Motor Controllers AC Variable Frequency Drives
RVBS
Specifications are subjected to change without notice.10/08/2021
14
Voltage Gain
C12
0x60C
Frequency at Minimum
Analog Input
0.0 to F03 (Maximum
Frequency 1)
0
O
R/W
Y
0.1
Hz
C13
0x60D
Frequency at Maximum
Analog Input
0.0 to F03 (Maximum
Frequency 1)
0
O
R/W
Y
0.1
Hz
C14
0x60E
Minimum Analog Input
Offset
0.0 to 100.0
0
O
R/W
Y
0.1%
C15
0x60F
Maximum Analog Input
0.0 to 100.0
1000
O
R/W
Y
0.1%
C16
0x6010
Analog Input Start
Frequency
0: C12:
1: 0Hz
0
O
R/W
Y
-
C17
0x6011
Analog Input Low-pass
Filter Gain
1 to 8
4
O
R/W
Y
-
Motor parameter setting (P group)
P01
0x0201
Motor (Rated capacity)
0.01 to 30.00
40/75
X
R/W
Y
0.01k
W
P02
0x0202
Motor (Rated current)
0.00 to 100.0
210/329
X
R/W
Y
0.01A
rms
P03
0x0203
Motor (Auto-tuning)
0: Disable
1: Tune when the
motor stops
(%R1, %X)
0
O
R/W
Y
-
P04
0x0204
Motor (No-load current)
0.00 to 50.00
152/211
X
R/W
Y
0.01A
rms
P05
0x0205
Motor (%R1)
0.00 to 50.00
847/720
X
R/W
N
0.01
%
P06
0x0206
Motor (%X)
0.00 to 50.00
1134/894
X
R/W
N
0.01
%
P07
0x0207
Motor (Slip
compensation gain for
driving)
0.0 to 200.0
1000
O
R/W
N
0.1%
P08
0x0208
Motor (Slip
compensation response
time)
0.01 to 10.00
100
O
R/W
N
0.01S
ec.
P09
0x0209
Motor (Slip
compensation gain for
braking)
0.0 to 200.0
1000
O
R/W
N
0.1%
P10
0x020A
Motor (Rated slip
frequency)
0.00 to 15.00
240/233
O
R/W
Y
0.01H
z
Additional motor control functions (H group)
H01
0x0301
Data Initialization
0: Disable initialization;
1: Initialize all function
code data to the
factory defaults;
2: Initialize motor 1
parameters
0
O
R/W
Y
-
H02
0x0302
Auto-reset (Times)
0: Disable;
1 to 10: Times
0
O
R/W
N
Time
s
H03
0x0303
Auto-reset (Reset
interval)
0.5 to 20.0
50
O
R/W
N
0.1Se
c.
H04
0x0304
Acceleration/Deceleratio
n Pattern
0: Linear;
1: S-curve (Preset);
2: S-curve (User)
0
O
R/W
N
-
H05
0x0305
Rotational Direction
Limitation
0: Disable;
1: Enable (Reverse
rotation inhibited);
2: Enable (Forward
rotation inhibited)
0
O
R/W
Y
-
H06
0x0306
Deceleration Mode
0: Normal
deceleration;
1: Coast-to-stop
0
O
R/W
N
-
H07
0x0307
Instantaneous
Overcurrent Limiting
(Mode selection)
0: Disable;
1: Enable
1
O
R/W
N
-
H08
0x0308
1st S-Curve acceleration
range (At starting)
0 ~ 50%
10
O
R/W
N
-
H09
0x0309
2nd S-Curve
acceleration range (At
arrival)
10
O
R/W
N
-
H10
0x030A
1st S-Curve deceleration
range (At starting)
10
O
R/W
N
-
H11
0x030B
2nd S-Curve
deceleration range (At
arrival)
10
O
R/W
N
-
Содержание RVBS
Страница 1: ...RVBS Variable Frequency Drive Rev 1 0...