2
GENERAL
The 40VMV vertical AHU (air-handling unit) is equipped with
a DC motor. The unit features dual drain spouts so it can be
mounted vertically or horizontally, and is ideal for closet
applications. Through thermostatic control of operations,
conditions can be varied to suit diverse requirements and
activities.
The equipment is initially protected under the manufacturer’s
standard warranty; however, the warranty is provided under the
condition that the steps outlined in this manual for initial
inspection, proper installation, regular periodic maintenance,
and everyday operation of the unit be followed in detail. This
manual should be fully reviewed in advance before initial
installation, start-up, and any maintenance. Contact your local
sales representative or the factory with any questions BEFORE
proceeding.
Table 1 shows components that may or may not be used for a
particular installation. Table 2 lists physical data for each unit
size. See Fig. 1 for model number nomenclature. Fig. 2 shows
unit dimensions.
Fig. 1 —Model Number Nomenclature
Table 1 —
Components Shipped With Unit
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these
procedures may result in damage to equipment. For
information about replacement oil type and viscosity, see
the Installation, Start-Up, and Service Instructions for the
38VMAH and 38VMAR outdoor units.
NAME
SHAPE
QUANTITY
FUNCTION
Copper pipes
2
Reducer for smaller pipe diameter (only for size 018 unit).
Drain plug
2
Plug for drain pan outlet
Wire grommet
2
For wire routing
Tie rope
3
————————————————————
Screw
4
————————————————————
PQ connection wire
2
To connect the outdoor unit, indoor unit and sub MDC.
Connecting wire
1
For occupancy sensor
No Beep Harness
1
Prevent beeping noise
LEGEND
MDC — Multiport Distribution Controller
Equipment Type
40
— Indoor Fan Unit Coil
Voltage (V-Ph-Hz)
VM
— VRF
Product Type
3
— 208/230-1-60
Blank
Model Type
V
— Vertical AHU
—
Capacity (Btuh)
012
— 12,000
018
— 18,000
024
— 24,000
030
— 30,000
036
— 36,000
048
— 48,000
40
054
— 48,000
VM
V
18
--
3
A
A
—
Design Revision
LEGEND
VRF
— Variable Refrigerant Flow