7
ELECTRICAL DATA
UNIT SIZE ---
VOLTAGE,
SERIES
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MIN WIRE
SIZE
{
MIN
WIRE
SIZE
{
MAX
LENGTH
(ft.)
}
MAX
LENGTH
(ft.)
}
MAX FUSE**
or CKT BRK
AMPS
MAX
MIN
LRA
RLA FLA
60
°
C
75
°
C
60
°
C
75
°
C
18---32
208---230/1 253
197
48
9.0
0.75 11.9
14
14
66
62
20
24---31
58
12.8 0.75 16.8
14
14
47
45
25
30---31
77
16.5 0.75 21.4
12
12
58
56
30
36---31
79
16.7
1.4
22.2
12
12
56
54
35
42---31
109
19.9
1.2
26.0
10
10
77
73
40
48---31
117
27.3
1.2
35.4
8
8
88
84
50
60---31
134
26.3
1.2
34.1
8
8
91
87
50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30
_
C (86
_
F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60
_
C (140
_
F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or
75
_
C (140 or 167
_
F) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of
the NEC (ANSI/NFPA 70).
}
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA ---
Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
SOUND POWER
UNIT SIZE ---
VOLTAGE, SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dB, without tone adjustment)
125
250
500
1000
2000
4000
8000
18---32
76
56.5
64.5
70
71
69
65
60.5
24---31
75
54.5
64
69
69.5
67.5
64
58
30---31
74
52
62.5
66.5
68.5
65
63.5
59
36---31
76
60
64
69.5
70
68.5
65.5
60.5
42---31
77
55.5
60
63.5
71.5
65
62.5
59
48---31
78
57
64
68
74
67
63
58.5
60---31
76
58.5
63
68
70.5
66.5
64.5
59.5
SOUND POWER WITH SOUND SHIELD
UNIT SIZE ---
VOLTAGE, SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dB, without tone adjustment)
125
250
500
1000
2000
4000
8000
18---32
75
56.0
64.5
69.5
70.5
68.5
65.0
59.5
24---31
74
54.0
63.5
69.0
69.0
67.5
63.5
57.5
30---31
74
51.5
62.0
66.5
67.5
64.5
62.0
57.5
36---31
76
58.5
63.5
69.5
70.5
69.0
65.5
60.5
42---31
75
55.0
60.5
63.5
69.0
64.5
61.5
56.0
48---31
75
57.5
63.0
67.5
71.5
65.5
60.5
54.5
60---31
75
58.5
62.5
67.5
69.0
64.5
61.5
56.0
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
REQUIRED SUBCOOLING
_
F (
_
C)
OUTDOOR HEATING PISTON #
18---32
10 (5.6)
42
24---31
12 (6.7)
46
30---31
11 (6.1)
55
36---31
10 (5.6)
57
42---31
11 (6.1)
61
48---31
11 (6.1)
61
60---31
12 (6.7)
76
25H
B
A
3
Содержание 25HBA3 Series
Страница 8: ...8 DIMENSIONS 25HBA3 ...