Carrier 38AE012 Скачать руководство пользователя страница 7

INSTALL FILTER DRIER(S) AND MOISTURE INDICA-
TOR(S) — Every unit should have a filter drier and liquid-
moisture indicator (sight glass). In some applications, depending
on space and convenience requirements, it may be desirable
to install 2 filter driers and sight glasses. One filter drier and
sight glass may be installed at A locations in Fig. 4. Or, 2
filter driers and sight glasses may be installed at B locations.

Select the filter drier for maximum unit capacity and mini-

mum pressure drop. Complete the refrigerant piping from
indoor unit to outdoor unit before opening the liquid and suc-
tion lines at the outdoor unit.

INSTALL LIQUID LINE SOLENOID VALVE — SOLE-
NOID DROP — It is recommended that a solenoid valve be
placed in the main liquid line (see Fig. 4) between condens-
ing unit (38AE/AKS) and fan coil (40RR, 40RE). (A liquid
line solenoid valve is required when the liquid line length
exceeds 100 ft [30.5 m] or when the condensing unit is con-
nected to the chiller barrel in a built-up chiller system.) This
valve prevents refrigerant migration (which causes oil dilu-
tion) to the compressor during the off cycle at low outdoor
ambient temperatures. The solenoid should be wired in par-
allel with the compressor contactor coil. This means of elec-
trical control is referred to as solenoid drop control.

INSTALL LIQUID LINE SOLENOID VALVE (OPTIONAL)
— CAPACITY CONTROL — If 2-step cooling is desired,
place a solenoid valve in the location shown in Fig. 4.

MAKE PIPING CONNECTIONS — Do not remove run-
around loop from suction and liquid line stubs in the com-
pressor compartment until piping connections are ready to
be made. Pass nitrogen or other inert gas through piping while
brazing to prevent formation of copper oxide.

Install field-supplied thermostatic expansion valve(s) in in-

door section. If 2 thermostatic expansion valves are installed
for 2-step cooling, install field-supplied liquid line solenoid
valve ahead of the second expansion valve.

PROVIDE SAFETY RELIEF — A fusible plug is located
on the compressor crankcase or in the liquid line (Fig. 5).
Do not cap this plug. If local code requires additional safety
devices, install them as directed.

Step 4 — Install Accessories —

Field install ac-

cessories such as winter start control or low-ambient control
before proceeding with wiring. Refer to the instructions shipped
with the accessory.

Step 5 — Complete Electrical Connections

POWER WIRING — Unit is factory wired for voltage shown
on nameplate. Provide adequate fused disconnect switch within
sight from unit and readily accessible from unit, but out of
the reach of children. Lock switch open (off) to prevent power
from being turned on while unit is being serviced. Discon-
nect switch, fuses, and field wiring must comply with na-
tional and local code requirements. See Tables 5A and 5B.

Route power wires through opening in unit end panel to

connection in unit control box as shown on unit label dia-
gram and in Fig. 6. Unit must be grounded.

Affix crankcase heater warning sticker to unit disconnect

switch.

CONTROL CIRCUIT WIRING — Control voltage is 24 v.
See Fig. 7 and unit label diagram for field-supplied wiring
details. Route control wires through opening in unit end panel
to connection in unit control box.

TXV — Thermal Expansion Valve

Fig. 4 — Location of Sight Glass(es)

and Filter Drier(s)

NOTE: 38AKS024 has a fusible plug in the liquid line.

Fig. 5 — Location of Fusible Plug (38AE)

LEGEND

EQUIP GND — Equipment Ground
NEC

— National Electrical Code

Factory Wiring

Field Wiring

Fig. 6 — Main Power Supply Wiring

7

Содержание 38AE012

Страница 1: ...ety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment ELECTRIC SHOCK HAZARD Separate power sources main an...

Страница 2: ...8AE012 13 8 in 35 38AE014 016 15 8 in 41 38AKS024 C 7 8 in 22 2 diameter knockout for control power D 2 in 50 8 diameter knockout for unit power NOTES 1 SERVICE AREAS Allow 3 ft 914 on both sides and...

Страница 3: ...Compressor 2 No 1 Fan 6 Terminal Block 1 Unit Power 10 Low Pressure Switch 3 High Pressure Switch 7 Terminal Block 2 Control Power 11 Hot Gas Bypass Piping Stub 3 8 in ODM 4 Circuit Breakers 8 Wraparo...

Страница 4: ...temperatures of 125 F for 38AE012 123 F for 38AE014 and 130 F for 38AE016 and 38AKS024 Table 1B Physical Data SI 60 Hz UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT kg 333 354 359 408 REFRIG...

Страница 5: ...emperatures of 125 F for 38AE012 123 F for 38AE014 and 130 F for 38AE016 and 38AKS024 Table 1D Physical Data SI 50 Hz UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT kg 333 354 359 408 REFRIGER...

Страница 6: ...and also refer to Part 3 of Carrier System Design Manual for design details and line sizing Refer to indoor installation instructions for addi tional information Table 3 Liquid Line Data UNIT MAXIMUM...

Страница 7: ...ugh piping while brazing to prevent formation of copper oxide Install field supplied thermostatic expansion valve s in in door section If 2 thermostatic expansion valves are installed for 2 step cooli...

Страница 8: ...80 50 20 0 74 38AE014 803 230 198 264 51 0 149 75 35 7 143 2 2 9 3 5 1 20 903 400 342 457 34 0 89 50 22 1 83 38AE016 803 230 198 264 66 9 206 100 47 9 200 2 2 9 3 5 1 20 903 400 342 457 43 0 121 60 2...

Страница 9: ...ctrical power source must agree with unit nameplate rating 5 All service valves must be open 6 Crankcase heater must be firmly locked into the com pressor crankcase START UP To Start Unit Set thermost...

Страница 10: ...Fig 9 38AE012 and 38AKS024 Charging Chart 10...

Страница 11: ...Fig 10 38AE014 Charging Chart 11...

Страница 12: ...Fig 11 38AE016 Charging Chart 12...

Страница 13: ...ers and provides capacity control Un loaders are factory set see Tables 1A 1D but can be field adjusted as described in the 2 following sections CONTROL SET POINT cylinder load point is adjustable fro...

Страница 14: ...r as required by location or outdoor air conditions Inspect coil monthly and clean as required Fins are not continuous through coil sections dirt and debris may pass through first section become trapp...

Страница 15: ...rvice literature Contactor Closed 1 Compressor leads loose 1 Check connections 2 Motor windings open 2 See compressor service literature 3 Single phasing 3 Check for blown fuse Check for loose connect...

Страница 16: ...control 3 Air in system 3 Purge and evacuate system 4 Partially plugged expansion valve or filter drier 4 Clean or replace SYSTEM IS NOISY 1 Piping vibration 1 Support piping as required 2 Compressor...

Страница 17: ......

Страница 18: ...l programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 9...

Страница 19: ...ONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N HAS CORRECT FAN ROTATION BEEN C...

Страница 20: ...R DB dry bulb TEMP EVAP ENTERING AIR WB wet bulb TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS L1 L2 L3 CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES ARE THE SIGHT GLASSES SHOW...

Отзывы: