9

Electrical Work

1.  The supply voltage must be the same as the rated voltage of the air 

conditioner.

2.  Prepare the power source for exclusive use with the air conditioner.

     

Stripping length of the connecting cable

Model

42EQV050M

42EQV060M

Power source

220 – 240 V Single phase, 50Hz
220 – 230 V Single phase, 60Hz

Maximum running current

10.0A

13.5A

Plug socket & fuse rating

13A

16A

Power cord

4 mm

2

 H07RN-F or 60245 IEC66 or 3.5 mm

2

 (AVG-12)

•  Wrong wiring connection may cause some electrical parts burn out.
•  Be sure to comply with local rule on running the wire from indoor unit 

to outdoor unit (size of wire and wiring method, etc.).

•  Every wire must be connected 

fi

 rmly.

•  If incorrect or incomplete wiring is carried out, it will cause an ignition 

or smoke.

•  Prepare the power supply for exclusive use with the air conditioner.
•  This product can be connected to the mains.
 Connection 

to 

fi

 xed wiring: A switch which disconnects all poles and 

has a contact separation of at least 3 mm must be incorporated in the 

fi

 xed wiring.

CAUTION

 

NOTE       

: Connecting cable

•  Wire type :  More than 1.5 mm² (H07RN-F or 60245 IEC66) or 1.3 mm² 

(AWG-16)

 

NOTE

•  Wire type :  4 mm

2

 H07RN-F or 60245 IEC66 or 3.5 mm

2

 (AVG-12)

L N

1 2 3

30

30

40

40

10

10

10

10

Connecting cable

Power cord

Terminal block

Earth line

Earth line

Connecting cable

Power cord

OTHERS

OTHERS

Gas Leak Test

Test Operation

To switch to the TEST RUN (COOL) 
mode, press [RESET] button for 
10 seconds. (The beeper will make 
a short beep.)

Auto Restart Setting

The product was shipped with Auto Restart function in the off position. 
Turn it on as required.

     

How to set the Auto Restart

Remote Control A-B Selection

To separate using of remote control for each indoor unit in case of 2 air 
conditioners are installed near.

Remote Control B Setup.

1.  Press [RESET] button on the indoor unit to turn the air conditioner ON.
2.  Point the remote control at the indoor unit.
3.  Push and hold [CHECK] button on the Remote Control by the tip of the 

pencil. “00” will be shown on the display (Picture 

1

).

4.  Press [MODE] during pushing [CHECK]. “B” will show on the display 

and “00” will disappear and the air conditioner will turn OFF. The Remote 
Control B is memorized (Picture 

2

).

Note :  1.  Repeat above step to reset Remote Control to be A.
 

 

2.  Remote Control A has not “A” display.

 

 

3.  Default setting of Remote Control from factory is A.

•  When two indoor units are installed in the same room or adjacent two 

rooms, if operating a unit, two units may receive the remote control signal 
simultaneously and operate. In this case, the operation can be preserved 
by setting either one remote control to B setting. (Both are set to A setting 
in factory shipment.)

•  The remote control signal is not received when the settings of indoor unit 

and remote control are different.

•  There is no relation between A setting/B setting and A room/B room when 

connecting the piping and cables.

• Check the 

fl

 are nut connections 

for the gas leak with a gas leak 
detector or soap water.

This product is designed so that, after a power failure, it can restart 
automatically in the same operating mode as before the power failure.

1.  Press and hold the [RESET] button on the indoor unit for 3 seconds to 

set the operation. (3 beep sound and OPERATION lamp blink 5 time/sec 
for 5 seconds)

2.  Press and hold the [RESET] button on the indoor unit for 3 seconds to 

cancel the operation. (3 beep sound but OPERATION lamp does not 
blink)

 

•  In case of ON timer or OFF timer are set, AUTO RESTART 

OPERATION does not activate.

Check places for
the indoor unit.

Check places for
the outdoor unit.

Information

1

2

RESET

RESET button

01_1115551229-EN.indd   9

01_1115551229-EN.indd   9

1/16/2558 BE   6:35 PM

1/16/2558 BE   6:35 PM

Содержание 38EYV050M

Страница 1: ...r unit 42EQV050M 060M Outdoor unit 38EYV050M 060M 1115551229 AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH 01_1115551229 EN indd 1 01_1115551229 EN indd 1 1 16 2558 BE 6 35 PM 1 16 2558 BE 6...

Страница 2: ...rainage 7 OUTDOOR UNIT 7 Installation Place 7 Precautions about Installation in Regions with Snowfall and Cold Temperatures 7 Refrigerant Piping Connection 8 Evacuating 8 Wiring Connection 8 Electrica...

Страница 3: ...STALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE...

Страница 4: ...be sure to stop the compressor unit before removing the refrigerant pipe If removing the refrigerant pipe while the compressor is operating with the service valve opened it may cause air suction and o...

Страница 5: ...mote control holder Shield pipe Attach to the front panel Air filter Installation plate 50 mm or more 170 mm or more 170 mm or more 6 5 Filter Filter Hook Hook Remark Detail of accessory and installat...

Страница 6: ...shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION CAUTION Failure to firmly install the unit may...

Страница 7: ...hem out The combination of using wire controller and batteries may cause of batteries explosion 3 Make hole for insert control wire by use screwdriver break the polyester sheet as shown on figure 7 4...

Страница 8: ...pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend t...

Страница 9: ...o obstructions near its air intake or air outlet 2 When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a high story of a building secure the no...

Страница 10: ...lves Packed valve at liquid side Service port Valve core Setting pin Packed valve at gas side Vacuum pump Vacuum pump adapter for counter flow prevention For R410A only Charge hose For R410A only Hand...

Страница 11: ...in case of 2 air conditioners are installed near Remote Control B Setup 1 Press RESET button on the indoor unit to turn the air conditioner ON 2 Point the remote control at the indoor unit 3 Push and...

Страница 12: ...O O O O O O X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X O 2 O O O X O O O O O O O O O O Z O O R410A O O O O O O O O X O O Z O O O O O O O X O O O O O O O O O O X...

Страница 13: ...2 GR O O X O O O o o o o o o o o o O O O R410A HFC R410A 1 6 R22 0 o o o o o o o o o o o o o o o o 02_1115551229 GR indd 2 02_1115551229 GR indd 2 1 16 2558 BE 6 36 PM 1 16 2558 BE 6 36 PM...

Страница 14: ...170 mm 170 mm 100 mm 100 mm 600 mm 600 mm O 6 5 A B C D A B C D 8 mm X 8 mm 10 mm 9 108 mm 28 mm 125 mm 2 5 m m 86 mm 102 mm 320 mm 600 mm 90 mm 600 mm 8 o o o o o o o o o o o o o 02_1115551229 GR ind...

Страница 15: ...r of pipe hole 35 120 180 240 O 23 mm 65 mm o u it ut ne 40mm To unit ut ine 3 mm To un t o t l ne 40mm O e 23mm om he gh s de edge s he c n e o p pe ho e o n i t u o i e 120mm 0 2 5 1 0 1 2 0 O se 8...

Страница 16: ...o o 2 3 1 2 3 7 4 8 5 9 0 25 N m 0 03 kgf m 6 7 3 1 16L 8 3 1 25L 9 3 1 25L 0 15 N m 0 02 kgf m 10 28 22 AWG 0 08 0 32 mm2 4 7 30 m 70 mm 5 mm 4 6 5 o o 0 12 N m 0 01 kgf m 7 8 9 28 22 AWG 0 08 0 32 m...

Страница 17: ...o o o o o o o o o 43 mm o o o o o o 43 mm o o o o o o o o X o o o o o 7 30 mm o o O o o o o o o o o o o o o o o o R 30 mm X o o polisin o o o o o X o o o 3 1 16L o 3 1 25L 1 2 o 1 1 3 o PRESET TIMER...

Страница 18: ...o o o o o o o I o o o o o o o o o o o o o o o o o o o o o o o o 20 m 15 20 16 20 o o 10 m o o o o o o o o 1 o o o o o I o o o o o o o 50 mm o o o o o o o o o o o 2 3 o o o E o o o o o o o o o o o o o...

Страница 19: ...o 1 o 2 o o o o o o o o 7 A o mm RIDGID o 90 A O o o o o o o o o X o o o o o o o o o o R410A vo R410A vo o o R410A vo 101 kPa 76 cmHg O 5 O 1 o 2 o 3 o o o O 4 o o 5 o o o o o 7 o o o o o o o o o o o...

Страница 20: ...o o o o o o o o o o o o o o o o o o TEST RUN COOL o o RESET 10 O o o o Auto Restart o Auto Restart o o o o o o o o o o o o 1 RESET 3 3 OPERATION 5 5 2 RESET 3 3 OPERATION o o o ON OFF O O o o o o o o...

Страница 21: ...MEMO 02_1115551229 GR indd 10 02_1115551229 GR indd 10 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Страница 22: ...MEMO 02_1115551229 GR indd 11 02_1115551229 GR indd 11 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Страница 23: ...02_1115551229 GR indd 12 02_1115551229 GR indd 12 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Страница 24: ...1115551229 02_1115551229 GR indd 13 02_1115551229 GR indd 13 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Отзывы: