Code 30
Reset input failure (4 to 20
Code 31
Demand limit input failure (4 to 20
These codes apply only if unit is configured for these
functions. If
signal is less than 4 or more than
20
reset or demand limit function is disabled and unit
functions normally. If
signal returns to the acceptable
range, function is automatically enabled.
Code 32
Loss of communication with compressor
relay module (DISO-LV)
Code 33
Loss of communication with EXV relay
module (DSIO-EXV)
If communication is lost with either of these modules,
unit shuts down without
This alarm resets
auto-
matically when communication is restored. The unit starts
up normally after alarm condition is reset. Probable cause
of condition is a faulty or improperly connected plug, wir-
ing error, or faulty module.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21
supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the
transformer supplying the DSIO-EXV module; or the
transformer supplying PS 1 for the transformers. These
transformers should not be grounded, or serious damage to
controls can result.
Check
to
be sure the
are
not grounded.
NOTE: If a blank
module is downloaded without be-
ing connected to the modules DSIO, this alarm is
energized.
Code 34
Loss of communication with 4 In/4 Out module
This applies only if one or more of the following options
are used:
external temperature reset
l
4-20
temperature reset
l
external switch controlled dual set point
l
switch controlled demand limit
l
4-20
demand limit
l
hot gas bypass
If communication is lost with 4 IN/4 OUT module, the
unit shuts off automatically, after finishing
Reset
of alarm is automatic when communication is restored. Start-up
after alarm is remedied follows a normal sequence. Proba-
ble cause of condition is a faulty or improperly connected
plug, wiring error, or faulty module.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21
supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT; the
trans-
former supplying the DSIO-EXV module, or the
trans-
former supplying PS 1 for the transformers.
These transformers
should
be grounded, or serious damage to controls can
result. Check to be sure the transformers are not grounded.
Code 36
Low refrigerant pressure, Circuit A
Code 37
Low refrigerant pressure, Circuit B
If suction pressure transducer senses a pressure below set
point for more than 5 minutes at start-up or more than
2 minutes during normal operation, affected circuit shuts
down without going through the
process. Reset is
automatic when pressure reaches 10 psig above set point if
there have been no previous occurrences of this fault on the
same day. If this is a repeat occurrence on same day, then
reset is manual, with LOCAL/ENABLE-STOP-CCN switch,
Factory configured set point is 27 psig for standard chillers
and 12 psig for brine chillers.
Possible causes of fault are low refrigerant charge, faulty
EXV, plugged filter drier, or faulty transducer.
Code 38
Failure to pump out, Circuit A
Code 39
Failure to pump out, Circuit B
The
process is terminated when saturated suc-
tion temperature is 10” F (5.5” C) below temperature at
51
ginning of
or
F (5.5” C) below leaving water
temperature or reaches a saturated suction temperature of
-15 F (-26 C). If appropriate saturated suction temperature
is not met within 3 minutes (on 2 consecutive tries}, circuit
shuts down without
Reset is manual with LOCAL/
ENABLE-STOP-CCN Switch, and start-up follows normal
sequence.
Possible causes for this alarm are a bad thermistor or trans-
ducer or a faulty EXV.
Code 40
Low oil pressure, Circuit A
Code 41
Low oil pressure, Circuit
If oil pressure differential is less than set point for more
than 2 minutes at start-up, or more than one minute during
normal operation, affected circuit shuts down without go-
ing through
process, Reset is manual with LOCAL/
ENABLE-STOP-CCN switch, and start-up follows normal
sequence.
Factory configured differential oil pressure is
6 psig.
Possible causes of fault are faulty compressor, EXV, crank-
case heater or transducer, refrigerant overcharge, insuffi-
cient oil charge, or tripped circuit breaker.
Code 42 Cooler freeze protection
If cooler entering or leaving water temperature is below
34 F (1.1 C) for water or more than 8” F (4.4” C) below set
point for brine, unit shuts down without
Chilled
water pump continues to run if controlled by chiller con-
trols. Reset is automatic when leaving water temperature
reaches
F (3” C) above set point, providing there has
been no prior occurrence of this fault the same day. If fault
has occurred previously the same day, reset is manual with
LOCAL/ENABLE-STOP-CCN switch.
Possible causes of fault are low water flow or faulty
thermistor.
Code 43 Low water flow
If any compressors are operating and entering water tem-
perature is 3” F (1.7” C) or more below leaving water tem-
perature for more than one minute, unit shuts down without
Chilled water pump also shuts down. Reset is
manual with LOCAL/ENABLE-STOP-CCN switch, and
start-up follows normal sequence.
This is a suitable method for sensing low water flow be-
cause entering water thermistor is in the cooler shell and
responds more quickly to compressor operation than the leav-
ing water thermistor in the leaving water nozzle, Possible
causes of fault are faulty chilled water pump, control or
thermistor.
Code 44
Low cooler suction temperature, Circuit A
Code 45
Low cooler suction temperature, Circuit B
If saturated suction temperature is less than 32 F (0°C)
and is 20” F (11” C) for water or 30” F
C) for brine or
more below leaving fluid temperature, mode 14 is dis-
played. Unit continues to run, but additional compressors
are not allowed to start, If condition persists for more than
10 minutes, fault code is displayed, and unit shuts down
without
Reset is manual with
STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor.
Code 46
High suction superheat, Circuit A
Code 47
High suction superheat, Circuit B
If EXV is fully open, suction superheat is greater than
75 F (42 C) and saturated evaporator temperature is less
than MOP (maximum operating pressure) for more than 5
minutes, unit shuts down after normal
process.
Reset is manual with LOCAL/ENABLE-STOP-CCN switch,
and start-up follows normal sequence.
Содержание 040-420
Страница 75: ......