ACCESSORY USAGE GUIDELINE

Accessory

REQUIRED FOR LOW---AMBI-

ENT APPLICATIONS

(Below 55

°

F)

REQUIRED FOR LONG

LINE APPLICATIONS*

(Over 80 Ft.)

REQUIRED FOR SEA

COAST APPLICATIONS

(Within 2 miles)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Accumulator

No

No

No

Compressor Start Assist Capacitor and

Relay

Yes

Yes

No

Motor Master

®

Control

or Low---ambient Pressure Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

Liquid Line Solenoid Valve

No

See Long---Line Application

Guideline

No

Ball Bearing Fan Motor

Yes

{

No

No

* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differntial, refer to Residential Split---System Longline Application Guideline.

{

Required for Low---Ambient Controller (full modulation feature) and MotorMaster

r

Control only.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when MotorMaster

r

is used.

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor

motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the

following applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the

following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of
low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.

Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Cycle Protector

The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay

after power to the compressor has been interrupted for any

reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.

6. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation

when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7. Isolation Relay

An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

8. Liquid--Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is

to be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in
the heating mode. See Long Line Guideline.

9. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in

order to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain

working head pressure at low--ambient temperatures down to 0

_

F

when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling operation is

used at outdoor temperatures below 55

_

F (12.8

_

C).

10. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,

designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling

mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C),

it maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

--12

_

C).
Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures

below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

25H

B

R

3

Содержание 25HBR3

Страница 1: ...essor S Filter drier S Loss of charge pressure switch S Balanced refrigeration system for maximum reliability Durability WeatherArmort protection package S Solid Durable sheet metal construction S Wir...

Страница 2: ...rporation has determined that this product meets the ENERGY STAR guidelines for energy efficiency Refer to the combination ratings in Product Data for system combinations that meet Energy Star guideli...

Страница 3: ...system operation The maximum allowable total equivalent length is 250Ft The maximum vertical separation is 200 Ft when outdoor unit is above indoor unit and 60 Ft when the outdoor unit is below the in...

Страница 4: ...ostat conversion kit is a 24 vac accessory that can turn a 4 wire thermostat application into a 5 wire application This kit can also be used to replace a broken thermostat wire or add an extra wire wh...

Страница 5: ...pplications 5 Cycle Protector The cycle protector is designed to prevent compressor short cycling This control provides an approximate 5 minute delay after power to the compressor has been interrupted...

Страница 6: ...low the second stage set point Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 14 Sound Hood Wraparound sound reducing cover for the compressor Re...

Страница 7: ...t applicable tables of the NEC ANSI NFPA 70 Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Loc...

Страница 8: ...8 DIMENSIONS Note Optional G dense wire grille shown 25HBR3...

Страница 9: ...NIT INTEGRATED HEATING CAPACITY MBTUH 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 23 4 kW 25HBR324A G FA4CNF024 25HBR330A G FA4CNF030 25HBR342A G FC4DNF042 A05007 25HBR336A G FC4DNF036 25HBR360A G FC4DNB060 2...

Страница 10: ...H 2417A 17 300 TDR TXV 14 00 12 00 15 600 3 84 9 900 2 52 8 5 58MVB060 14 CNRH 2417A 17 400 TDR TXV 14 00 12 00 15 600 3 82 9 900 2 52 8 5 58MVB080 14 CNRH 2417A 17 400 TDR TXV 14 00 12 00 15 600 3 84...

Страница 11: ...TDR TXV 14 00 11 70 20 600 3 60 13 700 2 52 8 4 58MVB100 20 CNRH 3017A 22 800 TDR TXV 14 00 11 70 20 600 3 60 13 700 2 50 8 2 58MVB120 20 CNRH 3017A 22 800 TDR TXV 14 00 11 70 20 600 3 60 13 700 2 50...

