In case of an RG..N replacement, or any changes to the NRG bus chain, the RG..Ns have to be readdressed. Follow
the procedure below (Figure 6) to readdress the RG..Ns on the NRG bus chain manually. Alternatively, auto-
addressing can also be performed digitally, check Communications section for further information.
Figure 6 Manual Auto addressing procedure
STEP 1: Hold the blue button while inserting the power supply plug of the NRGC-PN
STEP 2: Release the blue button once the Alarm LED flashes ON
3.4
Grounding
Connecting the protective ground for the NRG Controller
The NRG controller is equipped with a metal contact clip at the back of the product to provide functional grounding
via the Din Rail. The Din Rail must be conductive and grounded. Shielded Cat 5e cables fitted with an outer metallic
shell should be used. The shell should be connected to the wire screen of the cable.
Figure 7 Metal din clip on NRG controller for functional grounding
STEP 1
STEP 2