Condensate Drain
Install a trapped condensate drain line to unit connection as shown
in Fig. 13
.
The unit drain connection is a PVC stub. (See Fig. 14.)
Some areas may require an adapter to connect to either galvanized
steel or copper pipe. For these applications, install a field-supplied
threaded PVC adapter.
Fig. 13 —
Condensate Drain
NOTE: A trap must be installed in the condensate drain line to en
-
sure that the static pressure of fans is balanced with the water col
-
umn in the drain line and that condensate can drain completely
from pan. Without a trap, air can be drawn up drain line until water
level in condensate pan becomes equal to static pressure created
by fans, preventing complete drainage. Conditions will worsen as
filters become dirty.
Install clean-out plugs in trap. Pitch drain line downward to an
open floor drain or sump. Provide service clearance around drain
line to permit removal of unit panels. Observe all local sanitary
codes.
Fig. 14 —
Drain Pan Slope Adjustment
As shipped, the unit’s condensate drain pan is NOT sloped to
-
wards the drain connection. The pan slope must be changed to
pitch towards the side of the unit with the drain connection. (See
Fig. 14.) Loosen the 2 screws next to the drain outlet at both ends
of the unit, push drain pan down in the slots near the drain connec
-
tion, and up in the slots on the opposite end. Re-tighten screws.
The pan should have a pitch of at least 1/4 in. over its length to
-
ward the drain connection.
Fan Motors and Drives
Motor and drive packages are factory installed in all units. The
motor and drive packages consist of the following items:
1 — Fan motor
1 — Adjustable motor pulley
1 — Fan pulley
2 — Matched fan belts
(40RUA*25-30, 40RUQ*25, 40RUS*25-30 units)
For instructions on changing fan rotation, changing drive speeds
and adjusting drives, see Pulley and Drive Adjustment in the
Service section.
3” MIN.
[76]
NOTE: Dimensions in [ ] are in millimeters
Plug
Plug
3" Min.
[76]
3" Min.
[76]
From
Condensate
Pan
From
Condensate
Pan
Existing Floor
Drain, Sink, or
Hopper
Existing Floor
Drain, Sink, or
Hopper
Unit
Condensate
Conn
Unit
Condensate
Conn
Trap
Trap
Not Less Than 18" [457]
Long and Two Sizes
Larger Than Waste Pipe
Not Less Than 18" [457]
Long and Two Sizes
Larger Than Waste Pipe
To Sewer
To Sewer
1" Min.
1" Min.
Plug
Plug
Plug
Plug
3" Min.
[76]
3" Min.
[76]
3" Min.
[76]
3" Min.
[76]
Trap
Trap
[25]
[25]
Plug
Plug
Adjustment Slots
(Both Ends of Unit)
PVC Stub Unit
Drain Connection
Содержание 40RU 25
Страница 3: ...3 Fig 1 Dimensions Size 25...
Страница 4: ...4 Fig 1 Dimensions Size 25 cont...
Страница 5: ...5 Fig 2 Dimensions Sizes 28 and 30...
Страница 6: ...6 Fig 2 Dimensions Sizes 28 and 30 cont...
Страница 24: ...24 Fig 19 Typical Fan Discharge Connections for Multiple Fan Units Fig 20 Duct Flange Installation Duct Flanges...
Страница 37: ......