16

Outdoor Unit

Indoor Unit

Refrigerant

Service Valve

Low Side

High Side

A

B

C

D

A07360

Fig. 12 – Service Valve

Manifold Gage

500 microns

Low side valve

High side valve

Charge hose

Charge hose

Vacuum pump

Low side valve

A07361

Fig. 13 – Manifold

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of

accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and

liquid water. (See Fig. 14)

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS

2500

3000

3500

4000

4500

5000

A95424

Fig. 14 – Deep Vacuum Graph

Triple Evacuation Method

The triple evacuation method should only be used when vacuum

pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water.

Refer to Fig. 15 and proceed as follows:

1 Pump system down to 28 in. of mercury and allow pump to

continue operating for an additional 15 minutes.

2 Close service valves and shut off vacuum pump.
3 Connect a nitrogen cylinder and regulator to system and

open until system pressure is 2 psig.

4 Close service valve and allow system to stand for 1 hr. Dur-

ing this time, dry nitrogen will be able to diffuse throughout
the system absorbing moisture.

5 Repeat this procedure as indicated in Fig. 15. System will

then be free of any contaminants and water vapor.

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

RELEASE CHARGE INTO SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

A95425

Fig. 15 – Triple Evacuation Method

Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both
indoor and outdoor unit has not shifted during shipment.
Ensure tubes are not rubbing against each other or any sheet
metal. Pay close attention to feeder tubes, making sure wire ties
on feeder tubes are secure and tight.

CONTROL SYSTEM

The 40MFC/MFQ unit is equipped with a microprocessor control
to perform two functions:

1 Provide safety for the system
2 Control the system and provide optimum levels of comfort

and efficiency

The main microprocessor is located on the control board of

outdoor unit. Outdoor and indoor units have thermistors used to
monitor the system operation to maintain the unit within acceptable

parameters and control the operating mode.

Содержание 38MFC

Страница 1: ...for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe p...

Страница 2: ...1 60 3 208 230 1 60 Nominal Capacity 009 3 4 Ton 012 1 Ton 017 1 3 7 Ton HP 018 1 1 2 Ton AC 022 1 5 6 Tons Nominal Capacity 009 3 4 Ton 012 1 Ton 017 1 3 7 Ton HP 018 1 1 2 Ton AC 022 1 5 6 Tons 01 0...

Страница 3: ...tion in Heating Mode S Condenser High Temp Protection in Cooling Mode S Ease Of Service And Maintenance Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Application Flexibility Condensate...

Страница 4: ...e Flare Pipe Connection Size Liquid In OD 1 4 3 8 Pipe Connection Size Suction In OD 3 8 1 2 5 8 Condensate Drain OD ID in 0 65 0 63 Maximum Piping Length ft 65 98 Max Lift Fan Coil Above ft 25 30 Max...

Страница 5: ...Outdoor Unit Charge lb 2 6 2 87 3 52 Refrigerant Lines Connection Type Flare Pipe Connection Size Liquid In OD 1 4 3 8 Pipe Connection Size Suction In OD 3 8 1 2 5 8 Condensate Drain OD ID in 0 65 0 6...

Страница 6: ...D A14344 Model W in mm D in mm H in mm L1 in mm L2 in mm Operating Weight lb kg 9K 12K 30 7 780 9 8 250 21 2 540 21 6 549 10 9 276 70 5 32 0 17K HP 18K AC 29 9 760 11 2 285 23 2 590 20 9 530 11 4 290...

Страница 7: ...0 13m min 6 5 0 13m min 1 8m CEILING FLOOR A07891 Fig 2 Indoor Unit Clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E A07894 UNIT Minimum Value in mm A 24 610 B 24 610 C 80 2032 D 12 305 E 2...

Страница 8: ...abnormally Optimum performance will be achieved during this operating temperature envelope A14466 Fig 4 System Operating Envelope ELECTRICAL DATA UNIT SIZE OPER VOLTAGE MAX MIN COMPRESSOR OUTDOOR FAN...

Страница 9: ...m 300 volt rating and 2 64 inch thick insulation must be used CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Wires should be size...

Страница 10: ...interface CN4 Fan feedback interface CN5 Stepper motor interface P_1 Ground interface CN8 Room temperature sensor interface CN9 Pipe temperature sensor interface CN10A Display interface CN1 Electronic...

Страница 11: ...line interface CN6 Indoor fan interface CN4 Fan feedback interface CN5 Stepper motor interface P_1 Ground interface CN8 Room temperature sensor interface CN9 Pipe temperature sensor interface CN10A Di...

Страница 12: ...l CN16 Internal and external communication line interface CN6 Indoor fan interface CN4 Fan feedback interface CN5 Stepper motor interface P_1 Ground interface CN8 Room temperature sensor interface CN9...

Страница 13: ...erface CN10A Display interface CN12 Compressor top temperature sensor optional CN7 Exhaust temperature sensor CN17 Outdoor temperature amp condenser pipe temperature sensor CN1 CN2 Four way valve cont...

Страница 14: ...E FIELD PIPING FLARE CONNECTION A08104 Fig 10 Cooling CAPILLARY TUBE HEAT EXCHANGER CONDENSER HEAT EXCHANGER EVAPORATOR SERVICE VALVE LIQUID HTG LIQUID TWO PHASE CHECK VALVE HEATING MODEL ONLY REVERSI...

Страница 15: ...cified below ADDITIONAL REFRIGERANT CHARGE Unit Size oz ft g m 9K 18K 0 16 15 22K 0 32 30 S Capillary tubes in outdoor unit are used as metering devices Long Line Applications 38MFC Units 1 No change...

Страница 16: ...a nitrogen cylinder and regulator to system and open until system pressure is 2 psig 4 Close service valve and allow system to stand for 1 hr Dur ing this time dry nitrogen will be able to diffuse thr...

Страница 17: ...of the compressor The compressor is heated when this is not operating The preheating function will deactivate If T4 is greater than 41_F 5_C or the compressor starts operating Zero Crossing Detection...

Страница 18: ...unless interrupted by the cold blow algorithm This algorithm will not allow the fan to run if the indoor coil temperature drops below a preset value Defrost is controlled by the on board microprocesso...

Страница 19: ...off off off 4 way valve Outdoor fan Indoor fan Indoor fan breeze 10s xx 10s 30s 10s Defrost Cycle no longer than 10 min xx 60s for 9k 12k models A14478 For 17K 22K models XX 60 for 17k model XX 90 for...

Страница 20: ...In other conditions the compressor will have a 3 minutes delay at re start TROUBLESHOOTING This section provides the required flow charts to troubleshoot problems that may arise NOTE Information requi...

Страница 21: ...ip Possible Causes Installation mistake Defective PCB Trouble shooting If the EEPROM chip is welded on main PCB replace the main PCB directly Otherwise check whether the EEPROM chip is plugged into ma...

Страница 22: ...main PCB connected correctly Is the reactor connected well Power on Is the error extinguished Replace the indoor main PCB No Yes Measure the resistance of the reactor the one without capacitor If it...

Страница 23: ...ng signal feedback for 4 minutes or the zero crossing signal time interval is abnormal Possible Causes Connection mistake Defective PCB Trouble shooting Check if the connections and power supply is no...

Страница 24: ...he wires of fan motor Are all the connections good No Yes No Correct the connections No Yes Check whether the main PCB is normal through index 2 Yes Yes Check whether the fan motor is normal through i...

Страница 25: ...the LED will display the failure Possible Causes Wiring mistake Defective sensor Defective PCB Trouble shooting Check the connections between temperature sensor and main PCB Are the connections good...

Страница 26: ...continuity check Check if the IPM terminal resistance values are uniform Replace the IPM board or replace the main PCB if the IPM board and main PCB are integrated together No Check if the outdoor fan...

Страница 27: ...it with power supply and try to restart the unit when power supply is good No Yes No Correct the connections or replace the wires Yes Power on and when the unit is in standby check if the voltage betw...

Страница 28: ...eat exchanger of indoor and outdoor units Yes No Yes Yes Turn off the power supply and turn it on 10 minutes later Check if the unit can start normally No Check if the refrigerant charge volume is nor...

Страница 29: ...s and connectors Yes No IPM continuity check Check if the IPM terminal resistance values are uniform Replace the IPM board or replace the main PCB if the IPM board and main PCB are integrated together...

Страница 30: ...nce Value at 68_F 20_C Unit size 9K and 12K Unit size 17 18K Unit size 22K Blue Red 0 71 1 77 0 95 Blue Black Red Blue IPM continuity check Turn off the power let the large capacity electrolytic capac...

Страница 31: ...70 59 0 82 0 78 0 81 0 86 1 01 MPA 75 63 0 86 0 83 0 87 0 91 1 07 MPA 80 67 0 93 0 89 0 91 0 96 1 12 Heating Chart _F _C IDT ODT 57 53 14 12 47 43 8 6 37 33 3 1 27 23 3 5 17 13 8 11 PSI 55 439 413 36...

Страница 32: ...or 38 40MFC Q 012 3 A2 Control Board Input Output Values for 38 40MFC018 3 AC 38 40MFC017 3 HP A3 Control Board Input Output Values for 38 40MFC Q 022 3 A4 Temperature Sensor Values Temperature vs Res...

Страница 33: ...009 1 40MFC Q 012 1 CONTROL BOARD INPUT or OUTPUT VALUE CN1 Output Pin5 6 12V Pin1 Pin4 Pulse waveform 0 12V CN14 Input Pin1 3 3V Pin2 0 3 3V Normal value about3 3V CN15 Input Pin1 0 1 8V Pin2 1 8V CN...

Страница 34: ...ween the lines DC5V CONNECTOR 40MFC Q 012 3 CONTROL BOARD INPUT or OUTPUT VALUE CN14 Input Pin1 5V Pin2 0 5V Normal value about3 3V CN15 Input Pin1 5V Pin2 0 5V CN16 Input Pin3 Pin4 5V Pin1 Pin5 0 5V...

Страница 35: ...ltage DC5V CN10A Maximum voltage between the lines DC5V CONNECTOR 40MFC018 3 AC 40MFQ017 3 HP CONTROL BOARD INPUT or OUTPUT VALUE CN101 Input Pin1 5V Pin2 0 5V Normal value about5V CN102 Input Pin1 5V...

Страница 36: ...4 5V Pin1 Pin5 0 5V CN1 CN2 Output 230V High voltage CN11 CN22 Output Pin1 Pin5 0 230VHigh voltage CN10 CN13 Output 230V High voltage CN5 Output 230V High voltage CN6 Input 230V High voltage CN3 Input...

Страница 37: ...078 117 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2133 119 246 0 36954 0 32 35 2024 40 104 5 17519 80 176 1 17393 120 248 0 35982 1 34...

Страница 38: ...422 4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100 31 62 78 172 7 321 118 244 2 233 1 30 190 5 39 102 30 36 79 174 7 086 119 246 2...

Страница 39: ...oor unit EEPROM parameter error 1 l 1 times l P0 IPM malfunction or IGBT over strong current protection 6 l 2 times l P1 Over voltage or over low voltage protection 7 l 3 times l P2 High temperature p...

Страница 40: ...r Corp S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38 40MF 1SM Replace...

Отзывы: