background image

GB - 9

40KQV

E N G L I S H

IMPORTANT:
During the unit installation make first refrigerant connections
and then electrical connections. If unit is uninstalled first
disconnect electrical cables, then refrigerant connections.

Refer to the outdoor unit installation manual for tube sizing,
and limitations (slope, length, number of curves allowed,
refrigerant charge, etc.).

Tube diameter

Gas

Liquid

Mod.

(suction line)

(discharge line)

mm

(inches)

mm

(inches)

050 12.70 (1/2") 6.35 (1/4")

 080-110-130 15.87 (5/8") 9.52 (3/8")

For refrigerant tubes use seamless, insulated refrigeration grade
tube, (Cu DHP type according to ISO1337), degreased and
deoxidized, suitable for operating pressures of at least 4200 kPa
and for burst pressure of at least 20700 kPa.
Under no circumstances must sanitary type copper pipe be used.

Flaring the end of pipes

Remove the protection caps from the copper pipe ends.
Holding the tube downward, cut the extreme end off, removing any
copper shavings with a deburring blade.
Remove the flare nuts from the “FLARE” connection body of the
indoor unit and insert them into the pipes.
Make the flare to the pipe end with the proper flaring tool.

Flare end must not have any burrs or imperfections.
The length of the flared walls must be uniform.

Lubricate the end of pipe and the thread of the flare connection
with anti-freeze oil.
Tighten by hand and then use two wrenches to tighten all
connections fully, applying the tightening torque shown in the table.

Pipe connection to the unit

Use two wrenches to tighten all connections.
Insufficient tightening torque could cause a refrigerant leak from
the connection.
Excessive tightening torque will damage the pipe flare.

          Tube diameter

Torque

mm

(inches)

Nm

6.35

(1/4")

14

÷

18

9.52

(3/8")

33

÷

42

12.70

(1/2")

50

÷

62

15.87

(5/8")

63

÷

77

Once all connections have been completed, check for leaks using
soapy water.
Finally, wrap connections with anti-condensate insulation and
tighten with tape, without exerting excessive pressure on the
insulation. Repair and cover any possible cracks in the insulation.

Extra charge of refrigerant

Refer to installation manual of  38VYX series.

Checking

Pour several litres of water into the condensate drain pan and check
that it flows freely to the drain.
Check pipe gradient and look for possible obstructions.

Refrigerant connections

Pipe

Pipe insulation

Adhesive tape

Содержание 40KQV

Страница 1: ...40KQV INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Страница 2: ...he manuals for each unit These are supplied with the unit Contents Page Dimensions and weight 2 Technical data 3 Material supplied 3 Operating limits 3 Components required for a complete installation...

Страница 3: ...40KQV 050 080 110 130 Unit 19 36 38 38 Frame Grille assembly 3 5 5 5 kg 575 298 120 225 280 56 52 91 575 158 720 550 515 1 5 0 7 0 5 0 3 0 25 813 595 825 120 298 168 237 960 825 1 5 0 6 6 4 8 2 5 100...

Страница 4: ...it according to EN 60335 2 40 standards Technical data TableII Material supplied Description Quantity Use Installation instructions 1 Indoor unit installation Owner s Manual 1 Correct use Fresh air in...

Страница 5: ...to any other manufacturer s outdoor unit The manufacturer declines any liability for system malfunction resulting from unauthorised system combinations General information The manufacturer declines a...

Страница 6: ...nit flattening or kinking the refrigerant pipes or condensate pipes installation in areas with high frequency waves only partial insulation of the piping Non level installation which will cause conden...

Страница 7: ...possible in the room the air flow direction can be controlled by means of the remote control where used or automatically according to the operating mode cooling or heating this will ensure optimum dis...

Страница 8: ...unit may need to be tilted this operation may only be carried out with false ceilings with a minimum height of 300 mm First position the refrigerant lines as described in the chapter Refrigerant conne...

Страница 9: ...10 mm slope toward the outside Insert the plastic conduit provided Pass the power connection cables through the conduit see electrical connections Condensate drain pipe To ensure correct condensate wa...

Страница 10: ...o the pipes Make the flare to the pipe end with the proper flaring tool Flare end must not have any burrs or imperfections The length of the flared walls must be uniform Lubricate the end of pipe and...

Страница 11: ...Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louverconnector CP CG CA CV CLR B Outdoor unit connection SYSTEM CONFIGURATION Make the electrical connection...

Страница 12: ...Earth 1 Live connection indoor outdoor unit 2 Neutral connection indoor outdoor unit 3 Communication high voltage Cable passage Interconnection cable 4x1 mm2 H07 RN F Room Controller CZM connecting c...

Страница 13: ...yrene partition Introduce baffle supplied after frame has been hooked as per above figure Following that screw the frame grille assembly using the 4 screws Use locally purchased material suitable for...

Страница 14: ...gths can be calculated in accordance with the air distribution to an adjacent room diagram also taking into account the pressure drop through air diffusers and fresh air filters DO NOT use active carb...

Страница 15: ...either the or button to change the default value of minimum cooling set point temperature admitted in Degrees Celsius 17 or Degrees Fahrenheit 63 to the new value Degrees Celsius 17 32 or Degrees Fah...

Страница 16: ...perations or for any other needs Unit warning lights and guide for the owner Button T EMERGENCY Can be used when the remote control is lost or inoperative Use a screwdriver to press the push button th...

Страница 17: ...125H95 0605 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice June 2005 Supersedes April 2005 Printed in I...

Отзывы: