Main Protection

Fan speed is out of control

When the indoor fan speed is too low (300RPM) or too high (1500RPM) 
for a certain time, the unit stops and the LED displays a failure.

Inverter module protection

The inverter module has a protection function for current, voltage and 
temperature. If any of these protections engage, the corresponding code 
displays on the indoor unit and the unit stops working.

Indoor fan delayed open function

When the unit starts up, the louver activates immediately and the indoor 
fan opens 10s later. If the unit is running in the 

HEATING

 mode, the 

indoor fan is controlled by the anti-cold wind function.

Zero crossing detection error protection

If the AC detects that the time interval is not correct for a continuous 
240s, the unit stops and the 

LED

 displays the failure. The correct zero 

crossing signal time interval should be between 6-13ms.

Sensor protection at open circuit and breaking disconnection

If only one temperature sensor malfunctions, the air conditioner continues 
to work however the error code appears on the LED, in the event of any 
emergency use. If more than one temperature sensor malfunctions, the air 
conditioner stops working.

Operation Modes and Functions

FAN Mode

1. Outdoor fan and compressor stop
2. Temperature setting function is disabled and no setting temperature 

appears.

3. Indoor fan can be set to high/med/low/auto
4. The louver operates the same as in the 

COOLING

 mode.

Fig. 10 —AUTO FAN Mode

COOLING Mode

Indoor Fan Running Rules:

In the 

COOLING

 mode, the indoor fan runs all the time and the speed 

can be selected as 

HIGH

MEDIUM

LOW

 and 

AUTO

. When the 

setting temperature is reached, if the compressor stops running, the
indoor fan motor runs at the minimum or setting speed. The indoor fan is 
controlled by the rules shown in Fig. 11.

Fig. 11 — Indoor Fan Running Rules

The 

AUTO

 fan is controlled by the rules shown in Fig. 12.

Fig. 12 — Indoor Fan Running Rules

Evaporator Temperature Protection

When the evaporator temperature is less than the setting value, the
compressor stops.

a

b

c

d

e

T1
°C

10.8

°

F (6.0

°

C)

9

°

F (5.0

°

C)

7.2

°

F (4.0

°

C)

4.5

°

F (2.5

°

C)

1.8

°

F (1.0

°

C)

H

(H-L)*0.75+L

(H-L)*0.5+L

(H-L)*0.25+L

L

Setting fan

speed

Actual fan speed

T1-Td 

(°F)

L

H

M

Содержание 40MAHB Series

Страница 1: ...serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may res...

Страница 2: ...H B Q 36 A 3 40 INDOOR UNIT MA MODEL VOLTAGE 1 115 1 60 3 208 230 1 60 INDOOR UNIT FAN COIL UNIT TYPE H HIGH WALL INDOOR FAN COIL TYPE Q HEAT PUMP NOMINAL CAPACITY 06 1 2 TON 09 3 4 TON 12 1 TON 18 1...

Страница 3: ...terminal Refer to the CONNECTION DIAGRAMS on page 4 for 115 volt or 208 230 volt connection If installed in a high electromagnetic field area EMF and communication issues exist a 14 2 stranded shield...

Страница 4: ...g 1 Connection Diagram 12K 115V Fig 2 Connection Diagram 6K 18K 208 230 1 60 Fig 3 Connection Diagram 24K 36K 208 230 1 60 NOTES 1 Do not use thermostat wire for any connection between indoor and outd...

Страница 5: ...AHB Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 5 WIRING DIAGRAM Fig 4 Wiring Diagram All Sizes 115 and 208 2...

Страница 6: ...tice and without obligations 6 REFRIGERATION CYCLE DIAGRAM Fig 5 Refrigeration Cycle Diagram REFRIGERANT LINES IMPORTANT Both refrigerant lines must be insulated separately Refer to the outdoor unit s...

Страница 7: ...ZKFP 58 8 1 6 ZKFP 58 8 1 6 Volts V 115 208 230 208 230 208 230 208 230 208 230 208 230 208 230 Phase 1 1 1 1 1 1 1 1 FLA 0 2 0 25 0 25 0 25 0 13 0 5 0 5 0 5 MCA 0 25 0 31 0 31 0 31 0 16 0 63 0 63 0...

