5.7 -
Electrical data 30RQ 165R-520R
30RQ
165R 180R 210R 230R 270R 310R 330R 370R 400R 430R 470R 520R
Power circuit supply
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1) or (2)
Circuit A&B
kW
74,6 84,2 99,4 109,0 118,6 138,7 148,3 168,3 177,9 193,2 207,6 237,2
Power factor at maximum power
(1) or (2)
Displacement Power Factor (Cos Phi), standard
unit
0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83
Maximum operating current draw (Un)
(1) or (2)
Standard unit
A
129 145,6 172 188,6 205,2 239,9 256,5 291,2 307,8 334,2 359,1 410,4
Maximum current (Un-10%)
(1) or (2)
Standard unit
A
140,7 156,7 187,6 203,6 219,6 258,5 274,5 313,4 329,4 360,3 384,3 439,2
Maximum start-up current (Un)
(2) + (3)
Standard unit
A
305
362
348
401
418
453
469
504
520
547
572
623
Unit + option 25/25E
A
262
310
305
349
366
401
417
452
468
495
520
571
(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan c locked rotor current of the largest compressor.
5.8 -
Electrical data 30RQP 165R-520R
30RQP
165R 180R 210R 230R 270R 310R 330R 370R 400R 430R 470R 520R
Power circuit supply
Nominal voltage
V-ph-Hz
400 - 3 - 50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Maximum operating input power
(1) or (2)
Circuit A&B
kW
74,8 84,4 99,8 109,3 118,9 139,2 148,7 169 178,6 193,7 208,1 237,8
Power factor at maximum power
(1) or (2)
Displacement Power Factor (Cos Phi), standard
unit
0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85
Maximum operating current draw (Un)
(1) or (2)
Standard unit
A
126,3 142,9 168,4 185 201,6 235,4 252 285,8 302,4 327,9 352,8 403,2
Maximum current (Un-10%)
(1) or (2)
Standard unit
A
138
154
184
200
216
254
270
308
324
354
378
432
Maximum start-up current (Un)
(2) + (3)
Standard unit
A
302
359
344
398
414
448
465
498
515
541
565
616
Unit + option 25/25E
A
259
307
301
346
362
396
413
446
463
489
513
564
(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan c locked rotor current of the largest compressor.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
16