Compressor usage and electrical data
COMPRESSOR
30RA
Reference code
I Nom
I Max
LRA*
Circuit
040
050
060
070
080
090
100
120
140
160
200
240
DQ 12 CA 001EE
14.0
19.1
130
A
A1
B
B1
DQ 12 CA 002EE
16.2
22.1
130
A
A2
A1
A1
B
B2
B1
B1
DQ 12 CA 031EE
21.9
28.3
145
A
A2
A1+A2
A2
A1+A2
B
B2
B2
B1+B2
DQ 12 CA 036EE
24.5
32.8
155
A
A1
A1+A2
A1
A1
A1+A2
A1+A2
A1+A2+A3
B
B1+B2
B1+B2+B3 B1+B2+B3
Legend:
I Nom Nominal current draw at Eurovent conditions (see definition of conditions under nominal unit current draw), A
I Max
Maximum operating current at 360 V, A
LRA
Locked rotor current, A
* With option 25 (electronic starter) the LRA value is reduced by 40%; the maximum start-up time per compresor is <0.8 seconds.
Short-circuit stability and protection
30RA
Short-term short-circuit stability (1s)
With fuse
Other fuses
Other protection type
Without fuse
rms value/peak
rms value
rms value
I
2
t (A
2
s)/peak limit
kA*
kA **
kA***
kA****
040-080
5/7.5
80A gL:50
100A gL:30
19200/12
125A gL:25
160A gL:6
090-160
8/15
160A gL:100
200A gL:35
155000/20
200
8/15
200A gL:100
224A gL:40
280000/20
250A gL:35
240
8/15
250A gL:50
N/A
550000/25
*
This value corresponds to the switch/disconnect capacity, to the power distribution bus bar system capacity (if used) and to the protection circuit capacity in the standard
unit.
**
If the short-circuit current is higher, the unit can be protected by the fuse shown for the specific level.
The fuses (not supplied for Carrier units) are as recommended, to be installed upstream of the unit.
For unit sizes 040 to 160 a fused disconnect switch, equipped with fuses, can be installed in place of the standard unit switch. This should be done on site; please
contact the local service department or a qualified electrician. Alternatively please order the special version from the factory by contacting your local Carrier dealer.
For unit sizes 200 and 240 the installation requires drilling a hole into the control box, changing of the front door, and adapting the bus bar to be able to install the new
fused disconnect switch which is larger than the one used for the standard units.To order this special version from the factory, contact your local Carrier office.
List of recommended components with Siemens reference details:
30RA
Fused disconnect
Contact protection
Control handle
NH Fuses
New protection level with fused
disconnect switch, rms value, kA**
040-080
80 A: 3KL7114-3AA00
3KX71-32-1AA00
Use from disconnect switch
80 A 00gL: 3NA3 824 (3 off)
100
090-160
160 A: 3KL7123-3DA00
3KX71-32-2AA00
of the standard unit
160 A 00gL: 3NA3 836 (3 off) 50
200-240
200 A: 3KL7131-3AA00
3KX71-32-3AA00 +
3KX7112-4AA00
200 A 1gL: 3NA3 140 (3 off)
200 A gL: 50
3KX71-31-3AA00 +
224 A 1gL: 3NA3 142 (3 off)
224 A gL: 50
3KX71-31-3AB00
250 A 1gL: 3NA3 144 (3 off)
250 A gL: 50
224 A + 250 A: 3KL7132-3AA00
240
315 A: 3KL7141-3AA00
3KX71-32-4AA00 +
3KX7112-4AA00
315 A 2gL: 3NA3 252 (3 off)
315 A gL: 40
400 A: 3KL7142-3AA00
3KX71-31-4AA00 +
400 A 2gL: 3NA3 260 (3 off)
400 A gL: 30
3KX71-31-4AB00
*** Shows the new protection values with higher-capacity fuses than those specified in the previous column. If such fuses are part of the electrical installation upstream of
the unit, this is sufficient as anti-short circuit protection to the specified level, without additional protection.
**** If a protection device, other than the recommended fuses above, is used for the installation to ensure that no additional protection is required, the protection device must
have the specified thermal limit (I
2
t) and limit effect characteristics for the short-circuit current. If the protection device does not have the specified characteristics, one of
the specified protection fuses from the previous columns must be installed.