Carrier 38BYW Скачать руководство пользователя страница 2

Step 3—Clearance Requirements

When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Common clearances are 6
in. on 1 side, 12 in. on 2 sides, and 30 in. on service side of unit.
Allow 24 in. between units. Discharge air must be unobstructed
and must not recirculate.

Position so snow, ice, or water from roof or eaves cannot fall
directly on unit.

On rooftop applications, locate unit at least 6 in. above roof
surface. Place unit above a load-bearing wall and isolate unit and
tubing set from structure.

Arrange supporting members to adequately support unit and
minimize transmission of vibration to building. Consult local
codes governing rooftop applications.

Step 4—Operating Ambients

The minimum outdoor operating ambient in cooling mode is 55°F,
and the maximum outdoor operating ambient in cooling mode is
125°F. The maximum outdoor operating ambient in heating mode
is 66°F.

Step 5—Elevate Unit

Accumulation of water and ice in base pan may cause
equipment damage.

In areas where prolonged freezing temperatures are encountered,
elevate unit per local climate and code requirements to provide
clearance above estimated snowfall level and ensure adequate
drainage of unit.

Step 6—Check Defrost Thermostat

Check defrost thermostat to ensure it is properly located and
securely attached. There is a liquid header with a brass distributor
and feeder tube going into outdoor coil. At the end of 1 of the

feeder tubes, there is a 3/8-in. OD stub tube approximately 3 in.
long. (See Fig. 4.) The defrost thermostat should be located on stub
tube. Note that there is only 1 stub tube used with liquid header,
and on most units it is the bottom circuit.Metering Device

Step 7—Metering Device

NOTE:

A thermostatic expansion valve (TXV) is required on all

38BYW units. Step 8 refers to installation of the TXV.

Fig. 2—Connecting Tubing Installation

A94028

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

 MIN.

SUSPENSION

Fig. 3—Mount Unit to Pad

A94199

UNIT SIZE

MIN. PAD

DIM. (IN.)

TIEDOWN KNOCKOUT

LOCATIONS

A

(In.)

B

(In.)

C

(In.)

38BYW024-060

30 X 30

6-1/2

23-1/2

20

C

B

A

3

8

D. (9.53) TIEDOWN 

KNOCKOUTS (2) PLACES

Fig. 4—Defrost Thermostat Location

A97517

FEEDER TUBE

DEFROST
THERMOSTAT

STUB TUBE

2

Содержание 38BYW

Страница 1: ...installation of equipment 1 Locate unit away from windows 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding...

Страница 2: ...per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit Step 6 Check Defrost Thermostat Check defrost thermostat to ensure it...

Страница 3: ...alve To prevent damage to unit or service valves observe the following Use a brazing shield Wrap service valves with wet cloth or use a heat sink material Connect outdoor unit to indoor sections using...

Страница 4: ...th CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 9 CONNECT CONTROL WIRING Route 24 v control wires...

Страница 5: ...ling On a call for cooling thermostat makes circuits R O R Y and R G Circuit R O energizes reversing valve switching it to cooling position Circuit R Y energizes contactor starting outdoor fan motor a...

Страница 6: ...deline For buried line applications refer to Residential Split System Buried Line Application Guideline Required for Low Ambient Controller full modulation feature and MotorMaster Control only Fig 10...

Страница 7: ...NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION JW1 A97540 24 VAC HOT R G W W1 Y Y2 Y Y2 Y1 W2 R DH RVS COOLING C B L S1 S2 Y W2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S FK4C...

Страница 8: ...4 VAC COM HEAT STAGE 2 CUT JW1 SHR SHR FA FB FC FH FAN COIL SMART HEAT ODT A97410 24 VAC HOT R C Y G O RVS COOLING W2 OTHER HP THERMOSTAT FA FB FC FH FAN COIL SMART HEAT HEAT PUMP E R C Y G O W2T W3 W...

Страница 9: ...NALS MUST BE PRESENT 8 Y1 AND O CONNECTIONS TO 2 STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL Fig 13 Typical 24 v Circuit Connections using Carrier Model DF Thermost...

Страница 10: ...10...

Страница 11: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products...

Страница 12: ...46231 38byw1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 563...

Отзывы: