All the electrical connections must be carried out by qualified installers and all the wirings must be 

connected according to the wiring diagram.

Make ground connection prior to any other electrical connections.

All power sources must be turned off before wiring work and do not turn on the power until you have made 

sure all the wirings have been safety checked.

A main switch and circuit breaker or fuse must be installed, the capacity should be above 1.5 times of 

maximum current in circuit.

An individual branch circuit and single socket used only for this appliance must be available.

Wire cross section is depending on the rated current and national, state and local electrical wiring code. 

Consult local building codes and National electrical code for special requirement.

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly 

qualified persons in order to avoid a hazard.

The unit must be connected to the main power supply by means of a circuit breaker or a switch with a 

contact separation of at least 3mm in all poles. Installation of a residual current device (RCD) having a rated 

residual operating current not exceeding 30mA is advisable.

This appliance incorporates an earth connection for functional purposes only.

CAUTION

After the piping work is finished, make sure to check the connection part of each refrigerant pipe and confirm that there is no gas leak by 

applying soapy water to them or by using a leak detector specific for HFC refrigerants. Refer below picture for illustration.

            A: Low pressure stop valve            B: High pressure stop valve

            C& D: Indoor unit flare nuts

Check-point of indoor unit

Check-point of outdoor unit

A

B

C

D

4.3 REFRIGERANT PIPE

4.4 AIR EVACUATION

Connect the charge hose from the manifold gauge to the service port of the gas side packed valve.

Connect the charge hose to the port of the vacuum pump.

Fully open the handle Loof manifold gauge.

Operate the vacuum pump to evacuate air from the system until -76cmHg.

Close the handle Loof manifold gauge.

Fully open the valve stem of the packed valves.

Remove the charging hose form the service port.

Securely tighten caps of packed valve.

-76 cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Packed valve

Manifold valve

Compound gauge

Pressure meter

4.5 LEAKAGE TEST

* Please use tools for R410A system.

Liquid side:

φ

9.52mm       

R410A*

Chargeless length 

5m

Additional charge per meter

Liquid side:

φ

6.35mm       

15g

30g

Minimum length 

to reduce abnormal 

vibration & noise 

3m

NOTICE:

1. All power wires must be sized in according with national,state and local electrical wiring code. Consult local building codes and National Electrical Code for special 

requirements.
2. The outdoor power cord and interconnecting cable type should be H07RN-F.
3. The rated current of appliance  is indicated on the nameplate.

60mm

40mm

10mm

Power input cord

GND

60mm

40mm

10mm

GND

Connective Cable

38QHM009/38QHM012

38QHM018

38QHM024

11.0

16.0

18.5

17

25

30

Model

Rated Current(A)

Fuse Rating(A)

Power input cord

Connective Cable

3*1.5mm

3*1.5mm

3*2.5mm

5*1.5mm

5*1.5mm

5*2.5mm

(with Min. Crosse section)

(with Min. Crosse section)

4. REFRIGERANT PIPING WORK

5. WIRING

* Please use tools for R410A system.

Max. height difference(m)

Models

25

R410A  Inverter

Max. pipe length(m)     

10

30

20

40

20

QHM009/QHM012

QHM018
QHM024

NOTE
    Extended pipe length will affect the capacity and energy efficiency of the unit.
    The nominal efficiency is tested based on the pipe length of 5 meter.     
    When the pipe length is over 5m, the additional refrigerant should be added according to the pipe length.
    The max. pipe length is recommended as below.

W

1

2

3

L

N

Power Input

To Indoor

W

1

2

3

L

N

Power Input

To Indoor

W

1

2

3

To outdoor

W

1

2

3

To outdoor

QHM009
QHM012
QHM018

QHM024

Outdoor Unit

Indoor Unit

Model

Содержание 38QHM009

Страница 1: ...WALL MOUNTED AIR CONDITIONER INSTALLATION MANUAL...

Страница 2: ...installation service or disposal When any leakage of the contained fluorinated gas is detected the leak shall be stopped and repaired as soon as possible 4 Only qualified service personnel are allowed...

Страница 3: ...efrigerant gas leaks during installation ventilate the area immediately Refrigerant gas may produce a toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Expos...

Страница 4: ...e Step 1 Determine Wall Hole Position Step 2 Attach Mounting Plate Step 3 Drill Wall Hole Fix the mounting plate horizontally and level on the wall with five or more A type screws Install The Mounting...

Страница 5: ...t is hooked securely Use a wedge to prop up the unit if rear tubing is needed Hang The Indoor Unit For proper orientation of the refrigerant piping electrical cable and drain lines refer to below Fig...

Страница 6: ...th anchor bolts M10 to prevent it from collapsing Install the foundation and vibration proof rubbers to directly support the bottom surface of the fixing leg that is in contact with the bottom plate o...

Страница 7: ...he service port of the gas side packed valve Connect the charge hose to the port of the vacuum pump Fully open the handle Loof manifold gauge Operate the vacuum pump to evacuate air from the system un...

Страница 8: ...FAN SPEED etc on the remote controller work well Whether the louver moves normally Whether the room temperature is adjusted well Whether the indicator lights on the display panel are normal Whether t...

Отзывы: