background image

38MARB: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

81

APPENDICIES

Appendix 1

Table 21 — Temperature Sensor Resistance Value Table for T1, T2, T3, T4 (°C--K)

°C 

°F 

K Ohm

°C 

°F 

K Ohm

°C 

°F 

K Ohm

°C 

°F 

K Ohm

20

-4

115

.

266

20

68

12

.

6431

60

140

2

.

35774

100

212

0.

62973

19

-2

108

.

146

21

70

12

.0

561

61

142

2

.

27249

101

214

0.

61148

18

0

101

.

517

22

72

11.5

62

144

2

.

19

0

73

102

216

0.

59386

17

1

96

.

3423

23

73

10

.

9731

63

145

2

.

11241

103

217

0.

57683

16

3

89

.

5865

24

75

10

.

4736

64

147

2

.

03732

104

219

0.

56

0

38

15

5

84

.

219

25

77

10

65

149

1

.

96532

105

221

0.

54448

14

7

79

.

311

26

79

9

.

55

0

74

66

151

1

.

89627

106

223

0.

52912

13

9

74

.

536

27

81

9

.

12445

67

153

1

.

83

00

3

107

225

0.

51426

12

10

70

.

1698

28

82

8

.

71983

68

154

1

.

76647

108

226

0.

49989

11

12

66

.0

898

29

84

8

.

33566

69

156

1

.

70547

109

228

0.

486

10

14

62

.

2756

30

86

7

.

97

0

78

70

158

1

.

64691

110

230

0.

47256

-9

16

58

.

7

0

79

31

88

7

.

62411

71

160

1

.

59

0

68

111

232

0.

45957

-8

18

56

.

3694

32

90

7

.

29464

72

162

1

.

53668

112

234

0.

44699

-7

19

52

.

2438

33

91

6

.

98142

73

163

1

.

48481

113

235

0.

43482

-6

21

49

.

3161

34

93

6

.

68355

74

165

1

.

43498

114

237

0.

423

0

4

-5

23

46

.

5725

35

95

6

.

40

0

21

75

167

1

.

387

0

3

115

239

0.

41164

-4

25

44

36

97

6

.

13

0

59

76

169

1

.

341

0

5

116

241

0.

40

0

6

-3

27

41

.

5878

37

99

5

.

87359

77

171

1

.

29

0

78

117

243

0.

38991

-2

28

39

.

8239

38

100

5

.

62961

78

172

1

.

25423

118

244

0.

37956

-1

30

37

.

1988

39

102

5

.

39689

79

174

1

.

2133

119

246

0.

36954

0

32

35

.

2

0

24

40

104

5

.

17519

80

176

1

.

17393

120

248

0.

35982

1

34

33

.

3269

41

106

4

.

96392

81

178

1

.

136

0

4

121

250

0.

35

0

42

2

36

31

.

5635

42

108

4

.

76253

82

180

1

.

09958

122

252

0.

3413

3

37

29

.

9

0

58

43

109

4

.

57

0

5

83

181

1

.

06448

123

253

0.

33246

4

39

28

.

3459

44

111

4

.

38736

84

183

1

.

03

0

69

124

255

0.

3239

5

41

26

.

8778

45

113

4

.

21263

85

185

0.

99815

125

257

0.

31559

6

43

25

.

4954

46

115

4

.

04589

86

187

0.

96681

126

259

0.

30754

7

45

24

.

1932

47

117

3

.

88673

87

189

0.

93662

127

261

0.

29974

8

46

22

.

5662

48

118

3

.

73476

88

190

0.

90753

128

262

0.

29216

9

48

21

.

8

0

94

49

120

3

.

58962

89

192

0.

8795

129

264

0.

28482

10

50

20

.

7184

50

122

3

.

45

0

97

90

194

0.

85248

130

266

0.

2777

11

52

19

.

6891

51

124

3

.

31847

91

196

0.

82643

131

268

0.

27

0

78

12

54

18

.

7177

52

126

3

.

19183

92

198

0.

80132

132

270

0.

264

0

8

13

55

17

.

8

00

5

53

127

3

.

07

0

75

93

199

0.

777

0

9

133

271

0.

25757

14

57

16

.

9341

54

129

2

.

95896

94

201

0.

75373

134

273

0.

25125

15

59

16

.

1156

55

131

2

.

84421

95

203

0.

73119

135

275

0.

24512

16

61

15

.

3418

56

133

2

.

73823

96

205

0.

70944

136

277

0.

23916

17

63

14

.

6181

57

135

2

.

63682

97

207

0.

68844

137

279

0.

23338

18

64

13

.

918

58

136

2

.

53973

98

208

0.

66818

138

280

0.

22776

19

66

13

.

2631

59

138

2

.

44677

99

210

0.

64862

139

282

0.

22231

Содержание 38MARB

Страница 1: ...fies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices...

Страница 2: ...Q30AA3 3 00 36 000 38MARBQ36AA3 OUTDOOR UNIT 38 MA R B Q 36 3 38 OUTDOOR UNIT MA MODEL VOLTAGE 1 115 1 60 3 208 230 1 60 SYSTEM TYPE R OUTDOOR MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO...

Страница 3: ...d shielded wire can be used to replace L2 and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only NOTE Matches with multi family and residential fan coils re...

Страница 4: ...1 Connection Diagram 12K 115V Fig 2 Connection Diagram 6K 12K 208 230 1 60V Fig 3 Connection Diagram 24K 36K 208 230 1 60V NOTES 1 Do not use thermostat wire for any connection between indoor and out...

Страница 5: ...iagram Size 12K 115V Table 3 Wiring Diagram Size 12K 115V CN2 7 8 Input 115V AC CN18 Output 0 12V DC CN414 Output 0 160V AC CN60 Output 115V AC CN17 Input 0 5V DC CN16 Output 115V AC CN19 Output 115V...

Страница 6: ...ng Diagram Sizes 6 12K 208 230V Table 5 Wiring Diagram Sizes 6 12K 208 230V CN1A Input 230V AC CN31 Output 0 12V DC CN7 Output 0 310V AC CN60 Output 230V AC CN21 Input 0 5V DC CN15 Output 230V AC CN17...

Страница 7: ...Size 18K 208 230V Table 7 Wiring Diagram Size 18K 208 230V CN1A Input 230V AC CN4_2 4_3 Input 230V AC CN7 Output 0 310V AC CN60 Output 230V AC CN21 Input 0 5V DC CN31 Output 0 12V DC CN15 Output 230V...

Страница 8: ...P Compressor Top OLP Temperature Sensor EEV Electronic Expansion Valve FM1 DC Fan Motor COMP Compressor HEAT_Y Crankcase Heater CT1 AC Current Detector H PRO High Pressure Switch L PRO Low Pressure Sw...

Страница 9: ...H RI KHDW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 6 8 0XIIOHU ZD YDOYH...

Страница 10: ...VKDSH RI KHDW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 71 8 0XIIOHU ZD...

Страница 11: ...VKDSH RI KHDW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 71 8 0XIIOHU ZD...

Страница 12: ...DW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 70 8 7 0XIIOHU ZD YDOYH 0XI...

Страница 13: ...KHDW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 70 8 7 0XIIOHU ZD YDOYH 0...

Страница 14: ...KHDW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 7 807 0XIIOHU ZD YDOYH 0...

Страница 15: ...HDW LQVXODWRU OORZDEOH KHLJKW GLIIHUHQFH IW P OORZDEOH SLSH OHQJWK 3XOVH 0RGXODWLQJ 9DOYH DW OLTXLG VLGH 6WUDLQHU 3URSHOOHU IDQ 2XWGRRU KHDW H FKDQJHU RPSUHVVRU PRGHO QXPEHU 7 807 0XIIOHU ZD YDOYH 0XI...

Страница 16: ...up to the allowable length as specified in Table 10 Long Line Applications 1 No change in line sizing is required 2 Add refrigerant per Table 10 Table 10 Additional Charge System Size 12K 6K 9K 12K 1...

Страница 17: ...ig 17 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should be used Refer to Fig 18 and proceed as follows 1 Pump system down to 500 MICRONS of mercury and allow pump to conti...

Страница 18: ...stops and the LED displays the failure The correct zero crossing signal time interval should be between 6 13ms Sensor protection at open circuit and breaking disconnection If only one temperature sens...

Страница 19: ...etting value the compressor stops HEATING Mode Compressor Running Rules When T1 Ts T the compressor stops When T1 Ts T 1 5 the compressor is on T is the programmed parameter for temperature compensati...

Страница 20: ...door temperature reaches the setting temperature the compressor stops the indoor fan motor runs at the minimum speed or setting speed The anti cold air function is valid The indoor fan is controlled a...

Страница 21: ...o exit the FORCED DEFROSTING mode press and hold AUTO COOL for 5s again Fig 27 Defrost Chart Defrost Exit Conditions Any of the following conditions will cancel the DEFROST mode and change the unit to...

Страница 22: ...OPERATION function When the machine is off press TOUCH to engage the Forced Auto Mode Press TOUCH again within 5 seconds to engage the FORCED COOLING mode In FORCED AUTO FORCED COOLING or any other o...

Страница 23: ...the digital code Press OK to send as well Table 12 Inquiry Codes and Symbols To exit the Inquiry Mode Press and hold together the On Off and Fan buttons for 2 seconds CODE INQUIRY SYMBOL DESCRIPTION...

Страница 24: ...ly is shut off NOTE Remember to discharge the electricity power in capacitor Fig 30 Electrolytic Capacitors For other models connect discharge resistance approximately 100 40W or a soldering iron plug...

Страница 25: ...it or has short circuited Page 35 5 times X EC 54 Compressor discharge temperature sensor TP is an open circuit or has short circuited 5 times X EC 56 Evaporator coil outlet temperature sensor T2B is...

Страница 26: ...EN LED2 RED IU DISPLAY SOLUTION 1 IPM malfunction or IGBT over strong current protection X P0 Page 39 2 Over voltage or too low voltage protection O O P1 Page 42 3 EEPROM parameter error O E5 Page 27...

Страница 27: ...ameter Error or Compressor Driven Chip EEPROM Parameter Error EC51 Description Outdoor PCB main chip does not receive feedback from the EEPROM chip or the compressor driven chip Recommended parts to r...

Страница 28: ...ng connection from indoor terminal to indoor PCB Are they OK Turn on the unit check if W and 1 L are connected Check that the power LED is on No Yes Yes Unplug all the high voltage components connecte...

Страница 29: ...e black pin is for 3 port or N or S port the unit is normal running the voltage is moving alternately as positive values and negative values If the outdoor unit has malfunction the voltage will remain...

Страница 30: ...sing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal Recommended parts to repair Connection wires Indoor main PCB Troubleshooting and Repair Note Zero crossing dete...

Страница 31: ...the unit turns off Recommended parts to repair Connection wires Indoor main PCB Fan assembly Indoor main PCB Troubleshooting YES Turn the power off Wait 2 minutes then restart Is it within normal para...

Страница 32: ...otor Outdoor main PCB Troubleshooting NOTE For certain models outdoor PCB could not be removed separately In this case the outdoor electric control box should be replaced as a whole YES Power off Afte...

Страница 33: ...erwise proceed to step 2 2 Power on the unit and when the unit is in standby measure the pin4 5 voltage in the feedback signal connector If the value is not 5V change the PCB Otherwise proceed to step...

Страница 34: ...is lower than 0 06V or higher than 4 94V the LED displays the failure code Recommended parts to repair Connection wires Sensors Indoor main PCB Troubleshooting Fig 33 Test NOTE Figure 33 and the valu...

Страница 35: ...onnection wires Sensors outdoor main PCB Troubleshooting Fig 34 Test NOTE For certain model the outdoor PCB could not be removed separately In this case the outdoor electric control box should be repl...

Страница 36: ...than 50Hz however it does not maintain for a minimum of three minutes and this issue occurs 3 times the LED displays the failure code and the unit turns off Recommended parts to repair T2 Sensor Indo...

Страница 37: ...r PCB does not receive feedback from the display board Recommended parts to repair Communication wire Indoor PCB Display board Troubleshooting Is it still displaying the error code The unit functions...

Страница 38: ...the power wiring Are the L and N wired properly Reconnect L and N Replace the outoor main PCB Is the voltage between L and N normal Is the current normal Power on and measure the voltage between P an...

Страница 39: ...tdoor PCB Troubleshooting YES NO Is the IPM terminal resistance uniform NO YES Please refer to the Fan Speed is operating outside of normal range malfunction NO YES YES NO YES NO Check the wiring betw...

Страница 40: ...the electrolytic capacitors and ensure all the energy storage has been discharge 3 Disassemble the outdoor PCB or disassemble the IPM board 4 Measure the resistance value between P and U V W N U V W a...

Страница 41: ...ut notice and without obligations 41 DIAGNOSIS AND SOLUTION CONT Compressor Check Disconnect the compressor and check the resistance between U V V W and U W and all 3 values should be equal If not the...

Страница 42: ...o repair Power supply wires IPM module board PCB Reactor Troubleshooting Check the power supply Is it in working order Turn off the unit NO Check the connections and wires YES Are they in working orde...

Страница 43: ...blockages Troubleshooting NOTE For certain models the outdoor PCB can not be removed separately In this case the outdoor electric control box should be replaced as a whole Check if the air flow system...

Страница 44: ...ure protector broken Check if the outdoor unit ventilation is good Ensure that the outdoor unit s ventiliation is functioning properly High pressure protection Connect the high pressure switch and mai...

Страница 45: ...mmended parts to repair Connection wires IPM module board Outdoor fan assembly Compressor Outdoor PCB Troubleshooting Check the wiring between the PCB and the compressor Is it improperly wired Ensure...

Страница 46: ...connect the low pressure protector and the main control board Is the low pressure protector broken Method Disconnect the plug Measure the low pressure protector resistance If the protector is normal t...

Страница 47: ...he priority Examples If indoor unit A is operating in the COOLING mode or the FAN mode and indoor unit B is set to the HEATING mode unit A will power off and unit B will continue to operate in the HEA...

Страница 48: ...tdoor Main Chip and Compressor Driven Chip PC40 Description The main chip cannot detect the compressor driven chip Recommended parts to repair Outdoor PCB Electric control box Troubleshooting YES NO N...

Страница 49: ...sor Check 1 Disconnect the temperature sensor from PCB 2 Measure the sensor s resistance value using a multi meter 3 Check the corresponding temperature sensor s resistance value table Fig 36 Test Be...

Страница 50: ...Check 1 Disconnect the compressor power cord from the outdoor PCB 2 Measure the resistance valve of each winding using a multi meter 3 Check the resistance valve of each winding in Table 16 Table 16...

Страница 51: ...s and ensure all energy has been discharged 3 Dissemble the outdoor PCB or dissemble the IPM board 4 Measure the resistance valve between P and U V W N U V W and N Fig 38 Testing Digital Tester Resist...

Страница 52: ...wer on use a digital tester to measure the voltage when the unit operates in the COOLING mode the voltage is 0V If the voltage value is not in range the PCB is faulty and needs to be replaced Fig 39 M...

Страница 53: ...e of each winding using a multi meter 3 Check the resistance value of each winding in Table 17 Fig 41 EXV Check Table 17 Winding Colors LEAD WINDING COLOR NORMAL VALUE Red Blue About 50 Red Yellow Bro...

Страница 54: ...1 Temperature sensor checking Disconnect the temperature sensor from PCB measure the resistance value with a tester Fig 42 Tester Temperature sensors Room temp T1 sensor Indoor coil temp T2 sensor Out...

Страница 55: ...44 7 1 7 2 8 5 9 5 9 3 8 9 9 1 9 6 11 2 11 9 90 73 32 22 22 78 7 7 7 8 9 6 10 5 10 3 9 5 10 0 10 6 12 4 13 0 PSI 70 59 21 11 15 93 94 106 116 119 113 117 125 147 154 75 63 23 89 17 22 97 99 115 125 12...

Страница 56: ...2 78 0 56 27 23 2 78 5 17 13 8 33 10 56 0 2 17 19 17 18 27 28 BAR 55 12 78 30 3 28 5 25 3 22 8 20 8 18 5 16 5 65 18 33 32 5 30 0 26 6 25 4 23 3 20 5 19 0 75 23 89 33 8 31 5 27 8 26 3 24 9 21 5 20 0 P...

Страница 57: ...52 596 126 673 1050 10 5 152 25 8 901 48 022 3300 33 478 5 53 27 127 886 1100 11 159 5 10 471 50 848 3350 33 5 485 75 53 935 129 083 1150 11 5 166 75 11 988 53 578 3400 34 493 54 593 130 267 1200 12...

Страница 58: ...Unit Sizes 12 115V and 6 12K 208 230V Panel Plate NOTE This part is for reference only and the photos may differ from your actual unit Procedure Illustration 1 Turn off the air conditioner and the po...

Страница 59: ...ns without notice and without obligations 59 Procedure Illustration 4 Remove the water collecting cover screws 2 then remove the water collecting cover 5 Remove the front panel screws and then remove...

Страница 60: ...Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 60 Procedure Illustration 6 Remove the right panel screws 5 then remove the rig...

Страница 61: ...es 18K 208 230V Panel Plate NOTE This part is for reference only and the photos may differ from your actual unit Procedure Illustration 1 Turn off the air conditioner and the power breaker 2 Remove th...

Страница 62: ...gns without notice and without obligations 62 Procedure Illustration 4 Remove the water collecting cover screws 2 then remove the water collecting cover 5 Remove the front panel screws then remove the...

Страница 63: ...Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 63 Procedure Illustration 6 Remove the right panel screws 6 then remove the rig...

