DIAGNOSIS AND SOLUTION (CONT)
Indoor Units Mode Conflict (match with multi outdoor unit)
Description:
The indoor units cannot operate in the
COOLING
mode and
HEATING
mode simultaneously. The
HEATING
mode is the priority.
Examples:
• If indoor unit A is operating in the
COOLING
mode or the
FAN
mode, and indoor unit B is set to the
HEATING
mode, unit A will power off and
unit B will continue to operate in the
HEATING
mode.
• If indoor unit A is operating in the
HEATING
mode and indoor unit B is set to the
COOLING
mode or fan mode, unit B will change to
STANDBY
mode and unit A will not change modes.
NOTE:
No
: No mode conflict
Yes
: Mode conflict
Cooling Mode Heating Mode
Fan
Off
Cooling Mode
No
Yes
No
No
Heating Mode
Yes
No
Yes
No
Fan
No
Yes
No
No
Off
No
No
No
No