background image

28

Pulley and Drive Adjustment

To obtain desired fan speed, refer to the fan motor, drive data and

performance data in Tables 13-26

 

and adjust fan motor pulley as

follows:

1. Remove  belt  from  fan  motor  pulley  after  loosening  motor

from motor base.

2. Loosen  setscrew  in  moveable  flange  of  pulley.  Screw

moveable flange toward fixed flange to increase the fan speed

and away from fixed flange to reduce speed. Before tighten

-

ing setscrew, make certain that setscrew is over nearest flat

surface of pulley hub. (See Fig. 27.)

Condensate Drains

Keep condensate drains free of dirt and foreign matter.

Return-Air Filters

Refer to Replacing Filters section for filter accessibility and re

-

moval. Replace with clean filters of the sizes listed in Tables 1-6.

Chilled Water Coil Freeze Protection

Shut off water supply to unit. Remove side panel of unit and re

-

move vent and drain plugs in top and bottom of coil header. Drain

coil and blow out remaining water. Reinstall plugs and side panel.

Alternative freeze protection methods follow:

• Circulate hot water within the water coil’s supply main or

supplementary space heating.

• Close off supply lines to unit and open a union or field-

supplied drain valve in the return line.

• After draining as much water as possible from coils, add

sufficient  antifreeze  to  prevent  residual  water  in  the  coil

from freezing.

• Add a sufficient quantity of non-corrosive antifreeze to the

entire system to prevent all water within the system from

freezing.

Coil Removal

Remove unit panels and corner posts as required. Disconnect coil

connections and remove fastening screws. Remove coil through

end or side sections of unit.

Cleaning Cooling Coil

Remove return-air filters. Remove any heavy dirt that may have

accumulated on underside of coil. Coil can be cleaned more easily

with a stiff brush, vacuum cleaner, or compressed air when coil is

dry.  If  coil  is  wet  or  if  water  is  to  be  used  for  cleaning,  guard

against splashing water on electrical components or damaging sur

-

rounding area. Clean coil baffles as applicable and check for tight

fit to be sure air does not bypass coil.

Cleaning Insulation

The insulation contains an immobilized antimicrobial agent that

helps  inhibit  the  growth  of  bacteria  and  fungi.  Clean  the  inner

surface  of  the  insulation  according  to  the  separate  maintenance

instructions shipped with the unit.

Replacing Filters 

Filters can be removed and installed from either side of the unit.

Install new filters in units that have one fan as follows:

1. Remove the side access panel (retain screws).

2. Remove the filter retainer clip (see Fig. 28).
3. Remove old filters by lifting and tilting them out of the filter

track.  (See  Fig.  16  and  29.)  Use  the  factory-supplied  filter

hook to slide filters within reach for removal. The filter hook

is shipped inside the unit in the filter track.

4. Reverse the procedure to install new filters.

Fig. 28 — 

Remove Filter Retainer Clip

Fig. 29 — 

Filter Removal/Replacement

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution could cause equipment damage.

Increasing fan speed produces a greater load on motor.

Do not exceed rated capacity of motor.

IMPORTANT:  Draining  from  return  line  will  not  completely

drain water from coils.

CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution could cause equipment damage.

Do not operate unit without air filters.

Slide

Filter
Retainer
Clip

Содержание 40RU 25

Страница 1: ...performed by trained service personnel When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply...

Страница 2: ...mm Right Side 3 1 2 ft 1067 mm Left Side 2 1 2 ft 762 mm For units equipped with an economizer refer to the accessory in stallation instructions for additional clearance requirements Be sure floor wa...

Страница 3: ...3 Fig 1 Dimensions Size 25...

Страница 4: ...4 Fig 1 Dimensions Size 25 cont...

Страница 5: ...5 Fig 2 Dimensions Sizes 28 and 30...

Страница 6: ...6 Fig 2 Dimensions Sizes 28 and 30 cont...

Страница 7: ...o of Splits 2 2 2 No of Circuits per Split 18 20 24 Split Type Percentage Face 50 50 Rows Fins in 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 1 1 8 2 1 3 8 2 1 3 8 DX Coil...

Страница 8: ...2 No of Circuits per Split 18 20 24 Split Type Percentage Face 50 50 Rows Fins m 4 591 4 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 1 1 8 2 1 3 8 2 1 3 8 DX Coil Liquid Refri...

Страница 9: ...No of Circuits per Split 2 Split Type Percentage Face 50 50 Rows Fins in 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 1 1 8 DX Coil Liquid Refrigerant ODF 2 5 8 Steam Coil In MPT 1...

Страница 10: ...50 Rows Fins m 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 1 1 8 DX Coil Liquid Refrigerant ODF 2 5 8 Steam Coil In MPT 1 2 1 2 Steam Coil Out MPT 1 1 1 2 Hot Water Coil In MPT 1 2 H...

Страница 11: ...4 15 5 Face Area sq ft Lower 8 3 12 4 12 4 Rows Fins in 3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 2 1 3 8 ODM 2 2 1 8 ODM 2 2 1 8 ODM Chilled Water Out 2 1 3 8 ODM 2 2 1 8 ODM 2 2 1 8...

Страница 12: ...e Area sq m Lower 0 77 1 15 1 15 Rows Fins m 3 591 3 591 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 2 1 3 8 ODM 2 2 1 8 ODM 2 2 1 8 ODM Chilled Water Out 2 1 3 8ODM 2 2 1 8 ODM 2 2 1 8...

Страница 13: ...Nominal Tonnage 25 20 Tons 28 25 Tons 30 30 Tons Not Used A Placeholder Indoor Fan Options 1 Fan Drive and Motor Low Motor Efficiency Standard 2 Fan Drive and Motor Med Motor Efficiency Standard 3 Fan...

Страница 14: ...wing See Fig 7 for preferred suspension technique The unit needs support underneath to prevent sagging Fig 7 Preferred Suspension Technique LEGEND Accessory Line Alternate Air Intake and Discharge Air...

Страница 15: ...iping See Fig 8 which also lists recommended knockouts and access holes to use for each 40RU unit size Recommended fittings are listed in Table 8 The sensor bulb capillary tubes must be routed from th...

Страница 16: ...ms Min 10 Diams 8 Diams Min TXV Sensing Bulb Equalizer Line Sight Glass TXV Solenoid Valve Filter Drier TXV Sensing Bulb TXV 8 Diams Min 15 Diams Min 10 Diams Indoor Coil Equalizer Line First On Last...

Страница 17: ...wer 1 1 8 Street Elbow 1 1 8 Nipple 7 5 8 L 1 1 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 6 1 2 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Street Elbow 5 8 Nipple 9 1 2 L 5 8 Long...

Страница 18: ...g Radius Elbow 1 3 8 Nipple 23 1 4 L 1 3 8 Long Radius Elbow 40RUS 28 30 5 Supply Lower 2 1 8 Long Radius Elbow 2 1 8 Nipple 3 1 2 L 2 1 8 Long Radius Elbow 6 Return Lower 2 1 8 Long Radius Elbow 2 1...

Страница 19: ...r piping consult the Carrier System Design manual See Fig 12 for an example of a typical installation Recommended fittings are listed in Table 8 To access 40RUS coil vents and drains remove the unit s...

Страница 20: ...to pitch towards the side of the unit with the drain connection See Fig 14 Loosen the 2 screws next to the drain outlet at both ends of the unit push drain pan down in the slots near the drain connec...

Страница 21: ...ARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Do not use gas piping as an electrical ground Unit cabinet must have an uninterrupted unbroken el...

Страница 22: ...n with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclosure a...

Страница 23: ...ct to the unit s return air inlet near the filter rack using a canvas connection to prevent transmission of unit vibration If the duct blocks off the unit s access panel provide a slip joint in the du...

Страница 24: ...24 Fig 19 Typical Fan Discharge Connections for Multiple Fan Units Fig 20 Duct Flange Installation Duct Flanges...

Страница 25: ...ilters Testing for cooling heating system leaks Checking of all electrical connections Most unit service can be performed by removing one or both of the unit s side panels Coil cleaning removal or ins...

Страница 26: ...should setscrew work itself loose Fig 24 Fan Shaft Bearing Individual Fan Wheel Adjustment Loosen the 2 locking bolts holding the fan wheel hub to shaft See Fig 23 Position fan wheel in center of the...

Страница 27: ...eys 2 Align pulleys visually and tighten setscrews on fan pulley to lock it in place 3 Use the methods shown in Fig 27 to check proper pulley alignment Fig 27 Fan Pulley Adjustments 4 If pulleys are n...

Страница 28: ...ening screws Remove coil through end or side sections of unit Cleaning Cooling Coil Remove return air filters Remove any heavy dirt that may have accumulated on underside of coil Coil can be cleaned m...

Страница 29: ...10 0 10 0 Frame NEMA S213T D215T D215T Shaft Dia in 1 3 8 1 3 8 1 3 8 Table 15 Fan Motor Data Standard Motor SI UNIT 40RUA 25 40RUQ 25 40RUS 25 40RUA 28 40RUS 28 40RUA 30 40RUS 30 208 230 3 60 and 460...

Страница 30: ...ximum Full Turn From Closed Position 6 6 6 Shafts Center Distance in 9 12 10 99 6 67 9 43 6 67 9 43 Table 18 Medium Static Drive Data 60 Hz English UNIT 40RUA 25 40RUQ 25 40RUS 25 40RUA 28 40RUS 28 40...

Страница 31: ...um Full Turn From Closed Position 6 6 6 Shafts Center Distance in 8 16 10 02 6 67 9 43 6 67 9 43 Table 20 Standard Drive Data 60 Hz SI UNIT 40RUA 25 40RUQ 25 40RUS 25 40RUA 28 40RUS 28 40RUA 30 40RUS...

Страница 32: ...255 0 255 0 255 Maximum Full Turn From Closed Position 6 6 6 Shafts Center Distance mm 232 279 169 240 169 240 Table 22 High Static Drive Data 60 Hz SI UNIT 40RUA 25 40RUQ 25 40RUS 25 40RUA 28 40RUS...

Страница 33: ...7 958 11 27 991 11 99 1024 12 73 UNITa AIRFLOW cfm b EXTERNAL STATIC PRESSURE in wg 1 4 1 6 1 8 2 0 2 2 2 4 rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp 40RUA 25 40RUQ 25c 40RUS 25 6 000 954 3 83 1...

Страница 34: ...05 7 51 7080 13 82 6 59 14 17 6 85 14 81 7 36 15 40 7 88 15 97 8 40 16 52 8 94 17 06 9 49 UNITa AIRFLOW L s b EXTERNAL STATIC PRESSURE kPa 350 400 450 500 550 600 r s kW r s kW r s kW r s kW r s kW r...

Страница 35: ...865 9 45 884 9 81 921 10 52 956 11 24 991 11 98 1025 12 75 1059 13 54 UNITa AIRFLOW cfm b EXTERNAL STATIC PRESSURE in wg 1 4 1 6 1 8 2 0 2 2 2 4 rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp 40RUA 2...

Страница 36: ...13 04 5 18 13 40 5 42 14 07 5 90 14 71 6 39 15 34 6 90 15 97 7 44 16 61 7 98 7080 14 42 7 05 14 74 7 31 15 36 7 84 15 94 8 38 16 51 8 93 17 08 9 51 17 65 10 10 UNITa AIRFLOW L s b EXTERNAL STATIC PRE...

Страница 37: ......

Страница 38: ...the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 40RU 07SI Printed in U S A Form 40RU 7SI Rev B Pg 38 7 22 Replaces...

Страница 39: ...cluding main power supply TIGHT Y N ______________ HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS Y N _________ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINA...

Страница 40: ..._____ ____________ INDOOR UNIT ENTERING AIR DB TEMP ______________ ____________ INDOOR UNIT ENTERING AIR WB TEMP ______________ ____________ INDOOR UNIT LEAVING AIR DB TEMP ______________ ____________...

Отзывы: