19
Table 3 — 09DK Electrical Data
60 HERTZ
50 HERTZ
UNIT
09DK
UNIT
FAN MOTORS
CONTROL CIRCUIT
Volts -3 Ph
Supplied Volts
MCA
MOCP
(Fuse)
No.
FLA (ea)
Volts -1 Ph
Amps
Min
Max
020
500
208/230
187
254
14.8
20
2
6.6
115
7
200
380
342
418
8.8
15
3.9
220
600
460
414
508
7.4
15
3.3
115
100
575
518
632
7.6
15
3.4
115
024
500
208/230
187
254
14.8
20
6.6
115
200
380
342
418
8.8
15
3.9
220
600
460
414
508
7.0
15
3.3
115
100
575
518
632
7.6
15
3.4
115
028
500
208/230
187
254
13.9
20
6.6
115
200
380
342
418
8.8
15
3.9
220
600
460
414
508
7.4
15
3.3
115
100
575
518
632
7.6
15
3.4
115
034
500
208/230
187
254
21.4
25
3
6.2
115
200
380
342
418
12.7
20
3.9
220
600
460
414
508
10.7
15
3.3
115
100
575
518
632
11.0
15
3.4
115
044
500
208/230
187
254
20.1
25
6.6
115
200
380
342
418
12.7
20
3.9
220
600
460
414
508
10.1
15
3.3
115
100
575
518
632
11.0
15
3.4
115
UNIT
09DK
UNIT
FAN MOTORS
CONTROL CIRCUIT
Volts -3 Ph
Supplied Volts
MCA
MOCP
(Fuse)
No.
FLA (ea)
Volts -1 Ph
Amps
Min
Max
024
800
230
207
254
14.4
20
2
6.4
230
7
900
400
342
440
6.7
15
3.0
230
028
800
230
207
254
14.4
20
6.4
230
900
400
342
440
6.7
15
3.0
230
034
800
230
207
254
20.8
30
3
6.4
230
900
400
342
440
9.7
15
3.0
230
044
800
230
207
254
20.8
30
6.4
230
900
400
342
440
9.7
15
3.0
230
FLA
—
Full Load Amps
MCA
—
Minimum Circuit Amps (for wire sizing). Complies with
NEC (National Electrical Code, U.S.A.) Section 430-24.
MOCP —
Maximum Overcurrent Protective Device (Amps).
Fig. 21 — Wiring Diagram, Power Schematic; 09DK020-044
FC —
Fan Contactor
FM —
Fan Motor
TB —
Terminal Block Connection
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Splice
Factory Wire
Field Control Wiring
Field Power Wiring
LEGEND
Содержание 09DK Series
Страница 23: ......