background image

2

FAN BUTTON — The fan button determines fan operation.
The fan can be set to Auto, Off, Low, Medium, or High.
MODE BUTTON — The  Mode  button  selects the operating
mode of the thermostat. The mode can be set to Heat, Cool,
Auto, or Off.
NOTE: Certain modes may be locked out by the type of appli-
cation or the reading of the changeover sensor.

Set Clock — 

The  Set Clock function allows the user to

change the time and day displayed on the thermostat. Press and
hold the Mode and Fan buttons at the same time for 2 seconds
until the display changes. The display will show the Setup an-
nunciator. The current time will blink on and off. Press the UP
ARROW and DOWN ARROW buttons until the correct time
is shown. Hold down the buttons to quickly move through the
time display. The AM and PM annunciators will automatically
change. To scroll through by hours instead of minutes, hold
down the Fan button while pressing UP ARROW or DOWN
ARROW. To ensure the schedules are properly followed, make
sure that AM or PM is correct for the time chosen. When the
correct time is shown, press the Mode button to modify the day
of the week. The current day will blink on and off. Press the UP
ARROW and DOWN ARROW buttons until the correct day is
shown. Press the and hold the Mode and Fan buttons at the
same time again to exit the Set Clock mode.

Program Thermostat Schedules  — 

 Before pro-

gramming the thermostat, plan the thermostat daily schedule.
The schedule is divided into 7 days (Monday through Sunday).
Each day has from 2 to 4 time periods (Occupied 1, Occupied
2, Occupied 3, Unoccupied) depending on the configuration of
the thermostat. Each occupied time period has a start time, stop
time, heating set point, and cooling set point. The unoccupied
time period has a heating set point and a cooling set point. The
unoccupied time period is active whenever an occupied time
period is not active. Fill in Table 1 as an aid to programming
the daily schedules.

PROGRAMMING MODE — To  program  the  daily  sched-
ules, perform the following procedure:

1. Enter Programming mode by pressing and holding the

Mode and UP ARROW buttons. The Occupied 1 annun-
ciator will appear on the thermostat display. Use the UP
ARROW and DOWN ARROW buttons to set the
maximum number of Occupied periods for each day. The
thermostat can be set to 1, 2, or 3. After the number of
Occupied periods has been selected, press the Mode
button. See Fig. 3.

2. The cooling set point for Occupied 1 will be displayed.

Use the UP ARROW and DOWN ARROW buttons to
raise or lower the cooling set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C). Press the Mode button to continue. See
Fig. 3.

3. The heating set point for Occupied 1 will be displayed.

Use the UP ARROW and DOWN ARROW buttons to
raise or lower the heating set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C). Press the Mode button to continue. See
Fig. 3.

4. The cooling set point for Unoccupied will be displayed.

Use the UP ARROW and DOWN ARROW buttons to
raise or lower the cooling set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C) or ‘‘OF’’ (no unoccupied cooling). To
configure the Unoccupied Cooling set point to OF, press
the DOWN ARROW button until 35 F (2 C) is displayed.

Press the DOWN ARROW button again to display OF.
Press the Mode button to continue.

5. The heating set point for Unoccupied will be displayed.

Use the UP ARROW and DOWN ARROW buttons to
raise or lower the heating set point until the desired tem-
perature is shown. The range of acceptable values is 35 to
99 F (2 to 36 C). Press the Mode button to continue.

6. The day of the week will be shown. Use the UP ARROW

and DOWN ARROW buttons to change the day of the
week until the desired starting day is shown. Possible
choices are Mo (Monday) through Su (Sunday). Press the
Mode button when the desired day is shown.

7. The Start Time for Occupied 1 will be displayed. Use the

UP ARROW and DOWN ARROW buttons to raise or
lower the time until the desired Start Time is shown.
Press the Mode button to continue. See Fig. 4.

8. The Stop Time for Occupied 1 will be displayed. Use the

UP ARROW and DOWN ARROW buttons to raise or
lower the time until the desired Stop Time is shown. Press
the Mode button to continue.

9. The On/Off icon will be displayed. Use the UP ARROW

to turn the Occupied 1 period ON for this day. Use the
DOWN ARROW to turn the Occupied 1 period OFF for
this day.

10. Repeat Steps 2 through 9 to program the remaining

schedule for Occupied periods 2 and 3.

11. The Copy command can be used to copy the previous

day’s schedule if the schedules are the same. The copy
command becomes available after all the occupied peri-
ods are programmed in a day. Use the UP ARROW to
change the copy command to YES. Use the DOWN
ARROW to change the copy command to NO. Press the
Mode button when the choice has been made. See Fig. 5.
If NO was selected, the schedule will automatically
change to the next day and the user must enter the occu-
pied and unoccupied schedules for that day.
NOTE: Occupied 1 schedule heating and cooling set
points are the same for each day. Occupied 2 and 3 set
points may be set to different values for each day of the
week.
If YES was selected, the schedule will be copied to the
next day. The schedule copy may be repeated until Sun-
day is reached. The Sunday schedule cannot be copied to
Monday.

12. After all the times and set points for each day have been

entered, press and hold the Mode and UP ARROW
buttons to exit Programming mode.

NOTE: The thermostat will continue to follow the schedule
until a new one is entered.

If only one occupied schedule is selected, the Occupied 2

and 3 schedules are skipped. If the start time is set later in the
day than the stop time, the program will run from midnight of
that day to the stop time and then from the start time to mid-
night. If the same start and stop times are programmed for an
occupancy schedule, the thermostat will be in Occupied mode
for 24 hours. If one occupied period starts or stops within an-
other occupied period, the lower numbered schedule has priori-
ty. For example, if schedule Occupied 3 is running for 24 hours
and Occupied 2 schedule comes on from 1 to 3 PM, the set
points from Occupied 2 are in effect from 1 to 3 PM.
OVERRIDING THE SCHEDULE —  The schedule can be
overridden by pressing the UP or DOWN ARROW buttons to
change the desired temperature. The thermostat will use the
new set point until the next scheduled time period starts.

Содержание 33CSSP2-FC

Страница 1: ...thermostat stores programs for 7 independent days Batteries are not required During power interruption the internal NEVERLOST mem ory stores configuration settings for an unlimited time while the clock continues to run for at least 48 hours The thermostat can be configured to accept several different equipment configurations including 2 or 4 pipe operation The temperature display range of the ther...

Страница 2: ... F 2 to 36 C or OF no unoccupied cooling To configure the Unoccupied Cooling set point to OF press the DOWN ARROW button until 35 F 2 C is displayed Press the DOWN ARROW button again to display OF Press the Mode button to continue 5 The heating set point for Unoccupied will be displayed Use the UP ARROW and DOWN ARROW buttons to raise or lower the heating set point until the desired tem perature i...

Страница 3: ...L ONLY When the thermostat is configured for Cool Only operation only Cool Program On and Off modes can be selected HEAT COOL WITH CHANGEOVER SENSOR When the thermostat is configured for operation with a changeover sensor all the modes are available for operation If the water temperature is changed during the year the thermostat will au tomatically lock out the incorrect mode Heat or Cool modes ma...

Страница 4: ...by the installer The minimum temperature difference is enforced during Auto mode and Program On operation Single Set Point Operation When the thermostat is configured for single set point operation the display on the thermostat will change Instead of displaying current room temperature the large number shown will be the user set point This set point is used for both heating and cooling Press and h...

Страница 5: ...5 ...

Страница 6: ...6 ...

Страница 7: ......

Страница 8: ...nue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 533 30004 Printed in U S A Form 33CS 18SO Pg 8 6 03 Replaces 33CS 15SO Book 1 4 Tab 11a 13a Copyright 2003 Carrier Corporation ...

Отзывы: