Table 3 — Fitting Requirements (cont)
UNIT
ACCESS
HOLE NO.*
CONNECTION
TYPE
CIRCUIT
FITTINGS REQUIRED†
(in.)
40RMS
028, 034
5
Supply
Lower
2
1
⁄
8
Long Radius Elbow
2
1
⁄
8
Nipple, 3
1
⁄
2
L
2
1
⁄
8
Long Radius Elbow
6
Return
Lower
2
1
⁄
8
Long Radius Elbow
2
1
⁄
8
Nipple, 3 L
2
1
⁄
8
Long Radius Elbow
7
Return
Upper
2
1
⁄
8
Long Radius Elbow
2
1
⁄
8
Nipple, 6
7
⁄
8
L
2
1
⁄
8
Long Radius Elbow
8
Supply
Upper
2
1
⁄
8
Long Radius Elbow
2
1
⁄
8
Nipple, 11
7
⁄
8
L
2
1
⁄
8
Long Radius Elbow
40RM
034
1
Suction
Lower
1
3
⁄
8
Street Elbow
1
3
⁄
8
Nipple, 3 L
1
3
⁄
8
Long Radius Elbow
2
Liquid
Lower
5
⁄
8
Street Elbow
5
⁄
8
Nipple, 7
3
⁄
4
L
5
⁄
8
Long Radius Elbow
3
Liquid
Upper
5
⁄
8
Street Elbow
5
⁄
8
Nipple, 18
1
⁄
2
L
5
⁄
8
Long Radius Elbow
4
Suction
Upper
1
3
⁄
8
Nipple, 4
3
⁄
16
L
1
3
⁄
8
Long Radius Elbow
1
3
⁄
8
Nipple, 19
1
⁄
4
L
1
3
⁄
8
Long Radius Elbow
*See Fig. 4 for access hole location by number.
†Fittings are listed in order from header or tee stub connection out to access hole in corner support post.
Chilled Water Piping —
See Tables 1C and 1F for
chilled water connection sizes. For ease in brazing, it is rec-
ommended that all internal solder joints be made before unit
is placed in final position.
Knockouts are provided in the unit corner posts for 40RM
and 40RMQ refrigerant piping; additional field-fabricated ac-
cess holes are required for 40RMS chilled water piping. See
Fig. 4, which lists recommended knockouts and access holes
to use for each 40RMS unit size.
To size, design, and install chilled water piping, consult
the Carrier System Design manual. See Fig. 9 for an ex-
ample of a typical installation. Recommended fittings are listed
in Table 3.
To access 40RMS coil vents and drains, remove the unit
side panel over the coil header. Vent and drain plugs are on
the top and bottom of header, respectively. See the Service
section for information on preventing coil freeze-up during
winter.
Fig. 9 — Typical 40RMS Chilled Water Piping
17