8 -  DIAGNOSTICS – TROUBLESHOOTING

The control system has many fault tracing aid functions, 
protecting the unit against risks that could result in the failure 
of the unit. The local interface gives quick access to monitor 
all unit operating conditions. If an operating fault is detected, 
the alarm is triggered.

8.1 -  

E-mail notifications

The control provides the option to define one or two 

recipients.who.receive.e-mail.notifications.each.time.the.new.

alarm occurs or all existing alarms have been reset. 

NOTE:

  E-mail  notifications  can  be  configured  only  by 

Carrier service.

8.2 -   Displaying alarms

The control allows the quick display of the unit status. When 
the alarm is activated, the bell on the touch screen lights up.

• 

The blinking bell icon indicates that there is an alarm, 
but the unit is still running.

• 

The highlighted bell icon indicates that the unit is shut 
down due to a detected fault. 

8.3 -   Current alarms

The Current alarms view provides a list of currently active 
alarms, including the date and time the alarm occurred. The 
control displays up to 10 current alarms.
 
To access the Current alarms view, press the 

Alarm

  button   

 in the upper-right part of the screen, and then select 

Current Alarms

 

 

8.4 -   Resetting alarms

Touch Pilot control distinguishes between two types of 
alarms:
• 

General alarms

 are used to indicate pumps failure, 

transducers faults, network connection problems, etc.

• 

Major alarms

 are used to indicate process failure.

 
The alarm can be reset either automatically or manually via 
the Reset alarms menu. The Reset alarms menu displays up 

to.five.alarm.codes.which.are.currently.active.on.the.unit..Only.

logged-in users can access the menu (see also section 4.3.3). 
 
To access the Reset alarms menu, press the 

Alarm

  button  

and select 

Reset Alarms

 

 

 
The alarm can be reset without stopping the machine. In the 
event of a power supply interrupt, the unit restarts automatically 
without the need for an external command. However, any faults 
active when the supply is interrupted are saved and may in 
certain cases prevent a circuit or a unit from restarting. Once 

the.cause.of.the.alarm.has.been.identified.and.corrected,.it.will.

be displayed in the alarm history.

8.5 -   Alarm history

Information regarding resolved alarms is stored in the Alarm 
history menu which is divided into 50 recent alarms and 50 
recent major alarms. Alarm history can be accessed through 
the Touch Pilot user interface or the Network Service Tool.
 
To access the Alarm history menu, press the 

Alarm

  button  

 and select 

Alarm History

 

 

Содержание 30XA-ZE

Страница 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Control AquaForce PUREtec with R 1234ze E 30XA XAS XW 30XA ZE XW ZE...

Страница 2: ...ace access 13 5 2 Web browser configuration 13 5 3 Technical documentation access 13 6 TOUCH PILOT INTERFACE DETAILS 14 6 1 Menu structure 14 6 2 Detailed menu description 15 6 3 Alarms menu 20 6 4 Co...

Страница 3: ...7 21 Dry cooler option 30XW 31 7 22 Hydronic kit option 30XA 31 7 23 30XA ZE and 30XW ZE units HFO 31 7 24 High condensing temperature option 30XW 31 7 25 Maximum condenser leaving water temperature...

Страница 4: ...recommended to ensure optimal operation of the equipment as well as the optimization of all available functionalities Note that this document may refer to optional components and certain functions op...

Страница 5: ...ames with great care IMPORTANT Some specific safety precautions should be taken in case of HFO units For more information about handling the equipment safely please refer to the IOM Unit documentation...

Страница 6: ...the boards otherwise the boards may be damaged In the event of a power supply interrupt the unit restarts automatically without the need for an external command However any faults active when the sup...

Страница 7: ...eat reclaim option Suction gas temperature sensor This sensor is used to control the suction gas temperature It is located at the suction line of each compressor Discharge gas temperature sensor Thiss...

Страница 8: ...unit Heat reclaim condenser flow status 30XA only SIOB Heat reclaim DI 01 J1 Used to verify the water flow on the condenser side Heat reclaim enable switch 30XA only SIOB Heat reclaim DI 02 J1 Used to...

Страница 9: ...Setpoint NOTE The synoptic screen display may vary depending on pumps configuration 4 TOUCH PILOT CONTROL INTERFACE 4 1 General description Touch Pilot includes the 5 in touch screen allowing for easy...

Страница 10: ...hutdown by pressing Confirm Stop or return to the previous screen by pressing the Back button Once the unit has been stopped the Synoptic screen will be displayed see also section 4 2 2 Shows the last...

Страница 11: ...he necessary changes Press the Up Down buttons to navigate between the screens Once all the necessary modifications have been made press to confirm or to cancel changes 4 4 1 General parameters screen...

Страница 12: ...e selected period will be presented in the form of the green band on the timeline Press to confirm or to cancel changes 1 Selection of the applicable days for the time schedule 2 Modification of the p...

Страница 13: ...and use a direct connection NOTE Two users can be connected simultaneously with no priority between them The last modification is taken into account 5 3 Technical documentation access When theTouch P...

Страница 14: ...14 6 TOUCH PILOT INTERFACE DETAILS 6 1 Menu structure...

Страница 15: ...y Running Ready Override Tripout Test Runtest 3 0 to 1 Net Cmd Start Stop Unit start stop via Network 4 0 to 1 Net Cmd Occupied Unit time schedule via Network 5 min Minutes Left for Start Minutes befo...

Страница 16: ...conomizer Gas Temp B Economizer gas temperature circuit B 28 C Economizer Gas Temp C Economizer gas temperature circuit C 29 C Dry Cool Leav Water Tmp Dry Cooler Leaving Water Temperature units fitted...

Страница 17: ...own Indicator State Shutdown indicator status 21 0 to 100 Cond 3 Way Valve Pos Condenser 3 way valve position 22 off on Cooler Heater Command Evaporator heater command status 23 off on Ready or Runnin...

Страница 18: ...s condenser pump 1 12 hour Condenser Pump 2 Hours Operating hours condenser pump 2 not available 13 hour Free Cool A Pump Hours Pump operating hours in Free Cooling circuit A 14 hour Free Cool B Pump...

Страница 19: ...lve status circuit B Depends on the selected language English by default FREECOOL Free cooling No Status Unit Displayed text Description 1 GENERAL PARAMETERS GENERAL PARAMETERS 2 0 to 1 Free Cooling D...

Страница 20: ...26 6 7 C Cooling Ice Setpoint Ice storage setpoint 4 0 1 to 11 1 0 6 C Cooling Ramp Loading Cooling ramp loading setpoint 5 26 7 to 63 37 8 C Heating Setpoint 1 Heating setpoint 1 6 26 7 to 63 37 8 C...

Страница 21: ...6 1 to 15 1 min Unit Off to On Delay Unit Off to On delay 7 00 00 0 Night Mode Start Hour Night mode start time 8 00 00 0 Night Mode End Hour Night mode end time 9 0 to 100 100 Night Capacity Limit N...

Страница 22: ...no reset value 8 10 to 51 7 10 C OAT Full Reset Value OAT max reset value 9 0 to 13 9 0 C Delta T No Reset Value Delta T no reset value 10 0 to 13 9 0 C Delta T Full Reset Value Delta T max reset valu...

Страница 23: ...ek of the month Depends on the selected language English by default DATETIME Date Time configuration No Status Default Displayed text Description Date DD MM YY 1 1 to 31 Day of month Day of the month...

Страница 24: ...en remote off active unoccupied remote off active disabled network off active unoccupied network off active local unoccupied local off active open remote remote off active remote unoccupied remote off...

Страница 25: ...vailable the unit is stopped and started again with the second pump If there is no pump available the unit shuts down Units are fitted with the flow switch allowing for the water flow control For more...

Страница 26: ...eating setpoint 2 heating auto occupied heating setpoint 1 heating auto unoccupied heating setpoint 2 Any configuration default configuration REMOTE OPERATING TYPE Parameter status Active setpoint Hea...

Страница 27: ...dtoprotectthecompressors 7 8 Current limitation Current limitation is used via the demand limit function If the current limitation is active Current Limit Select in the GEN_CONF menu the control calcu...

Страница 28: ...units This function determines in which order the circuit capacity is changed Compressor loading is managed by starting stopping the compressors and controlling the position of the slide valve Two ty...

Страница 29: ...95 35 0 0 100 100 95 30 0 0 100 100 100 0 0 0 Loading sequence Unloading sequence Lead circ Lag circ 1 Lag circ 2 Lead circ Lag circ 1 Lag circ 2 0 0 0 100 100 100 30 0 0 100 100 95 35 0 0 100 100 90...

Страница 30: ...he contact is closed the unit enters the ice storage mode Space temperature AI 01 J25 Analogue input Active setpoint reset via space temperature control Capacity limit control AI 10 J9 Analogue input...

Страница 31: ...g Full Load Timeout when the water temperature setpoint is not reached Full Load Timeout GEN_CONF General Configuration 7 21 Dry cooler option 30XW 30XW units may come with the dry cooler option that...

Страница 32: ...6 holiday periods Each period is defined by three parameters the month the start day and the duration of the holiday period During the holiday periods the controller will be in occupied or unoccupied...

Страница 33: ...ight part of the screen and then select Current Alarms 8 4 Resetting alarms Touch Pilot control distinguishes between two types of alarms General alarms are used to indicate pumps failure transducers...

Страница 34: ...ove As above As above 24 15026 Economizer gas thermistor fault circuit C As above As above As above 25 15030 Free cooling liquid thermistor fault circuit A As above Free cooling disabled As above 26 1...

Страница 35: ...ump is running Discharge pressure transducer defective refrigerant leak or low condenser water temperature 80 10003 Condenser frost protection circuit B As above Circuit B shuts down but the pump is r...

Страница 36: ...uit A Manual None Defective or incorrectly wired solenoid valves defective current transformer 132 10088 Slide valve control unverifiable circuit B Manual None As above 133 10089 Slide valve control u...

Страница 37: ...temperature and the VFD fan 67 Alarm Option configuration has changed Contact Carrier Service 68 Alarm Emergency stop Contact Carrier Service 71 Alarm PTC 1 emergency stop Contact Carrier Service 72 A...

Страница 38: ...rvice 8 Alert DC undervoltage Contact Carrier Service 9 Alert Inverter overloaded Check the VFD output current 10 Alert Motor overtemperature Check the motor temperature 11 Alert Motor thermistor Cont...

Страница 39: ...No 13453 07 2016 Supersedes order No 13453 03 2016 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Отзывы: