFLOW cfm L speed 700 300 400 600 Upper Limit of ESP Fig B 40VMV018 Fan Curves Fig A 40VMV012 Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 EXTERNAL STATIC PRESSURE in wg H speed 500 A...

Страница 19: ...0VMV048 Fan Curves 0 00 0 20 0 40 0 60 0 80 1 00 1000 1200 1400 1600 1800 2000 EXTERNAL STATIC PRESSURE in wg H speed M speed Upper Limit of ESP L speed AIRFLOW cfm Fig G 40VMV054 Fan Curves 0 00 0 20...

Страница 20: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 16 40VMV001 01 Printed in U S A Form 40VM 2SI Pg 20 2 17 Replaces 40VM 1...

Отзывы: