25
9.2 - Electrical data, units with option 150
Standard-efficiency units (option 150)
30XW--/30XWH
254 304 354 402 452 552 602 652 702 802 852 1002 1052 1154 1252 1352 1452 1552 1652 1702
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Nominal start-up current*
Circuit A
A
303 388 388 587 587 587 587 772 772 772 772 587 587 587 772 772 772 772 772 772
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
587 587 587 587 772 772 772 772 772
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
757 757 757 943 965 986 1004 1004 1004
Maximum start-up current**
Circuit A
A
303 388 388 587 587 587 587 772 772 772 772 587 587 587 772 772 772 772 772 772
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
587 587 587 587 772 772 772 772 772
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
887 887 887 1072 1172 1202 1232 1004 1232
Cosine phi nominal***
0.79 0.78 0.79 0.83 0.85 0.85 0.85 0.84 0.86 0.87 0.87 0.85 0.85 0.85 0.86 0.85 0.86 0.87 0.86 0.87
Cosine phi maximum****
0.88 0.87 0.88 0.90 0.90 0.91 0.91 0.90 0.90 0.90 0.90 0.90 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
Total harmonic distortion****
%
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Maximum power input†
Circuit A
kW
97
111 122 156 173 191 191 249 268 286 286 191 191 191 252 252 271 290 290 290
Circuit B
kW
-
-
-
-
-
-
-
-
-
-
-
173 191 191 191 252 271 290 271 290
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
364 382 382 443 504 542 580 562 580
Nominal current drawn***
Circuit A
A
95
109 125 150 162 171 171 193 214 232 232 171 171 171 210 210 230 250 250 250
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
162 171 171 171 210 230 250 230 250
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
333 342 342 381 420 460 500 480 500
Maximum current drawn (Un)†
Circuit A
A
160 185 200 250 275 300 300 400 430 460 460 300 300 300 400 400 430 460 460 460
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
275 300 300 300 400 430 460 430 460
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
575 600 600 700 800 860 920 890 920
Max. current drawn (Un -10%)****
Circuit A
A
176 206 224 270 300 330 330 419 455 476 476 330 330 330 419 419 455 476 476 476
Circuit B
A
-
-
-
-
-
-
-
-
-
-
-
300 330 330 330 419 455 476 455 476
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
630 660 660 749 838 910 952 931 952
High-efficiency heat units (option 150)
30XW-P/30XWHP
512
562
712
812
862
1012
1162
1314
1464
1612
1762
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Nominal start-up current*
Circuit A
A
587
587
772
772
772
587
587
772
772
772
772
Circuit B
A
-
-
-
-
-
587
587
587
772
772
772
Option 81
A
-
-
-
-
-
749
757
943
965
986
1004
Maximum start-up current**
Circuit A
A
587
587
772
772
772
587
587
772
772
772
772
Circuit B
A
-
-
-
-
-
587
587
587
772
772
772
Option 81
A
-
-
-
-
-
862
887
1072
1172
1202
1232
Cosine phi nominal***
0.88
0.88
0.84
0.86
0.87
0.87
0.88
0.86
0.85
0.86
0.87
Cosine phi maximum****
0.91
0.92
0.90
0.90
0.90
0.91
0.92
0.91
0.91
0.91
0.91
Total harmonic distortion****
%
0
0
0
0
0
0
0
0
0
0
0
Maximum power input†
Circuit A
kW
173
191
252
271
290
173
191
252
252
271
290
Circuit B
kW
-
-
-
-
-
173
191
191
252
271
290
Option 81
kW
-
-
-
-
-
346
382
443
504
542
580
Nominal current drawn***
Circuit A
A
162
171
210
230
250
162
171
210
210
230
250
Circuit B
A
-
-
-
-
-
162
171
171
210
230
250
Option 81
A
-
-
-
-
-
324
342
381
420
460
500
Maximum current drawn (Un)†
Circuit A
A
275
300
400
430
460
275
300
400
400
430
460
Circuit B
A
-
-
-
-
-
275
300
300
400
430
460
Option 81
A
-
-
-
-
-
550
600
700
800
860
920
Maximum current drawn (Un -10%)****
Circuit A
A
300
330
419
455
476
300
330
419
419
455
476
Circuit B
A
-
-
-
-
-
300
330
330
419
455
476
Option 81
A
-
-
-
-
-
600
660
749
838
910
952
* Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor).
Values based on standard Eurovent unit operating conditions: evaporator entering/leaving water temp. = 12°C/7°C, condenser entering/leaving water temp. = 30°C/35°C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor).
Values obtained at operation with maximum unit power input.
*** Values based on standard Eurovent unit operating conditions: evaporator entering/leaving water temp. = 12°C/7°C, condenser entering/leaving water temp. = 30°C/35°C.
**** Values obtained at operation with maximum unit power input.
† Values obtained at operation with maximum unit power input. Values given on the unit name plate.