Carrier 38AQS012 Скачать руководство пользователя страница 17

17

supply disconnect and check the crankcase oil level. Add oil
only if necessary to bring the oil into view in the sight glass. If
oil is added, run the system for an additional 10 minutes, then
stop and check oil level. If the level remains low, check the
piping system for proper design for oil return; also check the
system for leaks. 

If the initial check shows too much oil (too high in the sight

glass) remove oil to proper level. See Preliminary Oil Charge,
page 16, for proper procedure for adding and removing oil. 

When the above checks are complete, repeat the procedure

with the unit operating at minimum load conditions. Unload
the compressor by disconnecting the field-control circuit lead
at TB2 

 .

Reconnect the field-control circuit lead when checks are

complete.

Final Checks  — 

Ensure all safety controls are operating,

control panel covers are on, and the service panels are in place.

Sequence of Operation

HEATING — Place thermostat selector at HEAT and set tem-
perature selector above room ambient.
COOLING — Place thermostat selector at COOL and set tem-
perature selector below room ambient.

When thermostat calls for unit operation (either heating or

cooling), the indoor-fan motor starts immediately. The
outdoor-fan motors and compressor start within 3 seconds to
5 minutes depending on when unit was last shut off by thermo-
stat, because unit contains a compressor time delay circuit.
When first-stage cooling is required, thermostat (TC1) closes,
causing the heat pump to start with an unloaded compressor.
When TC2 closes, demanding additional cooling, the compres-
sor loads to full load operation.

During heating, compressor is always fully loaded. When

TH1 demands first-stage heating, the heat pump starts within
3 seconds to 5 minutes depending on when unit was last shut
off by thermostat, because unit contains a compressor time
delay  circuit. (The defrost board has speed terminals to shorten
this cycle.) When TH2 of the thermostat closes, auxiliary heat
supply (electric strip heat) is energized in 1 or 2 stages depend-
ing on number of stages available and whether outdoor thermo-
stats are closed.

Defrost is achieved by reversal from heating to cooling cy-

cle and deenergization of outdoor-fan motors, allowing hot re-
frigerant gas to defrost outdoor coil. Defrost is achieved with a
timer set to initiate defrost every 30, 50, or 90 minutes (factory
set at 30 minutes).

Defrost is initiated when refrigerant temperature leaving the

outdoor coil is measured below 27 F (2.8 C), (typically when
the outdoor ambient temperature is below 45 F [7.2] C as
sensed by the defrost thermostat [DFT]).

Defrost is terminated when: The refrigerant temperature

rises to 65 F (18.3 C) (80 F [26.7 C] for 38AQS016) at the DFT
location on the liquid line; or the refrigerant pressure rises to
280 psig (1931 kPag) at the HPS2 location on the liquid line; or
the defrost timer completes the 10-minute cycle.
DUPLEX 38AQS012 OR 016 OUTDOOR UNITS WITH
40RMQ024 OR 40RMQ028 — The sequence of operation is
similar to the description above with the following exceptions:
Cooling — The control system may be configured in two differ-
ent ways: for face split coil operation or for full face active system.
Face Split Coil Operation — When TC-1 closes, condensing
unit A will start fully loaded. When TC-2 closes, condensing
unit B will start fully loaded.
Full Face Active Operation — When TC-1 closes, condensing
unit A and condensing unit B will start with unloaded

compressors. When TC-2 closes, the compressors in both con-
densing units will load.
Heating — When TH-1 closes, both condensing unit A and
condensing unit B will start in the Heating mode. When TH-2
closes, the auxiliary heat (electric resistance) heat will be
energized. 
SAFETIES — The high-pressure switch, loss-of-charge
switch, oil pressure safety switch, and compressor overtemper-
ature safety are located in a Signal-LOC™ circuit that prevents
heat pump operation if these safety devices are activated. A
light at the thermostat energizes when Signal-LOC circuit is
affected. The lockout system can be reset by adjusting the ther-
mostat to open the contacts (down for Heating mode, up for
Cooling mode), deenergizing the Signal-LOC circuitry. Com-
pressor overcurrent protection is achieved with a circuit
breaker which requires manual resetting at the outdoor unit
control box.

The unit is equipped with an oil pressure safety switch that

protects the compressor if oil pressure does not develop on
start-up or is lost during operation. The oil pressure switch is of
the manual reset type and therefore must be reset at the outdoor
unit. DO NOT RESET MORE THAN ONCE.

If oil pressure switch trips, determine cause and correct. DO

NOT JUMPER OIL PRESSURE SAFETY SWITCH.
To reset the oil pressure switch:

1. Disconnect power to the unit.
2. Press the RESET button on the oil pressure switch.
3. Reconnect power to the unit.

Unit is equipped with a no-dump reversing valve circuit.

When unit is in Cooling mode, reversing valve remains in cool-
ing position until a call for heating is requested by thermostat.
When unit is in Heating mode, reversing valve remains in heat-
ing position until there is a call for cooling.

The crankcase heater is in a lockout circuit. If crankcase

heater is defective, compressor is locked off. Heat pump re-
mains off until corrective action is taken. The lockout circuit
cannot be reactivated by adjusting the thermostat. To reset the
crankcase heater lockout, disconnect and then reconnect power
to unit.
LIQUID LINE SOLENOID — To minimize refrigerant
migration to the compressor during the heat pump OFF cycle,
the unit features a bi-flow liquid line solenoid valve. The valve
opens when the compressor is energized, and closes when the
compressor is deenergized. This feature reduces compressor
flooded starts, significantly increasing compressor life.
ACCUMULATOR — The unit accumulator controls the rate
of liquid refrigerant to the compressor during heat pump opera-
tion. The accumulator features a unique method for returning
oil to the compressor. The oil return mechanism is external to
the accumulator. The mixture of oil and refrigerant is metered
to the compressor by a brass orifice which is removable and
cleanable. The oil return mechanism also contains a solenoid
valve that opens when the compressor is ON and closes when
the compressor is OFF. This keeps the liquid refrigerant stored
in the accumulator from draining to the compressor during the
heat pump OFF cycle, which further protects the compressor
against flooded starts.
OIL CHARGE (Tables 1A and 1B) — Allow unit to run for
about 20 minutes. Stop unit and check compressor oil level.
Add oil only if necessary to bring oil into view in sight glass.
Refer to Preliminary Oil Charge section on page 16. Use only
Carrier-approved compressor oil.
CHECK OPERATION — Ensure operation of all safety con-
trols. Replace all service panels. Be sure that control panel
cover is closed tightly.

Y2

Содержание 38AQS012

Страница 1: ...her handy Use care in handling rigging and setting bulky equipment INSTALLATION Step 1 Complete Pre Installation Checks UNCRATE UNIT Remove unit packaging except for the top skid assembly which should be left in place until after the unit is rigged into position INSPECT SHIPMENT File claim with shipping company if shipment is damaged or incomplete CONSIDER SYSTEM REQUIREMENTS Consult local buildin...

Страница 2: ...HPS Cutout psig Cut in psig Loss of Charge Switch Liquid Line Cutout psig Cut in psig Head Pressure No 2 Fan Cycling Opens psig Closes psig Oil Pressure Switch Differential Set Point psig Close on Rise Open on Fall Defrost Pressure Switch HPS2 Opens psig Closes psig 400 300 7 3 22 5 160 10 255 10 9 5 1 5 280 10 180 2 THERMOSTAT Defrost Switch Opens F Closes F 65 27 80 27 UNIT 38AQS 012 016 OPERATI...

Страница 3: ...ns NOTES 1 Service clearances are as follows Side compressor 31 2 ft 1067 mm Side opposite compressor 3 ft 914 mm Ends 2 ft 616 mm Top 5 ft 1524 mm 2 See Table 2 and Fig 3 for weight distribution and center of gravity ...

Страница 4: ...r Fan Relay 14 Control Relay CR3 24 Muffler 6 Outdoor Fan Contactor 15 Liquid Line Solenoid 25 Oil Solenoid 7 Compressor Contactor 16 Control Relay CR2 26 Reversing Valve 8 Fan Motor Capacitors 17 No Dump Relay NDR 27 Accumulator 9 Circuit Breaker 18 Oil Pressure Switch 28 Coil 10 Fan No 2 19 Fusible Plug hidden 2 1 4 3 38AQS012 016 38 1 4 972 mm 26 11 16 678 mm Fig 3 Weight Distribution Table 2 W...

Страница 5: ...s field supplied Weight distribution shown in Fig 3 and Table 2 deter mines the type of support required Bolt unit securely to pad or supports after unit is in position and is level Be sure to mount unit level to ensure proper oil return to compressors Mounting holes on unit can be used to secure unit to vibration isolators if required COMPRESSOR MOUNTING As shipped compressor is held down by 4 bo...

Страница 6: ...ator between the filter drier s and the liquid connections on the indoor 40RMQ unit Braze or silver alloy solder all connections Pass nitrogen or other inert gas through piping while making connections to prevent formation of copper oxide Copper oxides are extremely active under high temperature and pressure Failure to prevent collection of copper oxides may result in system component failures VAP...

Страница 7: ... details 2 All wiring must comply with applicable local and national codes 3 Wiring and piping shown are general points of connection guides only and are not intended for or to include all details for a specific installation 4 Filter driers must be bi flow type suited for heat pump duty 5 Internal factory supplied TXVs and check valves not shown Fig 5A Typical System Piping and Wiring 38AQS With 4...

Страница 8: ...xpansion Valve Piping NOTES 1 All piping must follow standard refrigerant piping techniques Refer to Carrier System Design Manual for details 2 All wiring must comply with applicable local and national codes 3 Wiring and piping shown are general points of connection guides only and are not intended for or to include all details for a specific installation 4 Filter driers must be bi flow type suite...

Страница 9: ...um outdoor ambient air temperature for full cooling capacity Table 6 Minimum Outdoor Air Operating Temperature Applies to Cooling mode of operation only UNIT 38AQS COMPRESSOR CAPACITY CONDENSER TEMP F C MINIMUM OUTDOOR TEMP F C Standard Unit 012 100 67 90 32 2 80 26 7 35 1 7 45 7 2 016 100 67 90 32 2 80 26 7 23 5 36 2 2 LIQUID LINE BI FLOW FILTER DRIER TXV REDUCING TEE INDOOR COIL B A A UNIT 38AQS...

Страница 10: ...onged peri od it is recommended that the suction and discharge valves be closed to prevent an excessive accumulation of refrigerant in the compressor oil 3 Terminals for field power supply are suitable for copper copper clad aluminum or aluminum conductors CONTROL CIRCUIT WIRING Unit internal control cir cuit voltage is 24 volts See Table 8 for recommended thermo stats Connect thermostat assembly ...

Страница 11: ... National Electric Code U S A Standard Article 440 2 Motor RLA and FLA values are established in accordance with UL Underwriters Laboratories Standard 1995 U S A Standard Table 8 Recommended Thermostats LEGEND Thermostat kit includes Temp System relay pack Subbase has ON AUTO fan switch IMPORTANT The common COM terminals from all three fan coil relay boards must be connected to the P terminal in c...

Страница 12: ...Ground NEC National Electrical Code U S A TB Terminal Block Field Wiring Factory Wiring Fig 9 Main Power Supply Wiring LEGEND EQUIP Equipment GND Ground HC Heater Contactor IFC Indoor Fan Contactor IFM Indoor Fan Motor NEC National Electrical Code U S A TB Terminal Block Fig 10A Field Wiring Diagram 38AQS012 or 016 System With Standard Thermostat and Electric Heat ...

Страница 13: ...UPPLY 3 Ph ONLY L1 L2 L3 EQUIP GND TB1 HC1 HC1 CIRCUIT BREAKER 5 HP AND LARGER UNIT WIRING IFM BLK BLK BLK 21 22 23 12 13 11 1 2 3 HTR1 IFC FAN COIL NO 1 RELAY BOARD 33ZCRLYBRD FAN COIL NO 2 RELAY BOARD 33ZCRLYBRD FAN COIL NO 3 RELAY BOARD 33ZCRLYBRD TSTAT LEGEND NOTE Use copper conductors only EQUIP Equipment GND Ground HC Heating Contactor HTR Electric Heater IFC Indoor Fan Contactor IFM Indoor ...

Страница 14: ...LY 3 Ph ONLY L1 L2 L3 EQUIP GND TB1 HC1 HC1 CIRCUIT BREAKER 5 HP AND LARGER UNIT WIRING IFM BLK BLK BLK 21 22 23 12 13 11 1 2 3 HTR1 IFC FAN COIL NO 1 RELAY BOARD 33ZCRLYBRD FAN COIL NO 2 RELAY BOARD 33ZCRLYBRD FAN COIL NO 3 RELAY BOARD 33ZCRLYBRD TSTAT LEGEND NOTE Use copper conductors only EQUIP Equipment GND Ground HC Heating Contactor HTR Electric Heater IFC Indoor Fan Contactor IFM Indoor Fan...

Страница 15: ...ING THERMOSTAT HH07AT172 Degrees F and HH07AT162 Degrees C The thermostat has an adjustable heat anticipator for both first and second stage heating circuits SETTINGS Set adjustment lever for first stage anticipator at 0 79 left hand side Set adjustment lever for second stage anticipator right hand side at 0 42 OUTDOOR THERMOSTAT Refer to 40RMQ accessory heater installation instructions for detail...

Страница 16: ...arge modifications should be done only under supervision of a qualified refrigeration mechanic With all fans operating and compressor operating fully loaded adjust the refrigerant charge in accordance with the unit charging charts located on the inside of the control box doors and in Fig 12 and 13 1 Be sure to use Refrigerant 22 2 Regulate refrigerant drum valve to maintain suction pres sure at 80...

Страница 17: ...TC 1 closes condensing unit A and condensing unit B will start with unloaded compressors When TC 2 closes the compressors in both con densing units will load Heating When TH 1 closes both condensing unit A and condensing unit B will start in the Heating mode When TH 2 closes the auxiliary heat electric resistance heat will be energized SAFETIES The high pressure switch loss of charge switch oil pr...

Страница 18: ...r Unit Fans Each fan is supported by a formed wire mount bolted to the fan deck and covered with a wire guard The exposed end of the motor shaft is covered with a rubber boot In case a fan motor must be repaired or replaced be sure the rubber boot is put back on when the fan is rein stalled and be sure the fan guard is in place before starting the unit Figure14 shows the proper position of the mou...

Страница 19: ...mmended coil cleaners is strongly discouraged since coil and unit durability could be affected The following field supplied equipment is required for coil cleaning 2 1 2 gallon garden sprayer water rinse with low velocity spray nozzle Totaline Environmentally Sound Coil Cleaner Application Instructions Perform the following procedure to clean the coil NOTE Wear proper eye protection such as safety...

Страница 20: ...20 TROUBLESHOOTING CHART HEATING CYCLE LEGEND NOTE See Fig 17 for diagram showing heating cycle operation CCH Crankcase Heater N C Normally Closed ...

Страница 21: ...21 TROUBLESHOOTING CHART COOLING CYCLE LEGEND NOTE See Fig 18 for diagram showing heating cycle operation CCH Crankcase Heater TXV Thermostatic Expansion Valve ...

Страница 22: ...drier a distribution manifold and then through capillary tubes on each circuit 3 Each circuit evaporates the refrigerant and all the circuits are combined in the outdoor header with some of the circuits flow ing through the check valve A 4 The refrigerant then flows through the reversing 4 way valve accumulator and back to the compressor LEGEND NOTES 1 Check valves are designated A through D 2 Ill...

Страница 23: ...valve A and is then redirected to a final subcooling pass in center of coil face 012 or exits header via outlet tube 016 5 Refrigerant leaves the outdoor coil by way of check valve B to the liquid line 6 The refrigerant then flows through the filter drier and feeds the indoor coil by way of the TXV and feeder valves 7 Each circuit evaporates the refrigerant and the circuits are com bined in the in...

Страница 24: ......

Страница 25: ......

Страница 26: ...nue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 80001 Printed in U S A Form 38AQS 9SI Pg 26 1 01 Replaces 38AQS 8SI Book 1 1 Tab 5a 5a Copyright 2001 Carrier Corporation ...

Страница 27: ...IRING TERMINALS including main power supply TIGHT Y N _____________ HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS Y N _____________ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ___________ ARE PROPER AIR FILTERS IN PLACE Y N ____________ HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N ___________ DO THE FAN BELTS HAVE PROPER TENSION Y N ________...

Страница 28: ...COMPRESSOR AMPS L1 L2 L3 ______ ______ ______ ______ ______ _______ CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES ARE THE SIGHT GLASSES SHOWING OIL LEVEL IN VIEW Y N NOTES ___________________________________________________________________________________________________ ___________________________________________________________________________________________________ _____________________________...

Отзывы: