Carrier 38FZ/BZ 024 Скачать руководство пользователя страница 36

36

Sizing

Fig. 37 - Suction line

Pressure drop/10 m eqivalent length

Fig. 38 - Discharge line

Pressure drop/10 m eqivalent length

Legend:

1

Size 024

2

Size 036

2

Size 042

3

Size 048

4

Size 060

5

Size 072

6

Size 084

From Figure 38, for the selected unit we can obtain the pres-
sure drop corresponding to 10 m of equivalent length for each
diameter.

For other equivalent lengths, the pressure drop is obtained in
direct proportion. The total pressure drop for the line (sum
corresponding to the vertical and horizontal pipe runs) must not
be higher than 20 kPa.

Liquid line:

The liquid line diameter can be selected using table 6.

Table 6 - Liquid line

Size

Total equivalent length

Up to 10 m

From 10-30 m

From 30-50 m

024

3/8"

3/8"

3/8"

036

3/8"

3/8"

1/2"

042

3/8"

3/8"

1/2"

048

3/8"

1/2"

1/2"

060

3/8"

5/8"

5/8"

072

5/8"

5/8"

5/8"

084

5/8"

5/8"

3/4"

Necessary checks/precautions before start-up

-

Ensure that all electrical connections are properly
tightened.

-

Ensure that the unit is level and well-supported.

-

Check the condition of the ductwork in case damage has
occurred during installation.

-

The air filter should be clean and in place.

-

All the panels should be fitted and firmly secured with the
corresponding screws.

-

Make sure that there is sufficient space for servicing and
maintenance purposes.

-

Check the drain connections.

-

Ensure that there are no refrigerant leaks.

-

Confirm that the electrical power source agrees with the
unit nameplate rating.

-

Make sure that compressors float freely on the mounting
springs.

WARNING: The compressors are mounted on vibration
isolators. Do not loosen or remove the support mounting bolts.

Refrigerant charge

Gas tightness testing and dehydration

50TZ/YZ units are shipped fully charged with refrigerant R-407C
ready for operation. If, when the unit is run, symptoms of loss
of charge (for example, low pressure switch tripping or
abnormally low cooling capacities) are detected, first conduct a
leak test followed, if necessary, by a gas tightness test using
compressed nitrogen. For the latter all refrigerant must be
removed from the circuit. Transfer the refrigerant to a storage
tank and then rinse the circuit. For your information, we are
listing here some precautions that need to be taken into
consideration, when working with these units.

Refrigerant guidelines for R-407C

Refrigerant R-407C consists of a non-azeotropic blend of 23%
of R-32, 25% of R-125 and 52% of R-134a, and is character-
ised by the fact that at the time of the change in state the
temperature of the liquid/vapour mixture is not constant. All
checks must be pressure tests, and the appropriate pressure/
temperature ratio table must be used for the interpretation of
the values.

Leak detection is especially important for units charged with
refigerant R-407C. Depending on whether the leak occurs in
the liquid or the vapour phase, the proportion of the different
components in the mixture remaining in the unit is not the
same.

SPEED (m/s)

Содержание 38FZ/BZ 024

Страница 1: ...gle Package Cooling Units and Heat Pumps Installation operation and maintenance instructions Carrier is participating in the Eurovent Certification Programme Products are as listed in the Eurovent Dir...

Страница 2: ...rical connection between units 34 Thermostat connection 34 REFRIGERANT LINE CONNECTIONS 35 Refrigerant line selection 35 Checks before start up 36 Page REFRIGERANT CHARGE 36 Gas tightness testing and...

Страница 3: ...C Entering air temp o C Leaving air temp o C Leaving air temp o C Pressure drop air kPa Pressure drop air kPa Discharge air pressure Pa Discharge air pressure Pa Fan motor input Ph 1 Volts Fan motor i...

Страница 4: ...s not include the connection lines Based on an outdoor air dry bulb temperature of 35 C and a dewpoint suction temperature of 7 C Table 2 Physical data 50YZ 024 036 042 048 060 072 084 Nominal cooling...

Страница 5: ...size 024 230 V which is single phase The fan power supply is single phase except for sizes 072 and 084 which are three phase Based on an outdoor air dry bulb temperature of 35 C and a dewpoint suction...

Страница 6: ...e Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry M...

Страница 7: ...e Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry M...

Страница 8: ...e Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry M...

Страница 9: ...8 Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry M...

Страница 10: ...ce Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry...

Страница 11: ...ce Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry...

Страница 12: ...ce Evaporator access panel Compressor access panel Control box access panel Evaporator air inlet Evaporator air outlet Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry...

Страница 13: ...e Condenser air outlet Drain 3 4 MPT Unit supports Cable entry Main disconnect switch Compressor access panel Control box access panel Suction line 5 8 Liquid line 3 8 Condenser air inlet Note Standar...

Страница 14: ...e Compressor access panel Control box access panel Suction line 5 8 Liquid line 3 8 Condenser air inlet Condenser air outlet Drain 3 4 MPT Unit supports Cable entry Main disconnect switch Note Standar...

Страница 15: ...uction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Fig 10 Dimensions mm 38FZ BZ 042 Note Standar...

Страница 16: ...Condenser air outlet Drain 3 4 MPT Unit supports Cable entry Main disconnect switch When designing an installation always use up to date drawings available from your local Carrier office Note Standar...

Страница 17: ...Condenser air outlet Drain 3 4 MPT Unit supports Cable entry Main disconnect switch When designing an installation always use up to date drawings available from your local Carrier office Note Standar...

Страница 18: ...Condenser air outlet Drain 3 4 MPT Unit supports Cable entry Main disconnect switch When designing an installation always use up to date drawings available from your local Carrier office Note Standar...

Страница 19: ...Condenser air outlet Drain 3 4 MPT Unit supports Cable entry Main disconnect switch When designing an installation always use up to date drawings available from your local Carrier office Note Standar...

Страница 20: ...ondenser air outlet Drain 3 4 MPT Unit supports Cable entry When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return V...

Страница 21: ...panel Suction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return P...

Страница 22: ...panel Suction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return P...

Страница 23: ...panel Suction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return V...

Страница 24: ...panel Suction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return V...

Страница 25: ...panel Suction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return V...

Страница 26: ...ss panel Suction line 5 8 Liquid line 3 8 Condenser air inlet When designing an installation always use up to date drawings available from your local Carrier office Note Standard air supply and return...

Страница 27: ...es A 800 mm B 500 mm C 600 mm D 500 mm NOTE For size 50TZ YZ 060 D 600 mm Fig 23 Service area mm 38FZ BZ all sizes A 800 mm B 500 mm C 500 mm Fig 24 Service area mm 40TZ BZ all sizes A 600 mm B 500 mm...

Страница 28: ...0 600 610 Measured from point 38FZ BZ all sizes Fig 27 Centre of gravity approx 40TZ BZ all sizes 40TZ BZ 024 036 042 048 060 072 084 XG mm 290 300 308 310 310 430 460 YG mm 223 238 240 232 235 275 27...

Страница 29: ...36 Support 38FZ points 024 036 042 048 060 072 084 18 22 27 32 36 43 54 15 18 20 23 27 37 48 43 50 52 65 69 77 91 34 40 41 45 48 55 68 Control box Air Filter Fig 28 Weight distribution kg approx 50TZ...

Страница 30: ...Remove supply air panel and access panel h Exchange the position of panels and See Figs 31 and 32 S Standard NOTE In the 50TZ YZ 060 and 40BZ 060 units the standard indoor air discharge is through th...

Страница 31: ...t tica disponible Pa 1 2 2 1 50TZ YZ 036 outdoor fan 38BZ FZ 036 Available static pressure Pa Air flow l s Power input W 50TZ YZ042 ventilador exterior 38BZ FZ042 0 20 40 60 80 100 120 700 750 800 850...

Страница 32: ...20 40 60 80 100 120 140 160 180 1300 1400 1500 1600 1700 1800 Caudal de aire l s 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 Consumo W Presi n est tica disponible Pa 50TZ YZ084 ventilador interi...

Страница 33: ...rees with the specification on the unit nameplate Siting the unit Check the following points The location must be able to support the unit operating weight see Tables 1 and 2 Allow sufficient space fo...

Страница 34: ...ctured in accordance with the wiring diagram accompanying the unit Follow the instructions supplied with the control for thermostat assembly and handling The general rules below should be taken into a...

Страница 35: ...nt lines the following must be kept in mind Depending on the unit arrangement Fig 35 Refrigerant lines option A Suction line A siphon at the base of the vertical pipe run and inter mediate siphons eve...

Страница 36: ...electrical power source agrees with the unit nameplate rating Make sure that compressors float freely on the mounting springs WARNING The compressors are mounted on vibration isolators Do not loosen o...

Страница 37: ...Tables 3 and 4 Refrigerant system description The refrigerant circuit incorporates the following primary elements Refrigerant air heat exchanger made of high quality copper tubes and pretreated alumin...

Страница 38: ...n maximum performance from the unit special attention should be paid to the following points Electrical connections The supply voltage should be within the limits permitted by the compressor Ensure th...

Страница 39: ...door unit Similarly locate the welded joint of the liquid line sections Separate both lines suction and liquid lines by unsoldering them After completing this operation plug the ends of both lines to...

Страница 40: ...ssor Replace compressor Unit starts and stops frequently Defective compressor contactor Replace contactor Defective compressor Replace compressor Refrigerant losses Check and add the necessary quantit...

Отзывы: