The control is shipped with the brownout active. The change in
status is remembered until toggled to a new status. A power

down/power up sequence will not reset the status. It may be
necessary to do the toggle twice to cycle to the desired state of the

defeat.

230V Line (Power Disconnect) Detection

If there is no 230v at the compressor contactor(s) when the indoor
unit is powered and cooling demand exists, the appropriate error

code is displayed (see Table 6). Verify that the disconnect is closed

and 230v wiring is connected to the unit.

Compressor Voltage Sensing

The control board input terminals labeled VS, VR and L2 on

24ANA7 models and VS and L2 on 24ANA1 models (see Fig. 6)

are used to detect compressor voltage status, and alert the user of
potential problems. The control continuously monitors the high

voltage on the run capacitor of the compressor motor. Voltage
should be present any time the compressor contactor is energized,

and voltage should not be present when the contactor is

de--energized.

Contactor Shorted Detection

If there is compressor voltage sensed when there is no demand for

compressor operation, the contactor may be stuck closed or there is
a wiring error. The control will flash the appropriate fault code.

24ANA7 Models, Compressor Thermal Cutout

The control senses the compressor voltage at VR and VS. When

starting or running, a phase difference of the voltages on the inputs
will indicate the thermal protector is closed. If the phase difference

is 5 degrees or less for 10 seconds, the internal protector is open.

The control de--energizes the appropriate compressor contactor for
15 minutes, but continues to operate the outdoor fan. The control

Status LED will flash the appropriate code shown in Table 6. After
15 minutes, with a call for low-- or high--stage cooling, the

appropriate compressor contactor is energized. If the thermal

protector has not re--set, the outdoor fan is turned off. If the call for
cooling or heating continues, the control will energize the

compressor contactor every 15 minutes. If the thermal protector
closes, (at the next 15 minute interval check), the unit will resume

operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code is

displayed.

24ANA1 Models, Compressor Thermal Cutout

If the control senses the compressor voltage after start--up, and is

then absent for 10 consecutive seconds while cooling demand

exists, the thermal protector is open. The control de--energizes the
compressor contactor for 15 minutes, but continues to operate the

outdoor fan. The control Status LED will flash the appropriate
code shown in Table 6. After 15 minutes, with a call for low-- or

high--stage cooling, the compressor contactor is energized. If the

thermal protector has not re--set, the outdoor fan is turned off. If
the call for cooling continues, the control will energize the

compressor contactor every 15 minutes. If the thermal protector
closes, (at the next 15 minute interval check), the unit will resume

operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code is

displayed.

Low or High Contactor Open (24ANA7 models) / No

230V at Compressor (24ANA1 models)

If the compressor voltage is not sensed when the compressor
should be starting, the appropriate contactor may be stuck open or

there is a wiring error. The control will flash the appropriate fault
code. Check the contactor and control box wiring.

24ANA7 Models Only, Compressor Start Detection

In low--stage, if the specified start voltage at VR terminal is not

achieved, the start relay is de--energized after 1 second and the
control will flash the appropriate fault code.
In high--stage, if the specified start voltage at VS terminal is not
achieved, the start relay is de--energized after 1 second and the

control will flash the appropriate fault code.
If the specified start voltage is not achieved for 3 consecutive

low--stage starts, low--stage operation is locked out for 30 minutes.

If the specified start voltage is not achieved for 3 consecutive
high--stage starts, high--stage operation is locked out for 30

minutes. The control will flash the appropriate fault code.

Troubleshooting 24ANA7 units for proper switching

between low-- & high--stages

Check the suction and liquid pressures at the service valves.
Suction pressure should be reduced by 5--10% when switching

from low to high capacity. There should be a 10--20% increase in

liquid pressure when switching from low to high capacity.
Compressor current should increase 100--250% when switching

from low to high--stage.

Troubleshooting 24ANA1 units for proper switching

between low-- & high--stages

Check the suction pressures at the service valves. Suction pressure
should be reduced by 3--10% when switching from low to high

capacity.

NOTE

: The liquid pressures are very similar between low-- and

high--stage operation, so liquid pressure should not be used for
troubleshooting.
Compressor current should increase 20--45% when switching from

low-- to high--stage. The compressor solenoid when energized in

high--stage, should measure 24vac.
When the compressor is operating in low--stage the 24v DC

compressor solenoid coil is de--energized. When the compressor is
operating in high--stage, the 24v DC solenoid coil is energized.

The solenoid plug harness that is connected to the compressor has

an internal rectifier that converts the 24v AC signal to 24v DC.

DO NOT INSTALL A PLUG WITHOUT AN INTERNAL

RECTIFIER

.

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by

the DC solenoid, that modulates between high-- and low--stage. If

it is suspected that the unloader is not working, the following
methods may be used to verify operation.

1. Operate the system and measure compressor amperage.

Cycle the unloader on and off at 30 second plus intervals at

the UI (from low-- to high--stage and back to low--stage).
Wait 5 seconds after staging to high before taking a reading.
The compressor amperage should go up or down at least 20

percent.

2. If step one does not give the expected results, remove the

solenoid plug from the compressor and with the unit run-
ning and the UI calling for high--stage, test the voltage out-

put at the plug with a DC voltmeter. The reading should be
24 volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil resistance. The
resistance should be 32 to 60 ohms depending on com-

pressor temperature. If the coil resistance is infinite, much
lower than 32 ohms, or is grounded, the compressor must
be replaced.

24AN

A

Содержание 24ANA1 Infinity

Страница 1: ...cognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazard...

Страница 2: ...llation Specifications for this unit in residential new construction market require the outdoor unit indoor unit refrigerant tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Application Guideline and Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for ...

Страница 3: ...d tubing diameters Refer to Table 2 for accessory requirements There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Outdoor Unit Connected to Factory Approved Indoor Unit Outdoor unit contains correct system refrigerant charge for op...

Страница 4: ...r CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Installation of filter drier in liquid line is required Refer to Fig 3 and install filter drier as follows 1 Braze 5 in 127 mm liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor co...

Страница 5: ...m unit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if ...

Страница 6: ... board that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections This fan coil has an adjustable blower off delay factory set at 90 sec for high and low stage blower operation For other combinations of equipment consult the Product Data Sheet START UP CAUTION UNIT OPERATION AND SAFETY HAZARD Failure to follow...

Страница 7: ...ht on the outdoor board see Fig 6 indicates successful communication with the other system products The green LED will remain OFF until communications is established Once a valid command is received the green LED will turn ON continuously If no communication is received within 2 minutes the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light i...

Страница 8: ...s Table 3 Outdoor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 24ANA124 9 57 10 88 11 90 24ANA136 9 06 10 23 11 90 24ANA148 9 91 11 04 11 90 24ANA160 10 83 11 70 11 90 NOTE For 24ANA1 models in low ambient cooling the PWM output for both high and low stage equals the value for low stage operation below 55_F 1...

Страница 9: ...r the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriate fault code temporarily Table 4 Model Plug Information MODEL NUMBER MODEL PLUG NUMBER PIN RESISTANCE K ohms Pins 1 4 Pins 2 3 24ANA724 HK70EZ00...

Страница 10: ... Contactor Open 24ANA7 models No 230V at Compressor 24ANA1 models If the compressor voltage is not sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 24ANA7 Models Only Compressor Start Detection In low stage if the specified start voltage a...

Страница 11: ...rload attached to motor windings Compressor Control Contactors The contactor s have a 24 volt coil The electronic control board controls the operation of the appropriate contactors TEMPERATURE THERMISTORS Thermistors are electronic devices which sense temperature As the temperature increases the resistance decreases Thermistors are used to sense outdoor ambient OAT and coil temperature OCT Refer t...

Страница 12: ... that all wiring and tubing is secure in unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Users Manual with owner Explain system operation and periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing h...

Страница 13: ...nd exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed high stage Ther mal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage s...

Страница 14: ...M 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Return SRTN SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor THERMIDISTAT VARIABLE SPEED FURNACE TWO STAGE AIR CONDITIONER A09338 Thermidistat Model TP PRH 01 or TP NRH 01 w VS Furnace 2 Stage Air Conditioner Variable Speed Furnace Thermidistat 2 Stage Air Conditioner Heat Stage 2 O B W2 W2 Heat...

Страница 15: ...le with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plas...

Страница 16: ... W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANA 6SI Replaces 24ANA 5SI 24ANA ...

Отзывы: