panel. (See Fig. 2) It contains information needed to properly
install unit. Check rating plate to be sure unit matches job
specifications.

Step 2—Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to a pad,
tie down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern shown in
Fig. 2 to determine base pan size and knockout hole location.

On rooftop applications, mount on level platform or frame. Place
unit above a load-bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit
and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.

Roof mounted units exposed to winds above 5 mph may require
wind baffles. Consult Low-Ambient Guideline for wind baffle
construction.

NOTE:

Unit must be level to within ±2° per compressor manu-

facturer specifications.

Step 3—Clearance Requirements

When installing, allow sufficient space for airflow, wiring, refrig-
erant piping, and service. Allow 30 in. (762mm) clearance to
service end of unit and 48 in. (1219mm) above unit. For proper
airflow, a 5 in. (152mm) clearance on 1 side of unit and 12 in.
(305mm) on all remaining sides must be maintained. Maintain a
distance of 24 in. (610mm) between units. Position so water, snow,
or ice from roof or eaves cannot fall directly on unit.

On rooftop applications, locate unit at least 6 in. (152mm) above
roof surface.

Step 4—Operating Ambients

The minimum outdoor operating ambient in cooling mode is 55°F
(12.8°C), and the maximum outdoor operating ambient in cooling
mode is 125°F (51.67°C).

Step 5—Replace Indoor AccuRater® Piston, if Required

Check indoor coil piston to see if it matches the required piston
shown on unit rating plate. If it does not match, replace indoor coil
piston with piston shipped with this unit. The piston shipped with
outdoor unit is correct for any approved indoor coil combination.

Remove indoor coil piston if unit is to be installed on system
with a thermostatic expansion valve (TXV) metering device.
Failure to follow this caution could cause performance
problems or product failure.

Step 6—Make Tubing Connections

Relieve pressure and recover all refrigerant before system
repair of final unit disposal to avoid personal injury or death.
Use all service ports and open all flow-control devices,
including solenoid valves.

Fig. 2—Unit Reference Drawing

UNIT SIZE

A

B

C

D

E

In.

mm

In.

mm

In.

mm

In.

mm

In.

mm

024

27-1/2

698.5

22

558.8

8-3/16

207.9

2-13/16

71.4

6-15/16

176.2

036, 048, 060

34-15/16

887.4

30

762.0

8-13/16

207.9

4

101.6

9-3/4

247.6

A92471

AIR DISCHARGE

3

/

IN.

 

DIA 

LIQUID 

LINE CONN

FIELD CONTROL 
SUPPLY CONN

7

/

IN.

 

DIA HOLE

 

AIR DISCHARGE

AIR DISCHARGE

AIR IN

AIR IN

3/8

DIA TIEDOWN KNOCKOUTS

(2) PLACES IN BASEPAN

      

C

L

UNIT RATING 

PLATE

1.  Allow 30

 

in.

 (762 mm) clearance to service end of

     unit, 48

 

in.

 

(1219 mm) above unit, 6

 

in.

 

(152 mm) on one side, 12

 

in.

 

(305 mm)

     on remaining side, and 24

 

in.

 

(610 mm) between

     units for proper airflow.
2.  Minimum outdoor operating ambient in cooling mode is
     55

°

 F (12.8

°

 C) (unless low ambient control is used) max 125

°

 F (51.7

°

 C).

5.   Series designation is the 13th position of the unit model number.
6.   Center of gravity

NOTES:

ACCESS

PANEL

FIELD POWER SUPPLY CONN

7

/

IN.

 

DIA HOLE WITH 

1

/

IN.

 

DIA KNOCKOUT

               AND 

3

/

IN.

 

DIA KNOCKOUT

A

C

AIR IN

E

D

B

VAPOR LINE CONN

INDIANAPOLIS IN

46206

313948-401

REV A

MAX CKT-BKR

MAX HACR CKT-BKR

MAX FUSE

TYPE

MINIMUM CIRCUIT AMPS

LO

HI

DESIGN/TEST PRESSURE GAGE

FLA

HZ

PH

VOLTS AC

LRA

RLA

HZ

PH

VOLTS AC

MAX

PH

LBS

PISTON

MODEL

PROD

SERIAL

N/A

USA

N/A

CANADA

MAX OVERCURRENT PROTECTIVE DEVICE

kPa

kPa

PSI

PSI

FAN MOTOR

COMPRESSOR

SUITABLE FOR OUTDOOR USE

MIN

HZ

Kg

VOLTS

POWER SUPPLY

ID

OD

FACTORY CHARGED R-22

®

®

PERMISSIBLE VOLTAGE AT UNIT

CARRIER CORP

2

Содержание 38TUA

Страница 1: ...TALLATION RECOMMENDATIONS 1 Locate unit away from windows patios decks and so forth where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to cap...

Страница 2: ...does not match replace indoor coil piston with piston shipped with this unit The piston shipped with outdoor unit is correct for any approved indoor coil combination Remove indoor coil piston if unit...

Страница 3: ...braze sweat connec tions using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all f...

Страница 4: ...ep 8 Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hrs before starting unit To furnish power to heater only set thermostat to OFF position a...

Страница 5: ...CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 Fig 5 24 v Control Circuit Connections 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C CARRIER NON PROGRAMMABLE THERMOSTAT MODEL A...

Страница 6: ...OUTDOOR SENSOR CONNECTION C Y1 O C SEE NOTE 2 J2 JUMPER J1 JUMPER A97597 Fig 5 Typical 24 v Circuit Connections Continued A97368 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION C...

Страница 7: ...he three power connections on the field side When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop If indoor unit is equipped with a time d...

Страница 8: ...em operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing high performance and minim...

Страница 9: ...be weighed in NOTE Superheat F is at low side service port Table 5 Required Suction Line Temperature English SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 8...

Страница 10: ...ed Suction Line Temperature Metric C SUPERHEAT TEMP C SUCTION PRESSURE AT SERVICE PORT KPA 424 443 463 483 503 524 546 568 591 0 1 7 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6 1 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6...

Страница 11: ...11...

Страница 12: ...38tuac4si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 101 Catalog No 003 8001...

Отзывы: