32
Table 21 — Medium-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
Motor Drive
Motor Pulley Pitch Diameter
(mm)
109.2-134.6
109.2-134.6
109.2-134.6
Pulley Factory Setting
Full Turns Open
3.0
3.0
3.0
Fan Drive
Pulley Pitch Dia (mm)
239
239
239
Pulley Bore (mm)
36.5
49.2
49.2
Belt No. — Section
1 — B
2 — B
a
NOTE(S):
a. Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.
2 — B
a
Belt Pitch (mm)
1062
(2) 986
(2) 1011
(2) 986
(2) 1011
Fan Speeds (r/s)
Factory Setting
14.7
14.7
14.7
Range
13.3-16.4
13.3-16.4
11.2-13.9
Maximum Allowable Speed (r/s)
20.0
18.3
18.3
Change Per 1/2 Turn of
Moveable Motor Pulley
Flange
0.255
0.255
0.255
Maximum Full Turn From Closed
Position
6
6
6
Shafts Center Distance (mm)
232-279
169-240
169-240
Table 22 — High-Static Drive Data, 60 Hz — SI
UNIT
40RUA*25
40RUQ*25
40RUS*25
40RUA*28
40RUS*28
40RUA*30
40RUS*30
Motor Drive
Motor Pulley Pitch Diameter
(mm)
109.2-134.6
109.2-134.6
109.2-134.6
Pulley Factory Setting
Full Turns Open
3.0
3.0
3.0
Fan Drive
Pulley Pitch Dia (mm)
188
203
203
Pulley Bore (mm)
36.5
49.2
49.2
Belt No. — Section
2 — B
2 — B
2 — B
Belt Pitch (mm)
935
935
960
Fan Speeds (r/s)
Factory Setting
18.6
17.1
17.1
Range
16.9-20.0
a
NOTE(S):
a. It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s.
14.6-17.9
14.6-17.9
Maximum Allowable Speed (r/s)
20.0
18.3
18.3
Change Per 1/2 Turn of
Moveable Motor Pulley
Flange
0.323
0.278
0.278
Maximum Full Turn From Closed
Position
6
6
6
Shafts Center Distance (mm)
207-255
169-240
169-240
Содержание 40RU 25
Страница 3: ...3 Fig 1 Dimensions Size 25...
Страница 4: ...4 Fig 1 Dimensions Size 25 cont...
Страница 5: ...5 Fig 2 Dimensions Sizes 28 and 30...
Страница 6: ...6 Fig 2 Dimensions Sizes 28 and 30 cont...
Страница 24: ...24 Fig 19 Typical Fan Discharge Connections for Multiple Fan Units Fig 20 Duct Flange Installation Duct Flanges...
Страница 37: ......