Страница 12: ...8 2 58CV A X 070 12 CNRV 3017A 28 600 TXV 13 00 10 50 29 600 3 44 18 900 2 44 8 1 CNRV 3017A 28 400 TDR TXV 14 00 11 50 29 200 3 52 18 000 2 50 8 2 58MVB060 14 CNRV 3017A 28 400 TDR TXV 14 00 11 50 2...

Страница 13: ...8 4 58MVB120 20 CSRH 3612A 28 600 TDR TXV 14 00 11 50 28 800 3 62 18 100 2 54 8 4 58CV A X 070 12 CSRH 3612A 28 600 TDR TXV 14 00 11 70 28 800 3 64 18 000 2 56 8 5 58CV A X 090 16 CSRH 3612A 28 600 T...

Страница 14: ...13 20 11 00 35 000 3 50 21 000 2 46 8 2 58MVB040 14 CSRH 3612A 33 400 TDR TXV 13 50 11 20 34 800 3 52 20 800 2 48 8 2 58MVB060 14 CSRH 3612A 33 400 TDR TXV 13 20 11 00 35 000 3 48 21 000 2 44 8 1 58MV...

Страница 15: ...TDR TXV 14 00 11 50 41 000 3 64 25 400 2 58 8 1 58CV A X 110 20 CNRV 4824A 42 000 TXV 13 00 10 80 42 500 3 58 26 400 2 48 7 9 CNRV 4824A 41 500 TDR TXV 13 50 11 20 41 500 3 56 25 600 2 52 7 9 58MVB040...

Страница 16: ...50 11 20 47 500 3 30 29 400 2 52 8 2 FK4DNB006 47 000 TDR TXV 14 00 11 50 47 500 3 42 29 400 2 58 8 4 CAR 4817A 43 500 TDR TXV 13 00 10 80 46 500 3 24 29 800 2 46 8 1 58CV A X 090 16 CAR 4821A 44 500...

Страница 17: ...8MVB100 20 CSRH 6012A 46 000 TDR TXV 13 50 11 20 47 500 3 26 29 600 2 50 8 1 58MVB120 20 CSRH 6012A 46 000 TDR TXV 13 50 11 20 47 500 3 28 29 600 2 50 8 2 58CV A X 090 16 CSRH 6012A 46 000 TDR TXV 13...

Страница 18: ...04 15 04 1 67 14 42 14 42 1 86 13 76 13 76 2 06 675 72 20 63 11 24 1 25 19 87 10 95 1 39 19 07 10 66 1 54 18 23 10 35 1 71 17 35 10 04 1 90 16 43 9 70 2 11 67 18 77 14 41 1 25 18 05 14 11 1 38 17 28 1...

Страница 19: ...1 00 1 00 FK4DNF001 1 02 0 94 FK4DNF002 1 03 0 95 FK4DNF003 1 03 0 95 CAR 2414A 1 01 1 01 CAR 2417A 1 01 1 01 CAR 3014A 1 01 1 01 CAR 3017A 1 01 1 01 CNRF 2418A 1 01 1 01 CNRH 2417A 1 01 1 01 CNRH 30...

Страница 20: ...AR 3614A 1 00 1 03 CAR 3617A 1 01 1 04 CAR 3621A 1 01 1 04 CNRF 3618A 1 01 1 04 CNRH 3017A 1 01 1 04 CNRH 3617A 1 01 1 04 CNRV 3014A 1 01 1 04 CNRV 3017A 1 01 1 04 CNRV 3617A 1 01 1 04 CNRV 3621A 1 01...

Страница 21: ...12 CNRH 3617A 0 97 0 99 58CV A X 070 12 CNRH 4221A 0 99 0 99 58CV A X 070 12 CSRH 3612A 0 98 0 98 58CV A X 070 12 CSRH 4212A 0 98 0 98 58CV A X 070 12 CAR 3617A 0 98 0 98 58CV A X 090 16 CNRH 3617A 0...

Страница 22: ...V A X 070 12 CNRH 4821A 0 99 0 97 58CV A X 070 12 CSRH 4212A 0 98 0 96 58CV A X 070 12 CSRH 4812A 1 00 0 98 58CV A X 070 12 CAR 4817A 1 00 0 98 58CV A X 090 16 CNRH 4221A 0 98 0 96 58CV A X 090 16 CNR...

Страница 23: ...4 57 40 29 40 29 5 06 38 46 38 46 5 60 57 46 72 46 72 3 34 45 23 45 23 3 71 43 67 43 67 4 12 42 02 42 02 4 57 40 29 40 29 5 06 38 47 38 47 5 60 Cooling Indoor Model Capacity Power Furnace Model FC4DN...

Страница 24: ...95 5 53 63 10 35 87 6 05 60 01 34 75 6 61 56 79 33 60 7 21 67 65 44 49 83 4 58 62 86 48 76 5 00 60 20 47 66 5 46 57 46 46 53 5 97 54 61 45 35 6 52 51 65 44 13 7 13 63 60 91 48 02 4 53 58 49 46 94 4 95...

Страница 25: ...34 1 51 17 40 17 40 1 50 16 62 16 62 1 48 15 45 15 45 1 45 75 525 9 19 8 45 1 37 11 68 10 73 1 44 14 53 13 25 1 51 17 67 15 70 1 60 19 47 17 72 1 65 19 53 19 53 1 65 19 14 19 14 1 63 18 57 18 57 1 61...

Страница 26: ...AR 3014A 0 87 0 93 CAR 3017A 0 87 0 93 CNRF 2418A 1 00 0 96 CNRH 2417A 1 00 0 96 CNRH 3017A 0 87 0 93 CNRV 2414A 1 00 0 96 CNRV 2417A 1 00 0 96 CNRV 3014A 0 87 0 93 CNRV 3017A 0 87 0 93 CSRH 2412A 0 9...

Страница 27: ...3617A 0 97 0 98 CNRV 3014A 0 98 0 98 CNRV 3017A 0 98 0 98 CNRV 3617A 0 97 0 97 CNRV 3621A 0 97 0 97 CSRH 3012A 0 98 0 98 CSRH 3612A 0 96 0 95 CAR 3014A 0 97 0 95 58CV A X 070 12 CAR 3614A 0 97 0 94 5...

Страница 28: ...A X 070 12 CSRH 4212A 0 98 0 97 58CV A X 070 12 CAR 3617A 1 00 1 01 58CV A X 090 16 CNRH 3617A 1 00 1 02 58CV A X 090 16 CNRH 4221A 0 99 0 98 58CV A X 090 16 CNRV 3617A 1 00 1 02 58CV A X 090 16 CSRH...

Страница 29: ...9 1 01 58CV A X 070 12 CAR 4817A 0 99 0 99 58CV A X 090 16 CNRH 4221A 0 96 0 99 58CV A X 090 16 CNRH 4821A 0 98 0 98 58CV A X 090 16 CSRH 4212A 0 98 0 98 58CV A X 090 16 CSRH 4812A 0 99 0 99 58CV A X...

Страница 30: ...7 87 4 17 55 70 55 70 4 43 63 79 63 79 4 64 Heating Indoor Model Capacity Power Furnace Model FC4DN F B 048 1 00 1 00 FC4DN F B 048 1 01 1 01 FC4DN F B 060 1 01 0 99 FK4DNB006 0 99 0 98 FK4DNF005 0 99...

Страница 31: ...80 5 07 2250 25 67 23 62 4 22 31 26 28 73 4 35 37 37 34 07 4 51 44 05 39 12 4 67 51 64 46 99 4 83 58 08 58 08 4 98 60 16 60 16 5 02 57 77 57 77 4 95 75 1750 24 36 22 41 4 27 30 00 27 57 4 45 36 07 32...

Страница 32: ...on resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with steel wire safety guards Compressor Compressor will be hermetically sealed Compressor w...

Отзывы: