background image

38GL_M…G / 38YY(S)_M…G 

GB - 19

E N G L I S H

Unit maintenance and troubleshooting

Unit maintenance

The following maintenance operations must be carried out by
qualified personnel.

Cleaning the coil
When necessary, proceed as follows for more careful cleaning of
the coil:

Switch the mains supply OFF.
Remove unit top cover by losening holding screws and lifting the
cover.

Carefully clean the coil with a vacuum cleaner from inside to
outside.
With the same vacuum cleaner, dust the inside of the fan
compartment and the fan blades. Avoid any damage to the blades
which may cause future vibrations and noise.

Replace the unit cover and tighten the screws.

If the unit is started for the first time after a long period
during which it has been disconnected from the mains power
supply (for heat pump units only).
Energize the system by pressing the main switch, but do not start
the system (the remote controller must be in the OFF position).
Do not de-energize the unit during  the operating season.

Troubleshooting

Before starting troubleshooting check the correct operation
of all fuses installed on the electronic cards (if any).

Compressor and fan of the outdoor unit do not start:
• Unit is not energized; check the mains power connections.
• Main switch OFF; check and put to the ON position.
• Main switch fuses have blown; replace.
• Wait for 3 minutes; compressor cycling protection is on.
• Accessory pressure switch open; check and eliminate cause.
• Mains voltage too low.
• Electrical connections loose or wrong; check and repair.

Compressor will not start, but outdoor fan is running:
• Electrical connections of compressor loose or wrong; check and

repair.

• Compressor burnt out, seized or protection device on; check for

the cause and replace compressor if necessary.

• Faulty run capacitor for the single-phase models; replace it.

Compressor starts, but stops due to its overtemperature
protection (other than stops caused by the normal operation
of the thermostat):
• Wrong refrigerant charge (excessive or low) or air or other non

condensable gases in the circuit; drain refrigerant (see note 1),
evacuate and recharge.

• Mains voltage wrong (too high or too low).
• Condenser coil obstructed; remove obstructions.
• Outdoor fan off; check cause and repair.
• Run capacitor faulty; check and replace.
• Refrigerant circuit clogged; check and remove obstructions.
• Faulty reversing valve; replace it.
• Expansion device clogged or covered with ice; drain refrigerant

(see note 1), evacuate and recharge.

Compressor runs continuously:
• Unit selected too small for actual air conditioning needs.
• Indoor temperature selection too low (cooling)  or too high (heat

pump heating); check temperature selection.

• Refrigerant charge low; check and add refrigerant.
• Condenser fan faulty; replace.
• Air or other non condensable gases in the circuit; drain

refrigerant (see note 1), evacuate and recharge.

• Obstructions at air intake or dirty indoor unit filters; remove

obstruction or clean filter.

Ice on the outdoor coil (heat pump heating):
• Outdoor fan is off; check for cause and repair.
• Wrong electrical connection between indoor and outdoor units;

check and repair the electric connections.

• Check the correct positioning and connection of the outdoor coil

sensors.

Discharge pressure too high:

• Outdoor coil dirty or obstructed; clean or remove obstructions.
• Condenser fan faulty; replace.
• Refrigerant charge too high; drain some refrigerant (see note 1).
• Air or other non-condensable gases in the circuit; drain

refrigerant (see note 1), evacuate and recharge.

Discharge pressure too low:
• Refrigerant charge too low; add refrigerant.
• Outdoor coil dirty or obstructed; clean or remove obstructions.
• Indoor unit air filter dirty; clean filter.

Suction pressure too high:
• Refrigerant charge too high; drain some refrigerant (see note 1).
• Internal high pressure relief valve open; check for cause and

repair.

Suction pressure too low:

• Refrigerant charge too low; add refrigerant.
• Evaporator coil covered with ice; see the following points.
• Air circulation on the evaporator unit not sufficient; check for the

cause and repair.

• Expansion device or suction line clogged: check and repair.
• Outdoor unit fan does not stop during defrosting (heat pump

heating); check the connections.

Outdoor fan motor runs always at low speed:
• The cable is not connected to the card; check connections

between the temperature sensor and the card.

• Faulty temperature sensor; replace the sensor.
• Faulty electronic card; replace it.

Outdoor fan motor runs always at high speed:
• Short-circuited temperature sensor; replace the sensor.
• Faulty electronic card; replace it.

Outdoor fan does off or starts and stops due to its
overtemperature protection:
• Faulty fan motor capacitor; replace it.
• Electrical connections to the fan motor are loose; check and

tighten connections.

• Fan motor burnt-out; replace it.
• Fan motor bearings seized; check for cause and repair.
• Expansion device clogged or covered with ice; drain refrigerant

(see note 1), evacuate and recharge.

Note 1:
Do not release refrigerant to the atmosphere; use
refrigerant recovery equipment.

Содержание 38GL2M12G

Страница 1: ...38GL_M G 38YY S _M G INSTALLATION MANUAL...

Страница 2: ...ate with R 410A R 410A refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube which allows liquid to flow out of cylinder in an upright position In case of maintenance R 410A syst...

Страница 3: ...0 300 300 300 300 D mm 390 508 508 508 508 508 508 508 E mm 135 146 146 146 146 146 146 146 F mm 250 330 330 330 330 330 330 330 kg kg 39 55 58 58 75 69 109 112 Cooling Hi Wall Console Cassette Satell...

Страница 4: ...dels 38GL2M12G 38GL3M21G 38YY2M21G 38GL3M30G 38YY2M24G 38GL4M24G 38YY S 2M36G 38YY2M18G 38YY S 2M48G A mm 50 100 100 B mm 250 250 250 C mm 500 500 500 D mm 50 50 100 E mm 470 470 670 F mm 400 400 400...

Страница 5: ...pper pipe be used Pipe diameter Model Liquid Gas 38YY S Indoor Liquid Suction unit mm inches mm inches 2M18G A 6 35 1 4 9 52 3 8 B 6 35 1 4 9 52 3 8 2M21G A 6 35 1 4 9 52 3 8 B 6 35 1 4 12 70 1 2 2M24...

Страница 6: ...o 10 C see table VI Accessories for kit availability d b dry bulb w b wet bulb WARNING During heat pump operation unit will undergo several defrost cycles to eliminate ice that might possibly collect...

Страница 7: ...ins supply circuit The mains supply must be connected to the outdoor unit Connect indoor and outdoor units with field supplied copper pipes by means of flare connections Use insulated seamless refrige...

Страница 8: ...to get wet before connection Disconnecting the refrigerant connections after installation thiis will cause refrigerant leaks Connecting the condensate drain pipe to the outdoor unit Predominant head w...

Страница 9: ...dust No leak No mineral oil Neat Dry nitrogen brazing Vacuum Min 100 kPa 755 mmHg Charge liquid no gas Copper tubes during storage Use tools designed for R 410A higher pressure Keep inside clean 2 sta...

Страница 10: ...th a reamer Do not leave system open to atmosphere any longer than minimum required for installation Oil in the compressor is extremely susceptible to moisture absorption Always keep ends of tubing se...

Страница 11: ...mp connected to the service connection of the suction shut off valve as shown keeping the shut off valves completely shut until a 100 Pa 1 bar vacuum has been reached Now open the two way valve for 3...

Страница 12: ...must always be made through the outdoor unit If the indoor units are provided with heaters their power supply must be ensured by indoor sections L N R C Y R C Y A2 A1 L N R C Y R C Y A2 A1 L N R C Y...

Страница 13: ...oor unit C Neutral connection indoor outdoor unit Y Compressor interlocking contact Mod 38GL3M30G L N R C Y R C Y L N N A1 A2 230V 50Hz Y L N N Y 230V 50Hz R C Y L N R C Y B A1 A2 B L N R C Y R C Y R...

Страница 14: ...er supplies If the indoor units are provided with heaters their power supply must be ensured by indoor sections Mod 38GL2M36G 38GL2M48G Mod 38GL4M24G R C Y R C Y R C Y R C Y A1 A2 B1 B2 N N Y L N N Y...

Страница 15: ...power supply must be ensured by indoor sections Indoor units which are connected to the heat pump units need the Multisplit configuration by remote controller The two heat pump circuits can operate si...

Страница 16: ...mode The system will not operate if circuit A is not energized Terminal box legend Earth L Live power supply N Neutral power supply R Live connection indoor outdoor unit C Neutral connection indoor o...

Страница 17: ...on with neoprene coating 6 If the indoor unit is provided with an electric heater consult indoor unit installation manual for correct sizing of the wires 7 Electrical input refer to each one of the tw...

Страница 18: ...at high velocity Compressor will immediately start provided 3 minutes have elapsed since the last stop After 2 minutes of operation shut the suction valve with the same wrench Turn the system off and...

Страница 19: ...ressor Outdoor unit coil Filter Expansion device Capillary Expansion device Accurater Distributor Solenoid valve Service valve Indoor unit coil A1 Indoor unit coil A2 Indoor unit coil B1 Indoor unit c...

Страница 20: ...ain refrigerant see note 1 evacuate and recharge Compressor runs continuously Unit selected too small for actual air conditioning needs Indoor temperature selection too low cooling or too high heat pu...

Страница 21: ...wires are cut or sensor is faulty 3 Circuit A coil Unit is stopped Automatic Sensor is out of scale or not temperature sensor is faulty connected to the card sensor wires are cut or sensor is faulty...

Страница 22: ...L010127H20 1105 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice November 2005 Printed in Italy...

Отзывы: