3 - HANDLING
The unit can be handled by slings, lifting beam or stacker. In all cases, the lifting point has to be at the base of the unit. The centre of
gravity is at the centre of the unit.
This operation will be performed by qualified personnel.
The unit must be handled with care, and only in the horizontal position.
If the unit is handled by a lifting beam + slings, tubes need to be placed
in the holes provided in the support feet.
Ensure that the crane hook adapter is large enough to prevent the
belts applying any pressure to the AHU casing. Furthermore, ensure
that the steel tubes are secured to prevent any movement.
COLIS
PACKAGE
If the above-mentioned lifting methods cannot be used, the unit may be
lifted using a forklift truck, taking great care not to dent the lower panel
(use forks of a sufficient length).
Follow the applicable handling rules.
The units must be set down directly on flat, level ground. The flatness value must be the best possible, around one per thousand.
Under normal conditions of use, there is no need to fix the unit to the floor, unless it is being installed outside of the building.
The unit's support feet must be standing fully on their contact surface. It is important to allow sufficient service space to facilitate
maintenance operations.
5