Страница 8: ...method is the most effective way of assuring a system is free of air and liquid water see Fig 8 Fig 8 Deep Vacuum Graph Triple Evacuation Method Refer to Fig 9 and proceed as follows 1 Pump the system...

Страница 9: ...connection If only one temperature sensor malfunctions the air conditioner continues to work however the error code appears on the LED in the event of any emergency use If more than one temperature se...

Страница 10: ...e indoor unit defrost lamp illuminates and appears Evaporator Coil Temperature Protection Fig 15 Evaporator Coil Temperature Protection When the evaporator temperature is higher than the setting prote...

Страница 11: ...s in the COOLING mode for 30 minutes and turns to the AUTO mode at the 75 2 F 24 C setting temperature If the air conditioner is off before the power turns off and the air conditioner is required to s...

Страница 12: ...the digital code Press OK to send as well Table 3 Inquiry Codes and Symbols To exit the Inquiry Mode Press and hold together the On Off and Fan buttons for 2 seconds CODE INQUIRY SYMBOL DESCRIPTION C...

Страница 13: ...is shut off NOTE Remember to discharge the electricity power in capacitor Fig 18 Electrolytic Capacitors For other models please connect discharge resistance approximately 100 40W or a soldering iron...

Страница 14: ...or 2 OFF EL 01 Indoor outdoor unit communication error 3 OFF EH 02 Zero crossing signal detection error 4 OFF EH 03 Indoor fan operating outside of the normal range 5 OFF EC 51 Outdoor unit EEPROM par...

Страница 15: ...RED IU DISPLAY SOLUTION 1 IPM malfunction or IGBT over strong current protection X P0 Page 28 2 Over voltage or too low voltage protection O O P1 Page 31 3 EEPROM parameter error O E5 Page 16 4 Invert...

Страница 16: ...ameter Error or Compressor Driven Chip EEPROM Parameter Error EC51 Description Outdoor PCB main chip does not receive feedback from the EEPROM chip or the compressor driven chip Recommended parts to r...

Страница 17: ...ng connection from indoor terminal to indoor PCB Are they OK Turn on the unit check if W and 1 L are connected Check that the power LED is on No Yes Yes Unplug all the high voltage components connecte...

Страница 18: ...while the black pin is for 3 port or N or S port the unit is running normal the voltage is moving alternately as positive values and negative values If the outdoor unit malfunctions the voltage remai...

Страница 19: ...crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal Recommended parts to repair Connection wires Indoor main PCB Troubleshooting Note Zero crossing detection e...

Страница 20: ...the unit turns off Recommended parts to repair Connection wires Indoor main PCB Fan assembly Indoor main PCB Troubleshooting YES Turn the power off Wait 2 minutes then restart Is it within normal para...

Страница 21: ...otor Outdoor main PCB Troubleshooting NOTE For certain models outdoor PCB could not be removed separately In this case the outdoor electric control box should be replaced as a whole YES Power off Afte...

Страница 22: ...herwise proceed to step 2 2 Power on the unit and when the unit is in standby measure the pin4 5 voltage in the feedback signal connector If the value is not 5V change the PCB Otherwise proceed to ste...

Страница 23: ...is lower than 0 06V or higher than 4 94V the LED displays the failure code Recommended parts to repair Connection wires Sensors Indoor main PCB Troubleshooting Fig 21 Test NOTE Figure 21 and the valu...

Страница 24: ...onnection wires Sensors outdoor main PCB Troubleshooting Fig 22 Test NOTE For certain model the outdoor PCB could not be removed separately In this case the outdoor electric control box should be repl...

Страница 25: ...than 50Hz however it does not maintain for a minimum of three minutes and this issue occurs 3 times the LED displays the failure code and the unit turns off Recommended parts to repair T2 Sensor Indo...

Страница 26: ...r PCB does not receive feedback from the display board Recommended parts to repair Communication wire Indoor PCB Display board Troubleshooting Is it still displaying the error code The unit functions...

Страница 27: ...the power wiring Are the L and N wired properly Reconnect L and N Replace the outoor main PCB Is the voltage between L and N normal Is the current normal Power on and measure the voltage between P an...

Страница 28: ...tdoor PCB Troubleshooting YES NO Is the IPM terminal resistance uniform NO YES Please refer to the Fan Speed is operating outside of normal range malfunction NO YES YES NO YES NO Check the wiring betw...

Страница 29: ...ectrolytic capacitors and ensure all the energy storage has been discharge 3 Disassemble the outdoor PCB or disassemble the IPM board 4 Measure the resistance value between P and U V W N U V W and N F...

Страница 30: ...ut notice and without obligations 30 DIAGNOSIS AND SOLUTION CONT Compressor Check Disconnect the compressor and check the resistance between U V V W and U W and all 3 values should be equal If not the...

Страница 31: ...o repair Power supply wires IPM module board PCB Reactor Troubleshooting Check the power supply Is it in working order Turn off the unit NO Check the connections and wires YES Are they in working orde...

Страница 32: ...blockages Troubleshooting NOTE For certain models the outdoor PCB can not be removed separately In this case the outdoor electric control box should be replaced as a whole Check if the air flow system...

Страница 33: ...e protector broken Check if the outdoor unit ventilation is good Ensure that the outdoor unit s ventiliation is functioning properly High pressure protection Connect the high pressure switch and main...

Страница 34: ...connect the low pressure protector and the main control board Is the low pressure protector broken Method Disconnect the plug Measure the low pressure protector resistance If the protector is normal t...

Страница 35: ...mmended parts to repair Connection wires IPM module board Outdoor fan assembly Compressor Outdoor PCB Troubleshooting Check the wiring between the PCB and the compressor Is it improperly wired Ensure...

Страница 36: ...he priority Examples If indoor unit A is operating in the COOLING mode or the FAN mode and indoor unit B is set to the HEATING mode unit A will power off and unit B will continue to operate in the HEA...

Страница 37: ...36 97 6 13059 76 169 1 34105 116 241 0 4006 3 27 41 5878 37 99 5 87359 77 171 1 29078 117 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2...

Страница 38: ...37 3 74 165 8 358 114 237 2 489 5 23 234 9 35 95 35 78 75 167 8 084 115 239 2 422 4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100...

Страница 39: ...2 5 36 5 30 86 61 141 8 92 197 6 123 253 4 3 37 4 31 87 8 62 143 6 93 199 4 124 255 2 3 5 38 3 32 89 6 63 145 4 94 201 2 125 257 4 39 2 33 91 4 64 147 2 95 203 126 258 8 4 5 40 1 34 93 2 65 149 96 20...

Страница 40: ...t is for reference only and the photos may differ from your actual unit Procedure Illustration 1 Place your hands along the lter ssides pull the lter gently along the vertical direction and then remov...

Страница 41: ...specifications and designs without notice and without obligations 41 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 4 Open the panel assembly move the slider to secure the panel 5 Open the two...

Страница 42: ...l the two sides of the bottom panel along the direction shown in the image to the right to remove it 8 Pull the panel s support bar to remove it 9 Remove the panel assembly Caution If you want to clos...

Страница 43: ...and designs without notice and without obligations 43 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 10 Remove 1 screw from the display board 11 Rotate the display board subassembly in the dire...

Страница 44: ...tice and without obligations 44 DISASSEMBLY INSTRUCTIONS CONT Electrical parts Anti static gloves must be worn Procedure Illustration 1 Pull the two ends of the electronic control box cover with your...

Страница 45: ...stration 4 Disconnect the wires 5 Remove one screw used for the ground connection 6 Pull two clips of the electronic control box along the direction shown in the picture to the right to remove the mai...

Страница 46: ...tions 46 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 7 Remove the other screw used for the ground connection 8 Collapse the support bar 9 Pull the electronic control box cover along the direc...

Страница 47: ...ications and designs without notice and without obligations 47 DISASSEMBLY INSTRUCTIONS CONT Evaporator NOTE Remove the front panel electrical parts and the fan Procedure Illustration 1 Remove the 2 s...

Страница 48: ...without obligations 48 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustration 3 Remove the screw 1 on the evaporator located at the left xed plate 4 Remove the screw 1 on the evaporator located on the...

Страница 49: ...and without obligations 49 DISASSEMBLY INSTRUCTIONS CONT Fan Motor and Fan Procedure Illustration 1 Open the two stop blocks of the chassis assembly see picture on the right 2 Remove the chassis asse...

Страница 50: ...HB 01 40MAHB Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 50 DISASSEMBLY INSTRUCTIONS CONT Procedure Illustrat...

Отзывы: