Carrier 24ABB3 Скачать руководство пользователя страница 3

3

NOTES:

1.  Symbols are electrical 
     representation only.
2.  Compressor and fan motor 
     furnished with inherent 
     thermal protection.
3.  To be wired in  accordance 
     with National Electric 
     N.E.C. and local codes.
4.  N.E.C. class 2, 24 V circuit, 
     min.  40 VA  required, 
     60 VA on units installed 
     with LLS.
5.  Use copper conductors 
     only.  Use conductors 
     suitable for at least 
     75ºC (167ºF).
6.  Connection for typical 
     cooling only thermostat. 
     For other arrangements  
     see installation instructions.
7.  If indoor section has a 
     transformer with a 
     grounded secondary, 
     connect the grounded 
     side to the BRN/YEL lead.
8.  If any of the original  wire, 
     as supplied must be 
     replaced, use the same or 
     equivalent wire.
9.   Check all electrical 
       connections inside control 
       box for  tightness.
10.  Do not attempt to operate 
       unit service valves have 
       been opened.
11.  Do not rapid cycle 
       compressor.  
       Compressor must be off 
       3 minutes to allow 
       pressures to equalize 
       between high and low 
       side before starting.
12.  It is imperative to connect
      3Ø field power to unit with 
      correct phasing.  The 
      Phase Rotation Monitor 
      will not allow the contactor 
      to be energized if the 
      phasing is not correct.  If 
      phasing is reversed, 
      simply inter change any 
      two of the three power 
      connections on field side.

CONNECTION DIAGRAM

SCHEMATIC DIAGRAM (LADDER FORM)

1.  Compressor damage may occur if system is
      over charged.
2.  This unit is factory charged with R-410A in
      accordance with the amount shown on the
     rating plate.  The charge is adequate for most
      systems using matched coils and tubing not
      over 15 feet long.  Check refrigerant charge
      for maximum efficiency.  See Product Data
      Literature for required Indoor air Flow Rates
      and for use of line lengths over 15 feet.
3.  Relieve pressure and recover all refrigerant
     before system repair or final disposal.  Use all
     service ports and open all flow-control 
     devices, including solenoid valves.
4.  Never vent refrigerant to atmosphere.  Use
      approved recovery equipment.

335875-101 REV. A

 * MAY BE FACTORY INSTALLED

LEGEND

FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION

CONT

CAP

*CH

*CHS

COMP

*CTD
*HPS

IFR

*LLS

*LPS
OFM

CONTACTOR
CAPACITOR 
CRANKCASE HEATER
CRANKCASE HEATER SWITCH
COMPRESSOR
COMPRESSOR TIME DELAY
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR

CAUTION

*LPS

BLU/PNK

* CTD

*HPS

INDOOR BLOWER MOTOR

EXTERNAL

POWER

SUPPLY

24 V

(NOTE #3)

R

G

Y

BRN/YEL

YEL/PNK

BLU/PNK

YEL/PNK

*LLS

BLK

BLK

LOGIC

T1

T3

T2

C
R

IFR

*LPS

* CTD

*LLS

IFR

INDOOR

THERMOSTAT

Y

G

R

C

R

EXTERNAL POWER SUPPLY 24 V

LOGIC

T1

T3

T2

CONT

INDOOR THERMOSTAT  (NOTE #6)

VIO

BLK

BRN/YEL

*HPS

L1

EQUIP

GND

L2

L3

*CH

OFM

COMP

CAP

T2

T1

T3

L1

L3

L2

OFM

575 3Ø

POWER

SUPPLY

GND

EQUIP

T2

T1

T3

BLK

YEL

YEL

BLU

BLK

YEL

CAP

COMP

RED or BLK

RED or BLK

*CH

BRN

CONT

12

22

11

21

13

23

11

21

CONT

23

13

CONT

22

12

CONT

CONDENSING UNIT CHARGING INSTRUCTIONS

For use with units using R-410A refrigerant

COOLING ONLY 

CHARGING PROCEDURE

1.  Only use sub cooling charging method
     when OD ambient is greater than 70ºF 
     and less than 100ºF, indoor temp is 
     greater than 70ºF and less than 80ºF, 
     and line set is less than 80 ft.
2.  Operate unit a minimum of 15 minutes 
     before checking the charge.
3.  Measure liquid service valve pressure by 
     attaching an accurate gauge to the 
     service port.
4.  Measure the liquid line temperature by 
     attaching an accurate thermistor type or 
     electronic thermometer to the liquid line 
     near the outdoor coil.
5.  Refer to unit rating plate for required 
     subcooling temperature.
6.  Find the point where the required sub-
     cooling temperature intersects the 
     measured liquid service valve pressure.
7.  To obtain the required subcooling 
     temperature at specific liquid line 
     pressure, add refrigerant if liquid line 
     temperature is higher than indicated. 
     When adding refrigerant, charge in liquid
     form using a flow restricting device into 
     suction service port.  Recover refrigerant
     if temperature is lower. Allow a tolerance 
     of +/- 3ºF.

REQUIRED LIQUID LINE TEMPERATURE

Required Subcooling

Temperature  (ºF)

Liquid Pressure

at Service

Valve (psig)

6

8

10 12 14 16

251

259
266
274
283
291
299

308
317
326
335
345
354
364
374

76

74

72

70

68

78

76

74

72

70

80

78

76

74

72

82

80

78

76

74

84

82

80

78

76

86

84

82

80

78

88

86

84

82

80

90

88

86

84

82

92

90

88

86

84

94

92

90

88

86

96

94

92

90

88

98

96

94

92

90

100

98

96

94

92

102 100

98

96

94

104 102 100

98

96

384
395

406
416
427
439
450

462

474

106 104 102 100

98

108 106 104 102 100

110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110

120 118 116 114 112

122 120 118 116 114

78

80
82
84
86
88
90

92
94
96
98

100
102
104
106

108
110

112
114
116
118
120

122

124

Fig. 3 – Wiring Diagram — Model size 3 -- 5 tons, 575/3

Отзывы: