T-372
7–42
6. Place the ice bath in a location near sensors (see
). For Return Sensors, place the ice bath on
an elevated platform (ladder) of appropriate height.
Figure 7.29 Ice Bath
7. Once temperature stability is ensured, submerge the sensors in the ice water slurry. Make certain that the
sensors do not contact the container sides or bottom, or each other. Continuously stir the slurry mixture
during calibration.
8. Ensure that the Ice bath is at 0°C (32°F) using the calibrated reference thermometer. Confirm that the
sensor readings have stabilized and the sensors are /- 0.3°C (0.5°F). The readings can be taken
from the Uncal column in the Current Probe Offset Temperatures table.
9. Then, after confirming the sensor readings have stabilized, click on the Start Cal button (see
).
After clicking Start Cal, the process begins automatically and will complete in less than 5 minutes.
Figure 7.30 DataLINE - Start Cal Button
10. Continue to stir the ice bath during the testing. Calibration will fail if the stability cannot be achieved or the
sensor offset is greater than 0.3°C (0.5°F). Replace the sensor and recalibrate the sensors. See the
for sensor replacement procedures.
Содержание PrimeLINE 69NT40-571-001
Страница 2: ......
Страница 4: ......
Страница 14: ......
Страница 36: ......
Страница 110: ......
Страница 116: ......
Страница 171: ...8 1 T 372 SECTION 8 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 1 Legend Standard Unit Configuration ...
Страница 172: ...T 372 8 2 ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS Figure 8 2 Schematic Diagram Based on Drawing 62 11957 ...
Страница 176: ......
Страница 178: ......
Страница 180: ......
Страница 184: ......
Страница 185: ......