Table 1 — Electrical Data — Compressor Motor With Circuit Breaker
LEGEND
*Refer to physical data table to match compressor with correct com-
pressor or water-cooled condensing unit.
NOTES:
1. Compressor MTA and RLA values are maximum figures.
2. LRA values for PW second winding =
1
/
2
the LRA – XL value.
3. 3-Pole XL circuit breakers shown, other 3-Pole XL alternates
and 6-Pole PW breakers available. Terminal lugs for circuit
breakers available in package 06EA660152 (not shown).
4. Recommended RLA value shown is determined by: circuit
breaker must trip value
÷
1.40. Use this recommended (and
minimum) RLA value to determine nameplate stamping, mini-
mum contactor sizing, and wire sizing. RECOMMENDED RLA
FOR 06E COMPRESSORS EQUALS: MUST-TRIP (MTA) OF
CARLYLE APPROVED OVERCURRENT DEVICE BEING
USED
÷
1.40
5. Compressor operating amps at any specific condition can only
be determined from a performance curve.
6. Ohm values for resistance are approximate and shown for ref-
erence purposes only. Motors from different vendors and
motors of different efficiencies can differ up to 15% from data
shown.
7. Electrical data for compressor part numbers 06ER, 06EM and
50 Hz models (not shown) are available from Carrier Sales
Representative.
COMPRESSOR MOTOR DATA
CIRCUIT BREAKER
Compressor
Part Number
06E*
Voltage
(3 Ph - 60 Hz)
Hp
Maximum
Must Trip
Amps
Maximum
RLA
LRA-XL
LRA-PW
(first
winding)
Motor
Winding
Resistance
(Ohms)
Recommended
Circuit Breaker
Part No.
MHA MTA LRA
Recommended
RLA
A
250
208/230
20
108
87
345
207
0.32
HH83XB336
91
104
350
74.3
575
45
36
120
72
2.2
XA461
33
38
124
27.1
460
54
44
173
104
1.3
XA424
42
49
175
35.0
265
208/230
25
140
112
446
268
0.27
HH83XC509
110
127
420
90.7
575
57
46
164
98
1.6
XA469
46
53
164
37.9
460
70
56
223
134
1.1
XA426
55
643
210
45.7
275
208/230
30
168
135
506
304
0.22
HH83XC539
142
163
507
116.4
575
65
52
176
106
1.3
XA430
50
58
168
41.4
460
84
68
253
152
0.9
XA425
63
73
210
52.1
299
208/230
40
236
189
690
414
0.15
HH83XC537
187
215
636
153.6
575
94
75
276
165
1.0
XA551
74
85
236
60.7
460
118
95
345
207
0.58
XA550
92
106
295
75.7
LRA
—
Locked Rotor Amps
MHA —
Must Hold Amps
MTA
—
Must-Trip Amps
PW
—
Part-Winding (Start)
RLA
—
Rated Load Amps
XL
—
Across-the-Line (Start)
Fig. 5 — Component Location
LEGEND
C1
—
Compressor Contactor
C2
—
Compressor Contactor (PW)
CCB
—
Compressor Circuit Breaker
CHR
—
Crankcase Heater Relay
CR
—
Control Relay
FU
—
Fuse
GND
—
Ground
HPS
—
High-Pressure Switch
LPS
—
Low-Pressure Switch
NEC
—
National Electrical Code
NEMA —
National Electrical
Manufacturer’s Association
OPS
—
Oil Pressure Switch
POR
—
Pumpout Relay
TB
—
Terminal Block
TDR
—
Time Delay Relay
TM
—
Timer Motor
TR
—
Timer Relay