UDM 35/40 PANEL METER USER MANUAL 
 
 

 
 

11

 
Navigating & Programming within the Linearization Menu 

 
 

As 

 appears, press 

 followed by 

 and 

 keys to choose to 

ignore or enable linearization 

.   Press 

 to confirm your choice 

and advance to next step.  If you chose YES, you will be prompted to 

enter the number of Linearization Points,  

 using the escape 

button 

 to select the position, and the up 

 /down 

  buttons to select 

the numerical value, from 01-16.  Press enter 

 to confirm and advance.  

Next, the correlation between the inputs and outputs must be defined in 
the program.  
 
“In.01” will be displayed.  Press 

 to toggle through the positions, and 

use the 

 and 

 keys to select the value.  Press 

 to confirm and 

advance.  “Ou.01” will display next.  Again, using the escape key 

toggle to the appropriate position.  Use the 

 and 

 keys to select the 

value.  Press enter 

 to confirm and advance.  Repeat this procedure for 

each set of Inputs and Outputs, up through a maximum of 16.  Press the 
enter key 

 to confirm.  Press 

 to advance to the next program step 

sequence. 
 

 
Alarm Set-point Programming 

 
 
 

Up to 4 alarm set-points may be configured.  You may configure each set 

point using the following parameters, in order, as shown below: 
 

 

 

Minimum set-point limit 

 

 

 

Maximum set-point limit 

 

  

Set-point 

setting 

 

Содержание UDM 35 - PROGRAMMING

Страница 1: ...CARLO GAVAZZI A u t o m a t i o n C o m p o n e n t s UDM 35 40 Digital Panel Meter Programming Guide...

Страница 2: ...perature Compensation 6 7 Display Configuration 7 Scaling the Inputs 8 Decimal Point Position 9 Display Span Configuration 9 Linearization 11 12 Alarm Set Point Configuration 12 16 Digital Filtering 1...

Страница 3: ...DMSoft or PC HyperTerminal Powerful variable control by means of up to four 4 alarm outputs Alarms can be up down functions with automatic reset up down with manual reset and down alarm with disable f...

Страница 4: ...a description and the UDMxx display symbol for each basic parameter grouping Password for access to programming Input Probe Selection Signal Range current voltage temperature resistance Cold Junction...

Страница 5: ...d value from 5000 to 9000 allow direct access to alarm set points only Negotiating the Programming Menu After password is verified you are in the Programming Mode After approximately 20 seconds the un...

Страница 6: ...mately 20 seconds to begin programming before the unit reverts back to run mode To enter a unique password see Access to Programming Mode above Input Selection Press the key once to advance to Input W...

Страница 7: ...s 0000 is selected Auto will be displayed and the value will be automatically calculated from 100ms 999 9 ms Press to confirm Press to advance to next program step sequence Cold Junction Compensation...

Страница 8: ...5 base unit displays may be configured as 3 digit 1999 or 3 digit dummy zero 9990 When diSP is displayed press Then press keys to make selection Press to confirm Press to advance to next program step...

Страница 9: ...with a full scale 20mA 19 99mA setting it is possible to select an electrical input range from 4 00mA Lo E to 19 99mA Hi E by proceeding as follows When is displayed press LoE will appear Using the ke...

Страница 10: ...user to define the actual display span in engineering units corresponding to the previously defined electrical input range HiE and LoE The Lod value represents the minimum displayed value Hid represen...

Страница 11: ...nto 9 segments 9 segments 1 corresponding to the vertical axis The menu must be activated and the number of linearization points set 10 in this example Then the input output coordinates must be determ...

Страница 12: ...st be defined in the program In 01 will be displayed Press to toggle through the positions and use the and keys to select the value Press to confirm and advance Ou 01 will display next Again using the...

Страница 13: ...tion Off Delay Value 0 255s On Delay Value 0 255s Relay Selection normally energized or de energized Alarm Type off down up up with latch down with latch Color of display during alarm red orange green...

Страница 14: ...lue for each position When completed press enter to confirm and advance to next programming sequence Maximum Set Point The highest value above which it is not possible to program a set point Maximum S...

Страница 15: ...Off Delay When Off Delay is displayed you may opt to choose a value of 0 255 seconds Use the key to toggle to the desired position and select the correct value with the keys Press enter to confirm an...

Страница 16: ...he displayed value Fluctuations can also be introduced when the resolution of the displayed value is higher than the input resolution The use of a digital filter results in higher stability of the dis...

Страница 17: ...value to enter Press to confirm Press to advance to the next program step sequence Analog Output Programming Many times the displayed value must be retransmitted as an analog output The relationship b...

Страница 18: ...ect 1 Press to toggle to each remaining position and select 0 for each When completed press to confirm and advance to the next program sequence will be displayed Using the keys choose either A for 20m...

Страница 19: ...scaled to indicate Fahrenheit values by using the following guidelines The LoE and HiE are always expressed as Celsius values To display Fahrenheit values manually convert the LoD to a Fahrenheit val...

Страница 20: ...elect to dedicate a Command signal contact closure from the input module terminals 6 7 to perform one of the following C1 HOLD Function C2 Disable Keypad C3 Reset latch Alarms Press to select Command...

Страница 21: ...T module only You will see the connector port on the inside face of the module 2 With the UCABLE now installed on the Input module connect a line cord power source to the power supply module BPH or BP...

Страница 22: ...https www gavazzionline com images UDM40DS5ENG0404 pdf UDM3540 Program Flow Chart UDM3540 Input Output Modules UDM3540 FAQ English Panel Meter Selection Guide https www gavazzionline com usameters ht...

Отзывы: