2

INSTALLATION

IMPORTANT

: Effective January 1, 2015, all split system and

packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when handling

parts.

CAUTION

!

Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage
unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment

is damaged or incomplete. Locate unit rating plate on unit corner
panel. It contains information needed to properly install unit.

Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts

provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
For hurricane tie downs, contact distributor for details and PE

Certification (Professional Engineer), if required.
On rooftop applications, mount on level platform or frame. Place

unit above a load–bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit

and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require

wind baffles. Consult the Service Manual – Residential Split
System Air Conditioners and Heat Pumps for wind baffle

construction.

NOTE

: Unit must be level to within

±

2

°

(

3/8 in/ft,

9.5 mm/m)

per compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) above unit.

For proper airflow, a 6–in. (152.4 mm) clearance on 1 side of unit
and 12–in. (304.8 mm) on all remaining sides must be maintained.

Maintain a distance of 24 in. (609.6 mm) between units. Position

so water, snow, or ice from roof or eaves cannot fall directly on
unit.
On rooftop applications, locate unit at least 6 in. above roof
surface.

3/8–in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

View From Top

UNIT BASE PAN

Dimension in. (mm)

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

31–1/2 X 31–1/2

(800 X 800)

9–1/8 (231.8)

6–9/16 (166.7) 24–11/16 (627.1)

35 X 35

(889 X 889)

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

A05177

Fig. 2 – Tiedown Knockout Locations

Operating Ambient

The minimum outdoor operating ambient in cooling mode without

accessory is 55

°

F (12.78

°

C), and the maximum outdoor operating

ambient in cooling mode is 125

°

F (51.67

°

C). The maximum

outdoor operating ambient in heating mode is 66

°

F (18.89

°

C).

Check Defrost Thermostat

Check defrost thermostat to ensure it is properly located and
securely attached. There is a liquid header with a distributor and

feeder tube going into outdoor coil. At the end of the one of the

feeder tubes, there is a 3/8 in. O.D. stub tube approximately 2 in.
(50.8 mm) long (see Fig. 3). The defrost thermostat should be

located on stub tube. Note that there is only one stub tube used
with liquid header, and on most units it is the bottom circuit.

FEEDER TUBE

DEFROST

THERMOSTAT

STUB TUBE

A97517

Fig. 3 – Defrost Thermostat Location

Elevate Unit

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not allow water and/or ice to build up in base pan.

Elevate unit per local climate and code requirements to provide

clearance above estimated snowfall level and ensure adequate
drainage of unit.

Содержание 25HPB6

Страница 1: ...suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing o...

Страница 2: ...ications Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219...

Страница 3: ...rements Refer to Table 2 for field tubing diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuat...

Страница 4: ...valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE...

Страница 5: ...hrough power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death The u...

Страница 6: ...tem caps after system is opened to refrigerant flow back seated Replace caps finger tight and tighten with wrench an additional 1 12 turn 3 Close electrical disconnects to energize system 4 Set room t...

Страница 7: ...up To initiate a forced defrost speedup pins J1 must be shorted with a flat head screwdriver for 5 seconds and RELEASED If the defrost thermostat is open a short defrost cycle will be observed actual...

Страница 8: ...r temperature is below 70_F 21 11_C or the outdoor temperature is not in the favorable range adjust charge for line set length above or below 15ft 4 57 m only Charge level should then be appropriate f...

Страница 9: ...MANP036 FB4CNP048L FV4CNB006L 3 FPMAN 024 FFMANP031 FB4CNP036L FFMANP037 FV4CN B F 003L FX4DN B F 049L FPMBN 018 FPMAN 024 FFMANP030 FPMAN 036 FV4CN B F 005L 3 FX4DN B F 061L 3 FPMBN 024 FPMAN 030 FFM...

Страница 10: ...psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatib...

Отзывы: