INSTALLATION, OPERATION, & MAINTENANCE

WALL MOUNTED PROPELLER FANS

BELT AND DIRECT DRIVE

Models LW/LM, LR/LN, LJ/LK

INTRODUCTION

This manual is to be used to aid in the proper installation, operation, and maintenance of the above Carnes fans. This 
information is meant to serve as a general guide. Due to the variety and complexity of many installations it is the 
responsibility of the purchaser to assure that these procedures are handled by qualified personnel.

GENERAL CAUTIONS

 

1. 

Installation of this fan requires experienced personnel with knowledge of structural strength, mechanical setup

   

and electrical wiring. Do not attempt installation without qualified personnel.

 

2.

  Do not operate this fan in an environment or atmosphere where combustible or flammable materials, gasses or

   

fumes are present unless it has been specifically designed and manufactured for use in that environment.

MECHANICAL INSTALLATION CAUTIONS

 

1.

  Turn the propeller by hand to check clearances. If needed, adjust the bearing or motor position to center the

   propeller.
 

2.

  On belt drive units, check that belts are aligned and tensioned properly (see Maintenance section.)

 

3.

  Check that set screws are tight and shaft keys are in place.

ELECTRICAL INSTALLATION CAUTIONS

 

1.

  Be sure the supply voltage matches the motor plate voltage. On dual voltage motors, check the motor wiring to 

   

determine the voltage.

 

2.

  Fans must be grounded.

 

3.

  Keep all wiring clear of rotating components and moving parts such as powered or gravity dampers.

 

4.

  Make sure power is locked 

OFF

 at the service entrance before wiring or otherwise approaching the fan.

 

5.

  Electrical work must be done in accordance with local and/or national electrical code by a qualified electrician.

INSTALLATION

 

1.

  This fan is designed to be mounted in a wall or other building opening.

 

2.

  This fan is 

either

 built for supply 

or 

exhaust application.  Refer to the Model Number or dimensional drawings in this 

 

manual if there is any question.

 

3.

  Any optional dampers should be mounted to allow free and unobstructed operation. Allow a minimum of 8” clearance 

 

between the fan and damper.

 

4.

  Anchor the fan or fan structure securely to the wall, this will usually require lag bolts. Use all of the provided mounting 

 holes.

 

5.

  Refer to drawings on page 6 for standard installation.

START-UP

 

1. 

Operate the fan briefly to check for proper rotation direction. Incorrect fan rotation will over  heat the fan motor.

 

2. 

Check the operation of any dampers. Be sure they can open and close fully.

 

3.

  During the first few hours of operation, periodically check the fan for smooth operation.

 

4.

  After the first few hours of operation, shut the fan down and lock the power 

OFF

. Check sheave and propeller set 

   

screws for tightness. On belt drive units, check the belt tension. (see Maintenance section)

FORM 1426-C, Page 1

MECHANICAL AND ELECTRICAL START-UP CAUTION

Be sure the Inlet, Outlet and ductwork are open and free of loose objects

CARNES COMPANY    448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040    Phone: (608)845-6411    Fax: (608)845-6504    www.carnes.com