background image

9

INSTALLING DUCTWORK

Connect the return and supply ducts to the duct collars provided on
the unit. Adequate distance between the return and supply diffusers
should be maintained to avoid short circulation of air within the space.

The filter is located on the return side of the unit, on the rear or
bottom depending on the return air inlet arrangement.

A150671

Fig. 13 −

 

Installing Duct

OUTSIDE AIR CONNECTION

If necessary, an outside air connection knockout is located on the side
of the unit downstream of the air filter. It is recommended to field
supply and field install a booster fan on the duct work used for outside
air. A booster fan may be powered by the connection on the PCB
board CN43. The maximum input for the motor is 200W. The output
of the NEW FAN will be active while the indoor fan is active.

NOTE:  The amount of outside air is dependent on different
factors as the booster fan, outside air duct work type and length,
static pressure, conditions, etc..

Ø4.92” (125mm)

  Ø6.3”(160mm)

Fig. 14 −

 

Outside Air Connection

CONDENSATE PIPE INSTALLATION

The unit is supplied with a 1 1/4−in. OD drain connection to
connect copper or PVC drain piping. When installing condensate
piping, follow these recommendations:

S

Install drains to meet local sanitation codes.

S

The Ducted Style Indoor unit is supplied with a condensate lift

pump that is capable of lifting water 29.5in. (750mm).

S

The highest point in the condensate piping should be as close to

the unit as possible (see Fig. 17).

S

Condensate piping should slope downward in the direction of

condensate flow, with a minimum gradient of 1/100.

S

When multiple units are connected to a common condensate

drain, ensure the drain is large enough to accommodate the

volume of condensate from all units. It is also recommended to

have an air vent in the condensate piping to prevent air lock.

S

Condensate piping must not be installed where it may be

exposed to freezing temperatures.

S

To prevent the pipe from sagging, space hanging wires every

39−59in. (1−1.5m).

S

If the outlet of the drainpipe is higher than the body’s pump

joint, provide a lift pipe for the exhaust outlet of the indoor unit.

The lift pipe must be installed no higher than 21.7in. (55cm)

from the ceiling board. The distance between the unit and the lift

pipe must be less than 7.9in (20cm). Incorrect installation could

cause water to flow back into the unit and flood.

S

To prevent air bubbles, keep the drain hose level or slightly tiled

up <3in. (75mm).

1. Cover the drain hose with heat insulation to prevent

condensation and leakage.

2. Attach the mouth of the drain hose to the unit’s outlet pipe.

Sheath the mouth of the hose and clip it firmly with a pipe
clasp (see Fig. 15).

      Drainpipe

connecting port  

Drain hose

Pipe clasp

Insulation

Fig. 15 −

 

Indoor Drainpipe Installation

Fig. 16 −

 

Condensate piping without a pump

(39-59”)

(7.9”)

<20cm

)

7.

1

2(

mc

5

5

<

Lean over 1/50

1-1.5m

Ceiling

0 - 75mm 

(3”)

Fig. 17 −

 

Condensate piping with a pump

When connecting multiple drainpipes, install the pipes as
illustrated on Fig. 18.

0-53cm
(20.8”)

10cm
(4”)

Fig. 18 −

 

Connecting Multiple Drain Pipes

Содержание 40MBDQ series

Страница 1: ...rposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 INSTALLATION CLEARANCES 7 MAINTENANCE CLEARANCES 7...

Страница 2: ...injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property...

Страница 3: ...s If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wal...

Страница 4: ...ues exist a 14 2 stranded shielded wire can be used to replace L2 and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only Sizes 36 58 Recommended Connection...

Страница 5: ...mm 700 200 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84 18 1 18 In 34 65 8 27 26 54 23 62 5 51 27 80 1 97 5 35 30 79 7 48 1 57 36 22 20 3 07 5 83 3 46 4 41 54 mm 880 210 674 600 140 706 50...

Страница 6: ...6 DIMENSIONS CONT Airflow Airflow Fig 5 Indoor Unit Sizes 58K...

Страница 7: ...in 45cm 7 8 in 20cm 11 81 in 30cm 4 in 10cm Bottom Return Blower Motor Service Clearance Filter Service Clearance Blower Motor Service Clearance PCB Board Service Clearance Fig 7 Maintenance Clearance...

Страница 8: ...ely from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work CAUTION MOUNTING THE UNIT 1 INSTALLING HANGER BOLTS Install the hanger bolts at...

Страница 9: ...as close to the unit as possible see Fig 17 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 100 S When multiple units are connected to a com...

Страница 10: ...nect the drainpipe to the connector D see Fig 20 d Plug the power cable of the external pump to CN13 PUMP pin and plug the water level sensor cable to the CN5 WATER to enable the pump see Fig 23 Fig 1...

Страница 11: ...w these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 27 2 Using a piece of tubing or pipe fill the condensate lift pump reservoir with 70 oz of wa...

Страница 12: ...1 T2 T26 T3 T4 are sub menus for thermistors Do not select for setting external static pressure Fig 30 Wired Controller Menu Selection 1 If setting the external static pressure manually select SP and...

Страница 13: ...WG 0 10 0 216 0 336 0 528 0 0 64 Pa 25 54 84 132 0 160 36 In WG 0 168 0 312 0 48 0 62 0 0 64 Pa 42 78 120 155 0 160 48 In WG 0 18 0 404 0 616 0 64 0 0 64 Pa 45 101 154 160 0 160 58 In WG 296 0 416 58...

Страница 14: ...14 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 32 Fan Performance 40MBDQ09...

Страница 15: ...15 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 33 Fan Performance 40MBDQ12...

Страница 16: ...16 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 34 Fan Performance 40MBDQ18...

Страница 17: ...17 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 35 Fan Performance 40MBDQ24...

Страница 18: ...18 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 36 Fan Performance 40MBDQ36...

Страница 19: ...19 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 37 Fan Performance 40MBDQ48...

Страница 20: ...20 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 38 Fan Performance 40MBDQ58...

Страница 21: ...3 65 0 952 1000 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS Fig 39 Connection Diagrams sizes 09 to 24 Fig 40 Connection Diagrams sizes 36 and 58 Fig 41 Control and Power Wiring on Indoor Unit sizes...

Страница 22: ...ces Table 9 Flare Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar Copper pipe Clamp handle Red a...

Страница 23: ...is used relocate the IR receiver within line of sight of remote location using the 6 ft cable included The factory location of the IR receiver is inside the control box see Fig 48 A150642 Fig 48 Contr...

Страница 24: ...unit 4 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUTO Discharge air direction Pre set position based...

Страница 25: ...otection H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator coil temperature sensor T2 ope...

Страница 26: ...7310 W Morris St D Indianapolis IN 46231 Edition Date 09 18 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM 40MBD...

Отзывы: