background image

8

Step 2 — Position the Unit

Install  the  unit  in  a  location  that  meets  the  following

requirements:
• Allow adequate space for installation, service clearance,

piping, electrical connections, and necessary ductwork.

For specific unit dimensions, refer to Table and Fig. 2.

Allow clearance according to local and national codes. 

• Confirm that the ceiling is able to support the weight of

the unit. See Table 2 for nominal weight.

• There should be enough room within the false ceiling for

installation and maintenance. See Fig. 8.

• The false ceiling should be horizontal and level.
• Install the unit in a location within the room that allows

uniform air flow in all directions.

Fig. 8 —False Ceiling Installation

Select the unit position with the following points in mind:
• The unit should be installed in a position that is suitable

to support the total weight of the unit, refrigerant piping,

and condensate.

• Proper  access  should  be  provided  for  maintenance  of

refrigerant  piping,  EEV  (electronic  expansion  valve),

electrical  box,  and  condensate  pump.  A  two-foot

clearance is recommended all around the unit.

• The  unit  should  not  be  positioned  directly  above  any

obstruction.

• The unit must be installed square and level.

Step 3 — Mount the Unit

INSTALLING HANGER BOLTS  — Install  the  hanger

bolts at the locations shown in Fig. 2. Use 

3

/

8

-inch all-threaded

rod. For unit weight, see Table 2.
MOUNTING THE UNIT — Lift the unit on to the hanging

rods for mounting:

1. Use rods and fasteners to suspend the unit at the factory-

provided mounting holes.

2. Adjust the height of the unit until the bottom is level with

the false ceiling. There must be adequate space to provide

enough pitch for the drain.

3. Secure the unit in position with locknuts and washers on

both  sides  of  the  mounting  bracket.  Ensure  that  the

threaded  rod  does  not  protrude  more  than  two  inches

below the mounting brackets as shown in Fig. 9.

INSTALLING THE DUCT — Connect the return and supply

ducts  to  the  duct  collars  provided  on  the  unit.  Adequate

distance  between  the  return  and  supply  diffusers  should  be

maintained to avoid short circulation of air within the space.

The filter is located on the return side of the unit, on the rear or

bottom, depending on the return air inlet arrangement.

RETURN AIR ARRANGEMENT — Based on the return air

arrangement requirement in the field, the unit can be modified

from  rear  return  to  bottom  return.  Follow  the  instructions

below to change the return air arrangement. 

Remove Air Filter Frame and Cover Plate

1. Remove the screws that secure the filter frame to the rear

of the unit.

2. Remove the screws that secure the return air cover plate

to the bottom of the unit and set the cover plate aside. See

Fig. 10.

Fig. 10 —Removing Air Filter Frame and Cover 

Plate

DANGER

Units must not be installed where they may be exposed to

potentially  explosive  or  flammable  atmosphere.  If  this

instruction is not followed, a fire or explosion may result,

causing property damage, injury, or loss of life.

WARNING

The  equipment  and  its  ducting  (supply  and  return  air

ducts)  are  intended  for  use  in  one  room  only.  Do  not

install ductwork from a single unit to multiple rooms.

WARNING

The  ducting  for  the  7K  (40VML007--3)  and  9K

(40VML009--3)  (supply  and  return  air  ducts)  is

intended  for  use  in  one  room  only.  Do  not  install

ductwork from a single unit to multiple rooms for these

two models.

IMPORTANT: Be sure that the ceiling grid is supported

separately from the unit. The ceiling grid must not be

supported  by  any  part  of  the  unit  or  any  associated

wiring or piping work.

MINIMUM DRAIN
TILT 1/100

a40-1849

Fig. 9 — Threaded Rod

INDOOR UNIT

LEVELING

NUT

” THREADED

ROD

MOUNTING

BRACKET

SUPPLY AIR

OPENING

FRONT VIEW

When the unit is

level, tighten

nut to secure

the position of

the mounting

bracket on the

threaded rod.

Side rail

Dentilation panel

RETURN AIR

RETURN AIR

FILTER FRAME

COVER PLATE

Содержание 40VML007-024

Страница 1: ...could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage Recognize safety information This is th...

Страница 2: ...OT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the actual time r...

Страница 3: ...0 37 0 Medium 32 0 34 6 35 2 38 0 38 8 High 34 0 34 5 37 0 36 7 40 2 41 3 UNIT Unit Dimensions W x H x D in 30 3 4 x 8 1 4 x 19 3 4 39 1 4 x 8 1 4 x 19 3 4 48 x 8 1 4 x 19 3 4 Packing Dimensions W x...

Страница 4: ...015 018 36 1 4 39 3 8 28 7 8 32 1 4 7 7 8 37 3 4 024 44 7 8 48 37 5 8 41 46 1 2 AIR FILTER ELECTRICAL CONTROL BOX SIDE VIEW FRONT VIEW REAR VIEW BOTTOM VIEW P TOP VIEW SUSPENSION BRACKETS 4 P N 3 4 20...

Страница 5: ...M Low ax ESP er lim it of ESP P Upper limit of ESP p e r l i m Min ES U p M a x E S P i t o f E S P H S M S L S H S M S L S ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Poin...

Страница 6: ...ESP r l i m M L o w a x e E S P i t o f E S P Min p e r l i m ESP Upper limit of ESP U p M a x E S P i t o f E S P Fig 6 Size 018 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Ma...

Страница 7: ...ture theft vandalism and debris on jobsite Equipment covered in this manual is not suitable for outdoor installations Do not allow foreign material to fall into drain pan Prevent dust and debris from...

Страница 8: ...wo inches below the mounting brackets as shown in Fig 9 INSTALLING THE DUCT Connect the return and supply ducts to the duct collars provided on the unit Adequate distance between the return and supply...

Страница 9: ...piping The highest point in the condensate piping should be as close to the unit as possible See Fig 15 Condensate piping should slope downward in the direction of condensate flow with a minimum grad...

Страница 10: ...ge to or failure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls...

Страница 11: ...let Pipe Temperature Sensor XP1 4 Connectors XS1 4 XT1 2 Terminal Block Optional Component or Field Wiring EEV FM ALARM PUMP CN24 N3 CN1 C 8 CN2 EARTH Y G CN15 CN9 CN17 Y G L1 L2 controller To wired c...

Страница 12: ...Connector 2 Strip a suitable length of the insulation layer as shown in Fig 20 below Fig 20 Stripping The Wire 3 Use a suitable screwdriver to fix the communication wire on the outdoor unit communicat...

Страница 13: ...indoor To No 3 indoor To No 4 indoor To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoo...

Страница 14: ...ontroller HA HB L1 L3 L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resisto...

Страница 15: ...e unit ON in cooling mode The pump comes on Watch the end of the drain pipe for any water It may take time for the water to travel depending on the length of the drain pipe 4 During this test check an...

Страница 16: ...oller 40VM900001 Indoor unit addressing can be performed using the wireless remote controller When using the wireless controller the user must maintain a line of sight with the receiver on the indoor...

Страница 17: ...32 2 Press TEMP UP or TEMP DOWN to move the cursor and choose IDU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set as shown in Fig 33...

Страница 18: ...ting Cooling Mode Conflict E1 None Communication Error Between Indoor and Outdoor Unit E2 None Check Indoor Ambient Temperature Sensor T1 E4 None Check Evaporator Temperature Sensor T2B E5 None Check...

Страница 19: ...board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance...

Страница 20: ...the default settings v POSITION 1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 IN...

Отзывы: