background image

4

VALVE CORE

SERVICE VALVE

A14236

Fig. 5 –

 

Vapor Service Valve

Brazing Connections

Connect vapor tube to fitting on outdoor unit vapor service valves

(see Table 2). Connect liquid tubing to adapter tube on liquid

service valve. Use refrigerant grade tubing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat–sinking material

such as a wet cloth while brazing.

Apply heat absorbing paste or heat sink product between service

valve and joint. Wrap service valves with a heat sinking material

such as a wet cloth.
After wrapping service valve with a wet cloth, tubing set can be

brazed to service valve using either silver bearing or non–silver

bearing brazing material. Do not use soft solder (materials which

melt below 800

°

F/427

°

C). Consult local code requirements.

NOTE

:  Some outdoor units contain a mechanical fitting at the

liquid distributor.  This connection is not field serviceable and

should not be disturbed.

NOTE

:  For Liquid Service Valve 

 Braze lineset to adapter tube

BEFORE bolting adapter to valve.  This helps prevent overheating
and damage to plastic washer or o

ring.

For Vapor Service Valve 

 remove valve core from schrader port

on Service Valve BEFORE brazing.  This helps prevent

overheating and damage to valve seals (refer to Fig. 5). Replace

valve core when brazing is completed.

FIRE HAZARD

Failure to following this warning could result in personal

injury, death and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes

and contacts brazing torch.  Make sure the refrigerant charge is

properly removed from both the high and low sides of the

system before brazing any component or lines.

!

WARNING

Clean line set tube ends with emery cloth or steel brush. Remove

any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service

valve and joint. Wrap service valves with a heat sinking material

such as a wet cloth.
Braze joints using a Sil

Fos or Phos

copper alloy.

Table 2 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

UNIT SIZE

LIQUID

RATED VAPOR

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

18, 24

3/8

3/8

5/8

5/8

30, 36

3/8

3/8

3/4

3/4

42, 48

3/8

3/8

7/8

7/8

60

3/8

3/8

7/8

1–1/8

*

Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance 
data when using different size and length linesets.

Notes

:

1. Do not apply capillary tube indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 

20 ft. (6.09 m) vertical differential 250 ft. (76.2 m) Total Equivalent  Length, refer to 
the Residential Piping and Longline Guideline – Air Conditioners and Heat Pumps 
using Puron refrigerant.

Installing with Indoor Piston

Heat pumps with piston indoor ratings are shipped with the correct

piston size in the accessory bag.  Check piston size shipped with

indoor unit to see if it matches required indoor piston size. If it

does not match, replace indoor piston with correct piston size

which is listed on the rating plate.

NOTE

:  Heat pumps without piston indoor ratings may be

installed as a replacement component in a piston system.  When
installing a non

piston rated heat pump with with a piston indoor

the correct indoor piston must be installed.  When not listed on the
rating plate the correct piston size is listed in the product data.
Replacement pistons can be ordered from Replacement
Components.

13/16” BRASS HEX NUT

TEFLON

®

 SEAL

TEFLON

®

RINGS

3/4” BRASS HEX BODY

“H” DISTRIBUTOR

PISTON RETAINER

PISTON

A10342

Fig. 6 –

 

Indoor Piston Installation

Install Liquid Line Filter Drier Indoor

Refer to Fig. 7 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to 5 in. (127 mm) long liquid tube from

step 1.

4. Connect and braze liquid refrigerant tube to the filter drier.

IMPORTANT

: Installation of the filter drier in liquid line is

required.

A05227

Fig. 7 –

 

Liquid Line Filter Drier

Содержание 25HBC5

Страница 1: ...h a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testin...

Страница 2: ...Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm abo...

Страница 3: ...ng diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamin...

Страница 4: ...lve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tu...

Страница 5: ...nd voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Ope...

Страница 6: ...R C RVS COOLING C W2 HP THERMOSTAT TYPICAL FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE LEGEND 24 V FACTORY WIRING 24 V FIEL...

Страница 7: ...its R Y and R G Circuit R Y energizes contactor starting outdoor fan motor and compressor Circuit R G energizes indoor blower relay starting blower motor on high speed Should temperature continue to f...

Страница 8: ...f the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_...

Страница 9: ...rect Do not use chart to adjust refrigerant charge Table 5 Additional Subcooling Required Model 25H 4 Subcooling Delta from Rating Plate Value Outdoor Unit Tonnage Indoor Unit Additional Subcooling Re...

Страница 10: ...CN B F 005L FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4CNB006L 3 FPMAN 024 FFMANP031 FB4CNP036L FFMANP037 FV4CN B F 003L FX4DN B F 049L FPMBN 018 FPMAN 024 FFMANP030 FPMAN 036 FV4CN B F 00...

Страница 11: ...ditions or refrigerant slugging may occur Charge must be weighed in Note Superheat F is at low side service port Allow a tolerance of 3 F Note Indoor dry bulb between 70 F and 80 F Table 9 Required Su...

Страница 12: ...0 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compati...

Отзывы: