Carrier 25HPA6 Скачать руководство пользователя страница 9

9

GENERAL INFORMATION

Infinity Controlled low ambient cooling:

This unit is capable of low ambient cooling down to 0

°

F (--17.8

°

C)

without a kit ONLY when using an Infinity Control. A low
ambient kit is not required for Infinity controlled low ambient

operation. The Infinity Control provides an automatic evaporator
freeze thermostat. Low ambient cooling must be enabled in the

User Interface setup. Fan may not begin to cycle until about 40

°

F

(4.4

°

C) OAT. Fan will cycle based on coil and outdoor air

temperature.
Infinity controlled low ambient mode operates as follows:

S

Fan is OFF when outdoor coil temperature is less than outdoor air
temperature (+ 3

_

F/1.7

_

C) or outdoor fan has been ON for 30

minutes. (Fan is turned off to allow refrigerant system to stabilize.)

S

Fan is ON when outdoor coil temperature is less than outdoor air
temperature (+25

_

F/13.9

_

C) or outdoor coil temperature is more

than 80

_

F (26.7

_

C) or if outdoor fan has been OFF for 30 minutes.

(Fan is turned on to allow refrigerant system to stabilize.)

S

Low pressure switch is ignored for first 3 minutes during low
ambient start up. After 3 minutes, if LPS trips, then outdoor fan
motor is turned off for 10 minutes, with the compressor running. If

LPS closes within 10 minutes then cooling continues with the
outdoor fan cycling per the coil temperature routine listed above

for the remainder of the cooling cycle. If the LPS does not close
within 10 minutes, then the normal LPS trip response (shut down

cooling operation and generate LPS trip error) will occur.

Defrost

This control offers 5 possible defrost interval times: 30, 60, 90, 120
minutes, or AUTO.
Defrost intervals are selected by dip switches on the unit control
board or by the Infinity Control User Interface. The Infinity

Control selection overrides the control board dip switch settings.
Defrost interval times: 30, 60, 90, and 120 minutes or AUTO are
selected by the Infinity Control User Interface (the dip switches are

not used.)
AUTO defrost adjusts the defrost interval time based on the last

defrost time as follows:

S

When defrost time <3 minutes, the next defrost interval=120
minutes.

S

When defrost time 3--5 minutes, the next defrost interval=90
minutes.

S

When defrost time 5--7 minutes, the next defrost interval=60
minutes.

S

When defrost time >7 minutes, the next defrost interval=30

minutes.

The control board accumulates compressor run time. As the
accumulated run time approaches the selected defrost interval time,

the control board monitors the coil temperature sensor for a defrost

demand. If a defrost demand exists, a defrost cycle will be initiated
at the end of the selected time interval. A defrost demand exists

when the coil temperature is at or below 32

_

F (0

_

C) for 4 minutes

during the interval.
The defrost cycle is terminated when the coil temperature reaches

65

_

F (18.33

_

C)or 10 minutes has passed. When OAT is > 25

°

F

(--3.9

°

C), defrost will occur in low or high stage as demanded by

the thermostat or User Interface.
If OAT is

25

°

F (3.9

_

C), defrost will occur in high stage only,

regardless of thermostat or User Interface demand, and will
terminate at 50

_

F (10

_

C) coil temperature with a minimum of 2.5

minutes in defrost.
If the coil temperature does not reach 32

_

F (0

_

C) within the

interval, the interval timer will be reset and start over.

S

Upon initial power up the first defrost interval is defaulted to 30

minutes. Remaining intervals are at selected times.

S

Defrost is only allowed to occur below 50

_

F (10

_

C) outdoor

ambient temperature.

The outdoor fan output (ODF) will remain off for 20 seconds after
termination. This delay will allow time for the system to capture

the heat from the outdoor coil and reduce the “steam cloud” effect
that may occur on transition from defrost to heating cycle. The

outdoor fan output OFF delay of 20 seconds may be defeated to

enable the fan to energize immediately at the time of termination
and 12 seconds prior to the reversing valve de--energizing through

the

User

Interface

setup

screen

(available

with

SYSTXCCUID01--C), or forced defrost pins as follows:
The ODF fan delay defeat can be toggled by shorting the forced

defrost pins for >15 seconds while in the standby mode (status
LED on solid). The LED will start to flash when the toggle has

taken place.
Status code 4 shows the fan delay defeat is active (no delay).
Status code 3 shows that it si not active (20 second delay).
The code will continue to be displayed until after the short is
removed. There is a 5 second wait before the code is cancelled

once the short is removed. the code that is flashing will finish
before going back to solid LED. The control is shipped with the

ODF fan delay defeat NOT active.
The change in status is remembered until toggled to a new status.

A power down/power up sequence will not reset the status. It may

be necessary to do the toggle twice to cycle to the desired state of
the defeat.

Defrost Hold

On a non--communicating system, if the thermostat becomes

satisfied (Y1 or Y1 and Y2) before the defrost cycle is terminated,
the control will “hold” in defrost mode and finish the defrost cycle

on the next call for heat.
On models with communicating Infinity Control, defrost hold is

not needed because the User Interface will complete the defrost

cycle before shutting down the system.

Forced Defrost

On a system with non--communicating (non--Infinity) control,

forced defrost can be initiated by manually shorting the 2--pin

header labeled FORCED DEFROST (see Fig 6) on the control
board for 5 seconds then releasing.
On a system with communicating (Infinity) control, forced defrost
is initiated with the User Interface.
On all models, during a Forced Defrost:

S

If coil temperature is at defrost temperature of 32

_

F (0

_

C), and

outdoor air temperature is below 50

_

F (10

_

C), a full defrost

sequence will occur.

S

If coil temperature or outdoor air temperature does not meet the

above requirements, an abbreviated 30 second defrost will occur.

Quiet Shift

Quiet Shift is a field--selectable defrost mode which may eliminate
occasional noise that could be heard at the start of the defrost cycle

and restarting of the heating cycle. On a non--communicating
system, this feature must be enabled by selecting the 3rd position

of the 3--position dip switch.

For communicating (Infinity)

systems, it must be enabled at the User Interface. When activated,
the following sequence of operation will occur. Reversing valve

will energize and compressor will turn off for 30 seconds, then turn
back on to complete defrost. At the end of the defrost cycle, the

reversing valve de--energizes, compressor will turn off for another

30 seconds, and the fan will turn off for 40 seconds, before starting
in the heating mode.

Liquid--Line Solenoid Accessory

In heat pump long--line applications, a liquid--line solenoid is

required to control refrigerant migration in the heating mode. The
solenoid should be installed near the outdoor unit with the arrow

facing the outdoor unit. This is the direction of flow control. See
application manual for long--line application details.

Accessory Liquid Solenoid with Infinity Communicating

Control:

When using the Infinity Control, the liquid--line solenoid

25H

PA

6

Содержание 25HPA6

Страница 1: ...mation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result...

Страница 2: ... presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shipping company prior to installation if shipme...

Страница 3: ...IMPORTANT Flow arrow must point toward outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure...

Страница 4: ...EQUIRED FOR LONG LINE APPLICATIONS Over 80 ft 24 38 m REQUIRED FOR SEA COAST APPLICATIONS Within 2 miles 3 22 km Crankcase Heater Standard Standard Standard Evaporator Freeze Protection Standard with Infinityt Control Low Ambient not allowed with non communicating thermostat No No Liquid Line Solenoid Valve No Yes No Low Ambient Control Standard with Infinity Control Low ambient not allowed with n...

Страница 5: ...frigerant tubing and indoor coil are now ready for leak testing This check should include all field and factory joints Evacuate Refrigerant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended d...

Страница 6: ...ovide blower operation to match the capacities of the compressor during high and low stage cooling operation Tap selections on the furnace control board enable the installing technician to select the proper airflows for each stage of cooling Below is a brief summary of the furnace airflow configurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire ...

Страница 7: ...f 2 minutes in low stage adjust the set point at least 5 F 2 8 C below room ambient System Functions And Sequence Of Operation The 25HPA6 models utilize either an Infinity Communicating User Interface or a 2 stage cooling indoor thermostat With a call for first stage cooling the outdoor fan and low stage compressor are energized If low stage cannot satisfy cooling demand high stage is energized by...

Страница 8: ...ing of the by pass port is controlled by an internal electrically operated solenoid The modulated scroll uses a single step of unloading to go from full capacity to approximately 67 capacity A single speed high efficiency motor continues to run while the scroll modulates between the two capacity steps Modulation is achieved by venting a portion of the gas in the first suction pocket back to the lo...

Страница 9: ...nt temperature The outdoor fan output ODF will remain off for 20 seconds after termination This delay will allow time for the system to capture the heat from the outdoor coil and reduce the steam cloud effect that may occur on transition from defrost to heating cycle The outdoor fan output OFF delay of 20 seconds may be defeated to enable the fan to energize immediately at the time of termination ...

Страница 10: ...ot use chart to adjust refrigerant charge NOTE In heating mode check refrigerant charge only when pressures are stable If in doubt remove charge and weigh in correct refrigerant charge NOTE When charging is necessary during heating season charge must be weighed in accordance with unit rating plate 0 6 oz ft 17 74 g m of 3 8 in liquid line above or below 15 ft 4 57 m respectively EXAMPLE To calcula...

Страница 11: ...is no 230v at the compressor contactor s when the indoor unit is powered and cooling or heating demand exists the appropriate fault code is displayed Verify the disconnect is closed and 230v wiring is connected to the unit Compressor Voltage Sensing The control board input terminals labeled VS and L2 see Fig 6 are used to detect compressor voltage status and alert the user of potential problems Th...

Страница 12: ...ating conditions The comparison is S In cooling if the outdoor air sensor indicates 10_F 5 6_C warmer than the coil sensor or the outdoor air sensor indicates 20_F 11_C cooler than the coil sensor the sensors are out of range S In heating if the outdoor air sensor indicates 35_F 19 4_C warmer than the coil sensor or the outdoor air sensor indicates 10_F 5 6_C cooler than the coil sensor the sensor...

Страница 13: ...nect is closed and 230v wiring is connected to the unit Outdoor Air Temp Sensor Fault 53 Outdoor air sensor not reading or out of range Ohm out sensor and check wiring Outdoor Coil Sensor Fault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Low S...

Страница 14: ...2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be required available Heat Stag...

Страница 15: ...ing into suction line with compressor operating 10 Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard 11 Use hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liq...

Страница 16: ...10 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 05 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 25HPA6 1SI Replaces New 25HPA6 ...

Отзывы: