Table 3 - 38VMA072, 096, 120,144HDS
No. in refrigerant
system diagram
Symbol
Name
Major Function
A
INV
Inverter compressor
Inverter compressor is operated on frequencies between 20 Hz and 100 Hz.
B
INV1
Inverter compressor
C
Heat exchanger
To exchange heat with ambient environment.
D
FAN A
Left Inverter fan
The fan is operated at 13-step rotation speed by using the inverter.
E
FAN B
Right Inverter fan
The fan is operated at 13-step rotation speed by using the inverter.
F
EXV A
Electronic expansion valve
Used to adjust refrigerant volume.
G
EXV B
Electronic expansion valve
Used to adjust refrigerant volume.
H
EXV C
Electronic expansion valve
Used to adjust sub-cooling.
I
PHE
Plate Heat Exchanger
Used for sub-cooling liquid refrigerant from the electronic expansion valve.
J
SV4
Solenoid valve
Used to balance the oil between modules.
K
SV7
Solenoid valve
This valve opens at a pressure of 565.6 psi to prevent pressure from
increasing.
L
ST1
4-way valve
Used to switch the operation mode between cooling and heating.
M
H-LY1
High pressure sensor
Used to detect high pressure.
N
L-LY1
Low pressure sensor
Used to detect low pressure.
O
H-PRO
High pressure switch
Used to protect the system pressure. When system pressure is too high, the
pressure switch will open. Once the pressure switch is open, compressor
will stop and will restart after 12 minutes.
P
L-PRO
Low pressure switch
Used to protect the system pressure. When the system pressure is too low,
the pressure switch will open. Once the pressure switch is open,
compressor will stop, and will restart after 12 minutes.
Q
Pressure regulating valve
This valve opens at a pressure of 580 psig to prevent pressure from
increasing, thus resulting in no damage to functional parts due to the
increase of pressure in transportation or storage.
R
Oil separator
Used to separate oil from high pressure and high temperature refrigerant,
which is pumped out during compression.
S
Accumulator
Used to store the liquid refrigerant and oil. It can protect the compressor
from liquid slugging.
T
T3
Thermistor (outdoor coil deicer)
Used to detect liquid pipe temperature of ODU heat exchanger, determine
defrosting operation, and others.
1
T4
Thermistor (Outdoor air)
Used to detect outdoor / ambient temperature.
2
T5
Thermistor (liquid pipe)
Detects temperature of liquid pipe after Plate Heat Exchanger.
3
T6
Thermistor (Plate Heat
Exchanger gas pipe)
Detects temperature of gas pipe on the evaporation side of Plate Heat
Exchanger. Used to maintain constant control on superheated of the Plate
Heat Exchanger.
4
T7
Thermistor (Accumulator outlet)
Used to detect gas pipe temperature at the accumulator outlet.
5
INV Gas
Thermistor (INV discharge pipe)
Used to detect discharge pipe temperature. Enables the temperature
protection control of compressor, and others.
6
INV1 Gas
Thermistor (INV1 discharge pipe)
Used to detect discharge pipe temperature. Enables the temperature
protection control of compressor, and others.
10
Содержание 38VMA Series
Страница 8: ...II Refrigerant Circuit 1 Refrigerant Circuit Diagram Figure 17 38VMA072 096 120HDS 8...
Страница 9: ...Figure 18 38VMA144HDS 9...
Страница 11: ...2 Functional Parts Layout Figure 19 38VMA072 096 120HDS 11...
Страница 12: ...Figure 20 38VMA0144HDS 12...
Страница 13: ...3 Refrigerant Flow for Each Operational Mode a 38VMA072 096 120HDS Figure 21 Cooling Operation 13...
Страница 14: ...Figure 22 Cooling Oil Return 14...
Страница 15: ...Figure 23 Heating Oil Return and Defrost 15...
Страница 16: ...Figure 24 Heating Operation 16...
Страница 17: ...b 38VMA144HDS Figure 25 Cooling Operation 17...
Страница 18: ...Figure 26 Cooling Oil Return 18...
Страница 19: ...Figure 27 Heating Oil Return and Defrost 19...
Страница 20: ...Figure 28 Heating Operation 20...
Страница 21: ...III Function and Control 1 Operation Mode Figure 29 Operation Mode 21...
Страница 77: ...VIII Appendix 1 Wiring Diagram Figure 36 38VMA072 096 120HDS5 1 77...
Страница 78: ...Figure 37 38VMA144HDS5 1 78...
Страница 79: ...Figure 38 38VMA072 096 120HDS6 1 79...
Страница 80: ...Figure 39 38VMA144HDS6 1 80...
Страница 81: ...2 Electronic Control Box Layout Figure 40 38VMA072 096 120HDS5 1 Figure 41 38VMA144HDS5 1 81...
Страница 82: ...Figure 42 38VMA072 096 120HDS6 1 Figure 43 38VMA144HDS6 1 82...
Страница 83: ...Figure 44 Main control board layout Figure 45 ENC1 Outdoor unit addressing 83...
Страница 84: ...Figure 46 ENC4 network addressing Figure 47 ENC3 S12 Indoor unit quantity setting 84...
Страница 85: ...Figure 48 S5 Running mode priority setting Figure 49 S6 Auto addressing 85...
Страница 86: ...Figure 50 S11 anti snow setting Figure 51 S16 Mode setting 86...
Страница 87: ...Figure 52 S17 Heating mode setting Figure 53 S18 Cooling mode setting 87...
Страница 93: ...Figure 55 Control Board Views 93...
Страница 97: ...2 38VMA144HDS5 1 Figure 56 3 Phase Heat Pump Exploded View 97...
Страница 98: ...98...
Страница 99: ...Figure 57 Control Board Views 99...
Страница 103: ...3 38VMA072HDS6 1 38VMA096HDS6 1 38VMA120HDS6 1 Figure 58 3 Phase Heat Pump Exploded View 103...
Страница 104: ...Figure 59 Control Board Views 104...
Страница 108: ...4 38VMA144HDS6 1 Figure 60 3 Phase Heat Pump Exploded View 108...
Страница 109: ...109...