Страница 64: ...24 36K 208 230V Panel Plate NOTE This part is for reference only and the photos may differ from your actual unit Procedure Illustration 1 Turn off the air conditioner and the power breaker 2 Remove t...

Страница 65: ...time specifications and designs without notice and without obligations 65 Procedure Illustration 4 Remove the front right panel screws 2 and then remove the front right panel 5 Remove the front panel...

Страница 66: ...t any time specifications and designs without notice and without obligations 66 Procedure Illustration 6 Remove the water collecting cover screws 2 then remove the water collecting cover 7 Remove the...

Страница 67: ...Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 67 Procedure Illustration 8 Remove the right panel screws 8 then remove the rig...

Страница 68: ...d without obligations 68 ELECTRICAL PARTS PCB Board 12K 115V Procedure Illustration 1 Disconnect the compressor connector and release the ground wire 1 screw 2 Pull out the wires from the electrical s...

Страница 69: ...ht to change at any time specifications and designs without notice and without obligations 69 Procedure Illustration 4 Remove the board 2 hooks 5 Disconnect the connectors from the electronic control...

Страница 70: ...ce and without obligations 70 PCB Board 6K 12K 208 230V Procedure Illustration 1 Disconnect the compressor connector and release the ground wire 1 screw 2 Pull out the wires from the electrical suppor...

Страница 71: ...ht to change at any time specifications and designs without notice and without obligations 71 Procedure Illustration 4 Remove the board 2 hooks 5 Disconnect the connectors from the electronic control...

Страница 72: ...box cover 5 screws and 2 hooks 2 Disconnect the fan motor connector motor from the electronic control board 3 Remove the compressor connector 4 Pull out the two blue wires connected with the four way...

Страница 73: ...ecifications and designs without notice and without obligations 73 PCB Board 24K 36K 208 230V Procedure Illustration 1 Loosen the hooks 4 then open the electronic control box cover 2 Remove the screws...

Страница 74: ...cturer reserves the right to change at any time specifications and designs without notice and without obligations 74 Procedure Illustration 3 Pull out the connectors 4 Remove the 4 screws then remove...

Страница 75: ...nd without obligations 75 Fan Assembly Fan Motor NOTE Remove the panel plate and the connection of fan motor on PCB before disassembling fan motor Procedure Illustration 1 Remove the nut securing the...

Страница 76: ...turer reserves the right to change at any time specifications and designs without notice and without obligations 76 Sound Blanket Procedure Illustration 1 Remove the sound blanket side and top Sound B...

Страница 77: ...rant left in the system before removing the four way valve and the compressor For R32 R290 evacuate the system with the vacuum pump flush the system with nitrogen then repeat the two steps before heat...

Страница 78: ...confirm that there is no refrigerant left in the system before removing the four way valve and the compressor For R32 R290 you should evacuate the system with the vacuum pump flush the system with ni...

Страница 79: ...tice and without obligations 79 Procedure Illustration 3 Remove the hex nuts and washers securing the compressor located on the bottom plate 4 Heat up the brazed parts and then remove the discharge pi...

Страница 80: ...oltage is lower than 36V the capacitors are fully discharged Fig 45 Testing Be sure to turn off all the power supplies or disconnect all wires to avoid electric shock While checking the indoor or outd...

Страница 81: ...36 97 6 13059 76 169 1 34105 116 241 0 4006 3 27 41 5878 37 99 5 87359 77 171 1 29078 117 243 0 38991 2 28 39 8239 38 100 5 62961 78 172 1 25423 118 244 0 37956 1 30 37 1988 39 102 5 39689 79 174 1 2...

Страница 82: ...37 3 74 165 8 358 114 237 2 489 5 23 234 9 35 95 35 78 75 167 8 084 115 239 2 422 4 25 222 8 36 97 34 32 76 169 7 82 116 241 2 357 3 27 211 4 37 99 32 94 77 171 7 566 117 243 2 294 2 28 200 7 38 100 3...

Страница 83: ...4 3 37 4 31 87 8 62 143 6 93 199 4 124 255 2 3 5 38 3 32 89 6 63 145 4 94 201 2 125 257 4 39 2 33 91 4 64 147 2 95 203 126 258 8 4 5 40 1 34 93 2 65 149 96 204 8 127 260 6 5 41 35 95 66 150 8 97 206...

Страница 84: ...ed A Carrier Company Edition Date 07 21 Catalog No SG 38MARB 02 Replaces SG 38MARB 01 38MARB Service Manual Manufacturer reserves the right to change at any time specifications and designs without not...

Отзывы: