10

Step 6 — Make Electrical Connections — 

Be sure

field wiring complies with local building codes and NEC, and

unit voltage is within limits shown in Table 5.

Contact local power company for correction of improper

line voltage.

NOTE: Use copper wire only between disconnect switch(es)

and unit.
NOTE: Install branch circuit disconnect of adequate size to

handle unit starting current per NEC. Locate disconnect within

sight of, and readily accessible from, unit, per Section 440-14

of NEC. Some codes allow indoor unit to share disconnect with

outdoor unit if disconnect can be locked; check local code

before installing in this manner.

1. Route ground and power wires.

2. Route line power leads (see Fig. 16) from indoor dis-

connect to the fan coil unit. Place wire through hole on

the control box (Fig. 17). Connect wire to high voltage

terminal board (TB1) and ground screw. When routing

the wire in the unit, use care to keep the wire away

from refrigerant and condensate piping and any sharp

edges. The 208/230-v units are factory wired for

230-v to 24-v transformer operation. For 208-v to

24-v operation, interchange blue (208-v) and red

(230-v) wires. Cap any unused wires with wire nuts.

Table 5 — Electrical Data*

LEGEND

*All units are 208/230-1-60. Minimum operating voltage is 187, max-

imum is 253. Units will operate satisfactorily within this voltage
range.

†Electrical data is the same for both the 24,000 Btuh 024 unit and

the 024 unit that has been field-reconfigured for 18,000 Btuh. Refer
to Before Installation section on page 3 for reconfiguration details.

To avoid personal injury or damage to unit, do not make

electrical connections until all power sources are shut

down, locked out, and tagged off. Failure to do so could

result in personal injury or unit damage.

Operation of unit on improper line voltage constitutes abuse

and could affect warranty. Refer to Table 5 for permissible

operating limits. Do not install unit in system where voltage

may fluctuate above or below permissible limits.

According to NEC and most local codes, the unit must have

an uninterrupted, unbroken ground to minimize personal

injury if an electric fault should occur. The ground may

consist of electrical wire or metal conduit when installed in

accordance with existing electrical codes. Failure to follow

this warning could result in an electric shock, fire, or death.

SYSTEM

TYPE

UNIT

SIZE

FAN

HEATER

POWER

MIN WIRE SIZE

(AWG)

Motor 1 FLA

Motor 2 FLA

kW

FLA

MCA

MOCP

FLA

COOLING
ONLY

024†

0.5

0.53

15

0.50

14

036

1.3

1.60

15

1.30

14

048

1.1

0.5

2.00

15

1.60

14

060

1.3

1.3

3.30

15

2.60

14

HEAT PUMP

024†

0.5

2.00

8.66

9.29

15

  9.16

14

036

1.3

3.00

13.00

17.70

20

14.30

14

048

1.0

0.5

4.00

17.40

23.80

25

19.00

12

060

1.3

1.3

5.00

21.70

28.70

30

24.30

10

AWG

American Wire Gage

FLA

Full Load Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

MOCP —

Maximum Overcurrent Protection

NEC

National Electrical Code

Содержание 40QA024-060

Страница 1: ...PERATE FRESH AIR INSTALLATION OPTION 20 Ventilation Air Accessory 20 TROUBLESHOOTING 20 START UP CHECKLIST CL1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be haz...

Страница 2: ...field supplied for connection of the indoor and outdoor units refrigerant piping condensate drain piping thermostat power and control wiring For some applications a fresh air intake power vent fan and...

Страница 3: ...CITY tons 11 2 2 3 3 4 5 NOMINAL SIZE Btuh 18 000 24 000 30 000 36 000 48 000 60 000 OPERATING WEIGHT lb 108 108 117 117 149 179 MOISTURE REMOVAL WEIGHT Pints Hr 4 0 7 3 6 0 9 0 13 0 14 5 FINISH GM Mo...

Страница 4: ...3 4 5 NOMINAL SIZE Btuh 18 000 24 000 30 000 36 000 48 000 60 000 OPERATING WEIGHT lb 110 110 119 119 151 181 MOISTURE REMOVAL WEIGHT Pints Hr 4 0 7 3 6 0 9 0 13 0 14 5 FINISH GM Motorhome White with...

Страница 5: ...119 4 1013 16 1493 4 57 8 1368 4 91 2 1459 2 11 2 648 048 149 151 5 119 16 1817 5 65 8 1692 5 101 4 1783 1 97 8 555 3 31 16 992 060 179 181 7 8 2336 7 3 2211 7 65 8 2302 1 115 8 601 4 119 16 1512 NOT...

Страница 6: ...T CONCRETE SLAB Install hang ing bolts with expansion anchor TO MOUNT UNIT 1 Remove mounting bracket and reinstall the 2 hex head bolts factory supplied into each side of indoor unit as shown in Fig 6...

Страница 7: ...een the structure and the unit to absorb vibrations d A piston is shipped in the factory installed meter ing device body Fig 13 with the indoor unit Use Tables 4A 4C to verify that you have the requir...

Страница 8: ...pipe with nylon wire tie passing through hole Fig 15 NOTE Do not fasten nylon wire ties tight enough to deform the insulation as this affects its performance 5 Insulate condensate drain line s that a...

Страница 9: ...Fig 11 Hanging Fan Coil Unit Field supplied Fig 12 Routing Wires Over Piping NOTE Teflon Seal must face toward the outdoor heat pump unit Fig 13 AccuRater Metering Device at Service Valve Bypass Type...

Страница 10: ...lectrical data is the same for both the 24 000 Btuh 024 unit and the 024 unit that has been field reconfigured for 18 000 Btuh Refer to Before Installation section on page 3 for reconfiguration detail...

Страница 11: ...ues 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated cooling only units 4 Wiring and piping shown are general points of connection guides only...

Страница 12: ...mostat Operating Instructions Mount thermostat to a wall in the occupied space using 2 field supplied screws Locate the thermostat in an area that is not subjected to drafts or direct sunlight through...

Страница 13: ...nections must be made to the outdoor unit for it to operate as a system with the indoor unit Route 5 wires of field supplied 18 gage AWG thermostat cable between the low voltage terminal block of the...

Страница 14: ...FLAT THERMOSTAT FLATSTAT CARRIER COOLING ONLY HEAT COOL 53DFS250 FS SLIMLINE THERMOSTAT CARRIER HEAT PUMP COOLING ONLY HEAT COOL 53DFS250 SL 5 1 1 PROGRAMMABLE THERMOSTAT CARRIER COOLING ONLY HEAT CO...

Страница 15: ...te as a sys tem with the indoor unit Route 2 wires of field supplied 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit and the blue and brown...

Страница 16: ...16 Fig 20 Cooling System Wiring Diagram...

Страница 17: ...17 Fig 21 Heat Pump Wiring Diagram...

Страница 18: ...gh speed and the unit is equipped with the power ventilation kit the ventilation fan will operate to provide fresh air COOLING MODE OPERATION When the room ther mostat senses a demand for cooling the...

Страница 19: ...Maintenance procedures for the outdoor units are in the individual unit installation instructions To avoid the possibility of electric shock before performing any cleaning and maintenance operations...

Страница 20: ...Mode button until either COOL or HEAT is dis played as desired 4 Adjust thermostat set point to desired room tempera ture If system starts within a few minutes service may not be necessary If system...

Страница 21: ...t Cool Properly Air filter s in indoor unit is dirty or needs to be replaced Clean or replace air filter s Temperature is set too high or too low Reset temperature to desired comfort setting using the...

Страница 22: ...ent discussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs are available using popular vid...

Страница 23: ...CR BREAKER BEEN PROVIDED ____________ ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY ____________ IS THE DISCONNECT SWITCH INSTALLED WITHIN SIGHT OF THE UNIT ____________ IS THE LOW VOLTAGE...

Страница 24: ...ATION OUTDOOR UNIT MODEL NO SERIAL NO INDOOR UNIT MODEL NO SERIAL NO ACCESSORIES __________________________________________________________________________________ PISTONS 38HDC and 38QRC SYSTEMS ONLY...

Отзывы: