Carrier 40VMA Series Скачать руководство пользователя страница 11

11

REFRIGERANT PIPING

When connecting refrigerant piping from an indoor unit to an

outdoor unit, follow these guidelines:
• Check the maximum height drop and length of

refrigerant piping between the indoor and outdoor units.

To ensure the drop and length are acceptable, refer to the

refrigerant piping allowable limits in the outdoor unit

installation manual.

• The number of bends in the refrigeration piping must be

fewer than 15.

• Refrigerant piping connection between indoor and

outdoor units should be performed once the units are

secured at their respective installation locations.

• The refrigeration piping starts at the indoor unit and ends

at the outdoor unit or Multi-Port Distribution Controller

(MDC) (Heat Recovery systems).

• The refrigerant piping should be dry and free of dust and

other impurities.

• The bending angle of the refrigerant pipe should not

exceed 90° and the bending radius should be as large as

possible to prevent any breakage in piping.

• Use proper cutting and flaring tools to avoid leakage.

• Use a torque wrench for flare nuts. Refer to Table 3 for

flare nut torque recommendations.

Table 3 —Flare Nut Torque Recommendations

• Before insulating the suction and liquid refrigeration

pipes, perform pressure and leak tests. For details, see

the outdoor unit installation manual. Insulating both

suction and liquid refrigerant pipes is mandatory.

• Vacuuming and charging of the system should be carried

out as described in the outdoor unit installation manual.

Step 5 — Complete the Electrical 

Connections — 

Installation of wiring must conform with local building codes

and with National Electric Code ANSI/NFPA 70, current

editions. Units must be electrically grounded in conformance

with the code. In Canada, wiring must comply with CSA

C22.1, Electrical Code. 

This equipment in its standard form is designed for an

electrical supply of 208/230-1-60. Any damage to or failure of

units caused by incorrect wiring or voltage is not covered by

the warranty.
Electric wiring must be sized to carry the full load amp draw of

the motor, starter, and any other controls that are used with the

unit. See Table 4 for electrical data.

Table 4 —40VMA Electrical Data

LEGEND
MCA - Minimum Circuit Amps
MOPD - Maximum Overcurrent Protective Device

After the pipe work is complete, the electrical supply can be

connected by routing the cable through the appropriate casing

holes or knockouts and connecting the supply and ground

cables to the unit’s power terminal.
Be sure the power wiring and control wiring do not cross, as

this might cause disturbance on the controls side. See Figs. 17

and 18 for the wiring diagram.

NOTE:

 The indoor unit requires its own power supply. Indoor

units are not powered through outdoor units.

CAUTION

When connecting from an indoor unit to an outdoor unit,

the isolation valve at the outdoor unit should be in the

closed position throughout the refrigerant piping process. 
Failure to follow this procedure may result in equipment

damage.

Outside Diameter

Recommended Torque (FT-LB)

1

/

4

15

3

/

8

26

1

/

2

41

5

/

8

48

WARNING

Electrical shock can cause personal injury and death.

Disconnect power supply before making wiring

connections. There may be more than one disconnect

switch. Tag all disconnect locations to alert others not to

restore power until work is completed.

WARNING

All units must be wired strictly in accordance with the

wiring diagram furnished with the unit. Any wiring

different from the wiring diagram could result in personal

injury and property damage.

CAUTION

Any original factory wiring that requires replacement must

be replaced with wiring material having a temperature

rating of at least 105°C.
Ensure supply voltage to the unit, as indicated on the serial

plate, is not more than 10% over the rated voltage or 10%

under the rated voltage.
Failure to follow these recommendations may result in

equipment damage.

40VMA Unit Size

Power Supply

MCA

MOPD

36

5.7

15

48

6.3

54

6.9

72

8.5

96

10.0

Содержание 40VMA Series

Страница 1: ...ert symbol When this symbol is displayed on the unit and in instructions or manuals be alert to the potential for personal injury WARNING Electrical shock can cause personal injury and death Shut off...

Страница 2: ...size Figures 2 3 and 4 show the unit s dimensions Fig 4 Fig 8 shows fan performance curves Fig 1 Model Number Nomenclature Table 1 Components Shipped with Unit LEGEND VRF Variable refrigerant Flow NAM...

Страница 3: ...Low 43 8 43 4 43 9 48 5 47 7 Medium 47 8 47 8 47 8 50 0 50 8 High 49 5 50 4 51 4 52 1 53 5 UNIT Unit Dimensions W x H x D in 51 3 16 X16 1 2 X27 3 16 56 11 16 X20 X36 3 8 Packing Dimensions W x H x D...

Страница 4: ...4 DIMENSIONS Fig 2 40VMA036 054 Dimensions NOTE All dimensions are shown in inches...

Страница 5: ...5 DIMENSIONS CONT Fig 3 40VMA072 096 Dimensions NOTE All dimensions are shown in inches...

Страница 6: ...W G Upper Lim it of ESP 0 44 in W G Upper Limit of ESP 0 2 in WG Lower Limit of ESP 0 44 in WG Lower Limit of ESP 0 2 in WG ESP Fan Speed Range of Available Airflow Rate in H Speed Max Point Rating P...

Страница 7: ...in WG H Speed M Speed L Speed H Speed M Speed L Speed H Speed M Speed L Speed ESP Fan Speed Range of Available Airflow Rate in H Speed Max Point Rating Point Min Point Max CFM SP in Mid CFM SP in Min...

Страница 8: ...nit mounting point locations The unit must always be properly supported Temporary supports used during installation or service must be adequate to hold the unit securely To maintain warranty protect u...

Страница 9: ...t should be installed in a position that is suitable to support the total weight of the unit refrigerant piping and condensate Proper access should be provided for maintenance for refrigerant piping E...

Страница 10: ...t as possible See Fig 14 Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 inch per 100 inches See Fig 15 Fig 14 Condensate Piping When multiple...

Страница 11: ...damage to or failure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other con...

Страница 12: ...T2B Outlet Pipe Temperature Sensor XP1 8 Connectors XS1 4 Connector XT1 2 Terminal Block Optional Component or Field Wiring SW8 3GOT HUGXJ CN3 CN18 CN24 CN11 CN5 CN52 CN54 CN12 CN15 CN9 CN26 CN8 EARTH...

Страница 13: ...XS1 4 Connector XT1 2 Terminal Block Optional Component or Field Wiring SW8 3GOT HUGXJ CN3 CN18 CN24 CN11 CN5 CN52 CN54 CN12 CN15 CN9 CN26 CN8 EARTH 7 BLUE 7 WHITE 7 7 RED Display board To wired contr...

Страница 14: ...rs should be installed in a position that maintains good temperature control Position the thermostat approximately 48 inches above floor level Do not position thermostat where it can be directly affec...

Страница 15: ...connect the indoor unit side of the communication wires using the connector provided with the accessories as shown in Fig 26 See Fig 27 and 28 for typical communication wiring of the heat pump and he...

Страница 16: ...RRU 7R 6XE 0 7R RXWGRRU L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 wired controller Maximum wiring length L1 L2...

Страница 17: ...0 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Maximun wiring length IW RUH 6WUDQGHG 6KLHOG IW RUH 6WUDQGHG 6KLHOG IW RUH 6WUDQGHG 6KLHOG IW RUH...

Страница 18: ...ration is normal if applicable e No abnormal vibration or noise is noticed 3 While the system is in operation check the following on the outdoor unit a No abnormal vibration or noise is noticed b Cond...

Страница 19: ...vides an example of the unit 1 Remove the 12 screws from the fixed Safety Drain Tray and take off the tray as shown in Fig 31 2 Take off the tray along the direction of the arrow as shown in Fig 31 3...

Страница 20: ...n tray as shown in Fig 32 2 Remove all four bolts from the fan assembly as shown in Fig 33 3 Horizontally push fan assembly until it cannot not move any further 4 Lift up slightly and take down to rem...

Страница 21: ...ule In addition Ensure all the electrical connections are secure Check the condensate pump operation if applicable Check the heating and cooling action to confirm proper operation INDOOR UNIT ADDRESSI...

Страница 22: ...nd hold LOCK for at least ten seconds and press to query the address Programmable Controller 40VM900003 When setting an address connect only one wired controller to an indoor unit 1 Press FAN and BACK...

Страница 23: ...ystem Defrost OFF Operation Light ON Only FAN dd None Heating Cooling Mode Conflict E1 Communication Error Between Indoor and Outdoor Unit E2 Check Indoor Ambient Temperature Sensor T1 E3 Check Room T...

Страница 24: ...d fault Replace PC board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagneti...

Страница 25: ...atalog No 20 40VMA001 01 Printed in U S A Form 40VMA 2SI Pg 25 2 20 Replaces 40VMA 1SI Carrier Corporation 2020 APPENDIX A DIP SWITCH SETTINGS There are two DIP switches on the main board Figures A an...

Отзывы: